| Plan Review Notes For Permit 07100087 |
| Permit Number |
07100087 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-10 14:30:05 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | 2} INDICATE COMPLIANCE WITH 600.6 DISCONNECTS | | | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUTLINE | | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | | UNGROUNDED CONDUCTORS. SIGNS AND OUTLINE LIGHTING | | | SYSTEMS LOCATED WITHIN FOUNTAINS SHALL HAVE THE | | | DISCONNECT LOCATED IN ACCORDANCE WITH 680.12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|