| 2008-02-26 11:04:45 | REVIEW #: REV.4 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. FIRE/SMOKE DAMPERS ARE SHOWN WHERE DUCTS PENETRATE A |
| | 1-HOUR RATED WALL ASSEMBLY. IT IS NOT CLEAR WHY |
| | FIRE/SMOKE DAMPERS ARE SHOWN AT THIS LOCATON AS THIS IS |
| | NOT A SMOKE BARRIER. IN FACT, IT IS NOT CLEAR WHY THIS |
| | WALL IS RATED AT ALL. THE STORAGE ROOMS MEET THE |
| | CRITERIA FOR ACCESSORY USE AREAS IN ACCORDANCE WITH |
| | FBCB 302.2 AND THEREFORE NO RATED SEPARATION IS |
| | REQUIRED. THE DESIGNER CAN DESIGN ABOVE WHAT THE CODE |
| | REQUIRES. HOWEVER, FIRE/SMOKE DAMPERS, WHETHER REQUIRED |
| | OR NOT SHALL BE INSTALLED PER THEIR LISTING, |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND FBCM |
| | SECTION 607 IN ACCORDANCE WITH FBCM 607.2. |
| | |
| | 2. PLANS DO NOT INDICATE HOW THE SMOKE DAMPERS ARE TO |
| | BE CONTROLLED. SMOKE DAMPERS SHALL BE CONTROLLED BY ONE |
| | OR A COMBINATION OF METHODS IN ACCORDANCE WITH FBCM |
| | 607.3.2.1. IF SMOKE DAMPERS ARE TO REMAIN, SHOW |
| | COMPLIANCE WITH THIS SECTION. |
| | |
| | NOTE: ANY CHANGES TO THE MECHANICAL PLANS RELATED TO |
| | THE LOCATION OF OR THE NEED FOR DAMPERS AT DUCT |
| | PENETRATIONS OF THE STORAGE ROOM WALLS SHOULD BE |
| | COORDINATED WITH ARCHITECTURAL PLANS. ANY CHANGES TO |
| | ARCHITECTURAL PLANS SHALL BE SUBMITTED FOR BUILDING |
| | PLAN REVIEW IN CONJUNCTION WITH RESUBMITTED MECHANICAL |
| | PLANS. |
| | |