| 2007-10-16 14:38:12 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS TO ALL |
| | CUT SECTIONS OF PIPE ON THE RESUBMITTAL AND INDICATE |
| | THE LOCATION OF THE EXISTING POOL HEATER. SEE ATTACHED |
| | PERMIT INFORMATION TO THE GAS COMMENTS INDICATING GAS |
| | TO AN EXISTING POOL HEATER. |
| | |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: PERMIT INFORMATION INDICATES EXISTING GAS TO A |
| | POOL HEATER, THE BTU LOAD FOR THE EXISTING SYSTEM NEEDS |
| | TO BE ON THE RESUBMITTAL. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: LONGEST LENGTH OF THE SYSTEM NEEDS TO BE |
| | INDICATED ON THE PLANS, THIS INCLUDES THE POOL HEATER. |
| | IF GAS PIPING TO THE EXISTING POOL HEATER IS LONGER |
| | THAN THE PROPOSED ADDITION GAS OF 25 FEET GAS SYSTEM |
| | WILL NEED TO BE RESIZED. |
| | |
| | END OF COMMENTS: |
| | |