Plan Review Notes
Plan Review Notes For Permit 07100044
Permit Number 07100044
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-10 15:31:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 422.31(B) FOR PERMANENTLY CONNECTED APPLIANCES RATED
 OVER 300 VOLT-AMPERES OR1/ 8 HP, THE BRANCH-CIRCUIT
 SWITCH OR CIRCUIT BREAKER SHALL BE PERMITTED TO SERVE
 AS THE DISCONNECTING MEANS WHERE THE SWITCH OR CIRCUIT
 BREAKER IS WITHIN SIGHT FROM THE APPLIANCE OR IS
 CAPABLE OF BEING LOCKED IN THE OPEN POSITION. THE
 PROVISION FOR LOCKING OR ADDING A LOCK TO THE
 DISCONNECTING MEANS SHALL BE INSTALLED ON OR AT THE
 SWITCH OR CIRCUIT BREAKER USED AS THE DISCONNECTING
 MEANS AND SHALL REMAIN IN PLACE WITH OR WITHOUT THE
 LOCK INSTALLED. INDICATE LOCATION OF THE DISCONNECTING
 MEANS
  
 2} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 COMPLIANCE ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718