| 2007-10-14 11:57:01 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | |
| | 2) NOTE: PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR |
| | DESIGN PROFESSIONAL AS REQUIRED PER FAC 61G15-23.002. |
| | |
| | 3) NOTE: PLEASE SUBMIT A CODE COMPLIANT RISER FOR |
| | EXISTING AND NEW. PLEASE SEE THERE ARE SEVERAL ITEMS |
| | WHICH ARE NOT CORRECT. |
| | FOR EXAMPLE: CONDUCTOR SIZES ON FEEDERS WHICH ARE SHOWN |
| | AS 5/0'S AT SEVERAL LOCATIONS WHICH IS NOT POSSIBLE AS |
| | THERE ARE NO 5/0 CONDUCTORS BASED ON AWG (AMERICAN WIRE |
| | GAUGE). PLEASE SEE 240.4 AND 310.16 AND ADJUST ALL NEW |
| | AND EXISTING CONDUCTORS ON RISER FOR CODE COMPLIANCE. |
| | PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS. |
| | PLEASE LABEL AND CORRELATE PANELS AND EQUIPMENT ON |
| | RISER. (HPE, MAIN ETC) |
| | PLEASE COMPLETE RISER FOR EXISTING AND NEW.215.5, 230, |
| | 240.4, 310.16 ETC |
| | |
| | 4) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 408.4 AS CIRCUITS NEED TO BE SPECIFIC TO ROOMS AND |
| | AREAS IN WHICH THEY FEED. |
| | PLEASE SEE 700.12F AS NOTED ABOVE FOR EM/EXT LTS. |
| | |
| | 5) NOTE: PLEASE SEE 210.62 AND 220.43 FOR MISSING STORE |
| | FRONT WINDOW RECEPTACLES REQUIRED WHICH ARE NOT SHOWN |
| | AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE SEE 600.5 FOR SIGN CIRCUIT. IS THE ONE |
| | SHOWN ON EXISTING PANEL *MAIN* THE SAME AS HPE? PLEASE |
| | CORRELATE. |
| | |
| | 7) NOTE: PLEASE SEE PANEL MAIN, INDICATES A 90AMP |
| | BREAKER ON #8AWG WHICH IS NOT SUFFICIENT. |
| | PLEASE COORDINATE AND COMPLETE. |
| | |
| | 8) NOTE: PLEASE KNOW ONCE THE ADDRESSING REVIEW IS |
| | COMPLETED, A NEW SUITE/UNIT WILL BE GIVEN AND THIS |
| | NEEDS TO BE STATED ON PLANS. |
| | THE SCOPE WORK ON TITLE BLOCK MENTIONS NEW RETAIL |
| | STORE, YET PLANS CALL FOR SPACE TO BE PART OF FUTURE |
| | BUILD OUT? |
| | PLEASE CLARIFY IF THIS IS TWO NEW SPACES BEING CREATED |
| | FROM THE EXISTING STORE. |
| | FBC 106.1.2, 110.1.2. |
| | FAC 61G15-23.002 |
| | |
| | 9) NOTE: PLEASE CLARIFY IF THIS EXISTING BUILDING/SPACE |
| | HAS A FIRE ALARM SYSTEM. IF YES, PLEASE INDICATE THE |
| | LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE PER FBC |
| | 11-4.28.1,.2 AND .3(4). |
| | **(EVEN AS FA WOULD BE UNDER SEPARATE PERMITS) |
| | ** (THIS IS ONLY NOTED AND THIS REVIEWER IS NOT STATING |
| | THAT A FA SYSTEM IS REQUIRED. (ONLY REVIEWING FOR ADA |
| | COMPLIANCE IF SYSTEM EXISTS OR WILL BE REQUIRED PER |
| | BUILDING REVIEWER OR FIRE MARSHAL) |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |