2008-10-03 08:43:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. DESIGN PRESSURE SPECIFIED BY ENGINEER IS -67.9, BUT
 THE CHART FOR -40 TO -60PSF WAS USED (SHEETS 10 AND
 16). THE CHART FOR DESIGN PRESSURES -60 TO -90 ON
 SHEETS 10 AND 17 SHOULD BE USED. PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR SCHEDULES. IN THIS CASE, IT APPEARS
 THAT YOU ARE USING 8 TOP, ALT 8 BOTTOM. PLEASE NOTE
 THAT THIS REVIEW WOULD NOT HAVE FAILED FOR THIS REASON
 ONLY, BUT SPECIFYING THE INFORMATION CORRECTLY ASSISTS
 THE PLAN REVIEWER. AS THE INSTALLATION SCHEDULE MUST BE
 REVISED DUE TO OTHER COMMENTS, PLEASE REVISE THIS
 COLUMN.
  
 3. A 2" EDGE DISTANCE FOR BLOCK REQUIRES A FACTOR OF
 .5, SEE SHEET 10. PLEASE REVISE INSTALLATION SCHEDULE.
  
 DUE TO THE NUMBER OF TIMES THIS REVISION HAS FAILED, IT
 IS SUGGESTED THAT THE QUALIFIER CONTACT ME PRIOR TO
 RESUBMITTAL. IF THE QUALIFIER CONTACTS ME, I WOULD
 SCHEDULE AN APPOINTMENT TO DO A PRELIMINARY REVIEW
 PRIOR TO RESUBMITTAL. THIS IS OPTIONAL, SUBJECT TO THE
 QUALIFIER'S DISCRETION.
  
  
  