2007-10-24 07:51:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ENGINEER SPECIFIES A SYSTEM WHICH REFERS TO GENERAL
 LIMITATION #9.SEE NOA, NO ENHANCED FASTENING ALLOWED;
 THE SYSTEM IS LIMITED TO -52.5.
  
 2.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 3 AND
 ZONE 1.IF 9 IS THE NUMBER NEEDED FOR -52.5 PSF, HOW
 COULD THAT BE SUFFICIENT FOR -114.9PSF?
  
 3.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 1.THE
 NOA STATES THAT THERE SHOULD BE ONE PER 3.2 SQUARE
 FEET.FOR A 32SF BOARD, THAT SHOULD BE 10 FASTENERS
 (32/3.2=10), NOT 9.WHEN RESUBMITTING, PLEASE SUBMIT
 CALCULATIONS TO SHOW HOW YOU HAVE ARRIVED AT THE
 FASTENING PATTERNS FOR ZONES 1 AND 3.IT IS UNCLEAR
 HOW YOU HAVE DETERMINED THE FASTENING WHICH IS IN
 CONFLICT WITH THE NOA.
  
 4.WHEN RESUBMITTING, ENGINEER IS TO PROVIDE AN
 EXPLANATION AS TO HOW HE HAD ARRIVED AT DESIGN
 PRESSURES FROM FIRST REVIEW AND FASTENING PATTERNS FROM
 SECOND REVIEW (JUSTIFICATION FOR SIGNED, SEALED, DATED
 ENGINEERING CALCULATIONS SUBMITTED).
  
 A SET HAS BEEN RETAINED.WHEN RESUBMITTING, PLEASE
 SUBMIT TWO COMPLETE SETS OF PERMIT DOCUMENTS (INCLUDING
 TWO NOAS).