| 2007-10-17 14:08:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLEASE SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL |
| | PLAN, SEE 2004 FBC/M 403.2. |
| | |
| | 2) PLEASE SHOW HOW BATHROOM EXHAUST FANS WILL COMPLY |
| | WITH 2004 FBC/M 403.2.1 (3) |
| | *** 2004 FBC/M 403.2.1 (3) WHERE MECHANICAL EXHAUST IS |
| | REQUIRED BY TABLE 403.3 , RECIRCULATION OF AIR FROM |
| | SUCH SPACES SHALL BE PROHIBITED. ALL AIR SUPPLIED TO |
| | SUCH SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN |
| | EXCESS OF THAT REQUIRED BY TABLE 403.3 . |
| | (EXAMPLE) FAN MAY RUN CONTINUOUSLY, FAN MAY BE |
| | CONTROLLED BY A SWITCH AND PARALLEL WITH AIR HANDLER |
| | UNIT SO THE FAN TURNS ON WHEN EVER SOMEONE IS IN THE |
| | BATHROOM OR WHEN EVER THE AIR HANDLER TURNS ON, OR THE |
| | SUPPLY AIR DUCT MAY BE REMOVED FROM THE BATHROOM AND A |
| | TRANSFER DUCT BE INSTALLED. |
| | |
| | 3) PLEASE SHOW HOW THE DUCT SMOKE DETECTOR WILL COMPLY |
| | WITH 2004 FBC/M 606.4.1 OR THE EXCEPTIONS. |
| | *** 2004 FBC/M 606.4.1SUPERVISION. |
| | THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE |
| | ALARM SYSTEM. THE ACTUATION OF A DUCT SMOKE DETECTOR |
| | SHALL ACTIVATE A VISIBLE AND AUDIBLE SUPERVISORY SIGNAL |
| | AT A CONSTANTLY ATTENDED LOCATION. |
| | EXCEPTIONS: |
| | 1. THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR |
| | ACTIVATES THE BUILDING = S ALARM-INDICATING APPLIANCES. |
| | |
| | 2. IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH |
| | A FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR |
| | SHALL ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL IN AN |
| | APPROVED LOCATION. DUCT SMOKE DETECTOR TROUBLE |
| | CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE SIGNAL |
| | IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED AS AIR |
| | DUCT DETECTOR TROUBLE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |