| 2008-07-11 13:45:47 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT |
| | ISSUANCE.A PHOTOCOPY MACHINE HAS BEEN PROVIDED IN THE |
| | LOBBY FOR THIS PURPOSE. |
| | |
| | 2ND REVISION REVIEW, ONLY ONE SET OF FLOOR PLAN AND |
| | INSTALLATION SCHEDULE PROVIDED.THIS CANNOT BE ISSUED |
| | UNLESS TWO COMPLETE SETS PROVIDED. |
| | |
| | 2.ON THE PRODUCT APPROVAL, YOU'VE HIGHLIGHTED THE |
| | MOUNTING DETAILS ALTERNATIVE 1, 3A (OPTION 2), 3, AND |
| | 8.ON SHEETS 16 AND 17, WALL MOUNT 5, 2, 3A, AND 9 |
| | HAVE BEEN HIGHLIGHTED.THE INSTALLATION SCHEDULE |
| | SPECIFIES "WALL MOUNTING INSTALL A", WHICH IS NOT ONE |
| | OF THE CHOICES ON THIS PRODUCT APPROVAL.PLEASE |
| | CORRELATE. THE ANCHOR SPACING REQUIRED CANNOT BE |
| | REVIEWED WITHOUT THIS INFORMATION. |
| | |
| | ALSO PLEASE NOTE THAT MARKING THE PRODUCT APPROVAL IS |
| | HELPFUL AS IT ASSISTS WITH PLAN REVIEW AND INSPECTIONS, |
| | BUT IF YOU DO THIS, IT MUST BE CODE COMPLIANT AND |
| | CORRELATE WITH THE JOB.HIGHLIGHTER CANNOT BE USED TO |
| | SHOW CODE COMPLIANCE AS IT DOES NOT APPEAR WHEN |
| | SCANNED.THE INFORMATION ON THE INSTALLATION SCHEDULE |
| | IS REQUIRED BY BUILDING OFFICIAL'S POLICY. |
| | |
| | 2ND REVISION REVIEW, VARIOUS DETAILS AND ANCHOR SPACING |
| | WERE HIGHLIGHTED THROUGHOUT THE PRODUCT APPROVAL, |
| | INCLUDING 9" ANCHOR SPAC ING.INSTALLATION SCHEDULE |
| | SPECIFIES "WALL MOUNT A" WHICH I CANNOT LOCATE IN THE |
| | PRODUCT APPROVAL, WITH 11" SPACING.REVISE THE SHUTTER |
| | CONNECTION MOUNTING TYPE TO CORRELATE WITH THE |
| | CONNECTION TYPE YOU PROPOSE TO USE. |
| | |
| | 3.ADDRESSED. |