2007-10-26 09:49:22****CORRECTIONS****
 ***RESUB SUBMITTED BY EMAIL***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ENGINEER SPECIFIES A SYSTEM WHICH REFERS TO GENERAL
 LIMITATION #9.SEE NOA, NO ENHANCED FASTENING ALLOWED;
 THE SYSTEM IS LIMITED TO -52.5. (NOT ADDRESSED)
  
 2.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 3 AND
 ZONE 1.IF 9 IS THE NUMBER NEEDED FOR -52.5 PSF, HOW
 COULD THAT BE SUFFICIENT FOR -114.9PSF? (REVISED, OK)
  
 3.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 1.THE
 NOA STATES THAT THERE SHOULD BE ONE PER 3.2 SQUARE
 FEET.FOR A 32SF BOARD, THAT SHOULD BE 10 FASTENERS
 (32/3.2=10), NOT 9.WHEN RESUBMITTING, PLEASE SUBMIT
 CALCULATIONS TO SHOW HOW YOU HAVE ARRIVED AT THE
 FASTENING PATTERNS FOR ZONES 1 AND 3.IT IS UNCLEAR
 HOW YOU HAVE DETERMINED THE FASTENING WHICH IS IN
 CONFLICT WITH THE NOA. (REVISED, OK)
  
 4.ADDRESSED
  
 A SET HAS BEEN RETAINED.WHEN RESUBMITTING, PLEASE
 SUBMIT TWO COMPLETE SETS OF PERMIT DOCUMENTS (INCLUDING
 TWO NOAS).
  
 PLEASE PROVIDE TWO COMPLETE SIGNED, SEALED, ORIGINALS
 WITH TWO NOAS