| Plan Review Notes For Permit 07100119 |
| Permit Number |
07100119 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-25 09:15:11 | DENIED; | | | 1. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | | 2.WATER RISER DIAGRAM REQUIRED PER FBC BUILDING CHAPTER | | | 1 SECTION 106.3.5.1.3(3) | | | 3. SHOW 5' TURNING RADIUS ON PLANS ( IN BATHROOMS) AND | | | L & W MESSUREMENTS. | | | 4. BREAK SINK IS ONLY SHOWN ON PLUMBING PAGE. IF BREAK | | | SINK IS TO BE INSTALLED IT MUST MEET ADA REQUIREMENTS | | | OF CHAPTER 11 OF THE BUILDING CODE. SEE SECTIONS | | | 11-4.24.1 THRU 11-4.24.7. SHOW DETAIL WITH ALL REQUIRED | | | MEASUREMENTS ON PLANS. | | | 5. A CUP DISPENSER SHOULD BE INSTALLED WITH THE | | | HANDICAP DRINKING FOUNTAIN FOR PEOPLE WITH BAD BACKS. | | | SEE SECTION 11-4.1.3(10). | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|