| 2007-11-09 16:41:13 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. AH-1 IS STILL LISTED, BASED ON MODEL NUMBER, AS A |
| | CHILLED WATER AHU. PLAN STILL INDICATES THAT THERE IS |
| | AN EXISTING CONDENSING UNIT ON THE ROOF. ELECTRICAL |
| | PLANS STILL SHOW THERE IS ELECTRICAL SERVICE FOR A |
| | CONDENSING UNIT ON THE ELECTRICAL PANEL. AT LEAST ONE |
| | PIECE OF THIS INFORMATION IS INCORRECT. AS STATED IN |
| | PREVIOUS REVIEW COMMENT, THIS IS EITHER A CHILLED WATER |
| | SYSEM WITH NO CONDENSER (AS INDICATED BY AHU MODEL |
| | NUMBER) OR A SPLIT SYSTEM WITH THE WRONG AHU LISTED ON |
| | PLANS. PLEASE COORDINATE INFORMATION ON MECHANICAL |
| | PLANS REGARDING THE TYPE OF EQUIPMENT BEING USED. ALSO, |
| | IF IT IS DETERMINED THAT THERE IS NO CONDENSING UNIT, |
| | PLEASE COORDINATE WITH ELECTRICAL PLANS. SEE ATTACHED |
| | MANUFACTURER'S DATS FOR THE CARRIER 40RMS012 AIR |
| | HANDLER. |
| | |
| | 5. OK |
| | |
| | 6. DO THE AIR HANDLER AND EXHAUST FANS RUN CONTINUOUS? |
| | IF NOT, HOW WILL AIR BE PROVIDED WHENEVER THE RESTROOMS |
| | ARE OCCUPIED? SHOW COMPLIANCE WITH FBC,M 401.3 WHICH |
| | REQUIRES VENTILATION TO BE PROVIDED WHENEVER THE SPAE |
| | IS OCCUPIED. ALSO, OUTSIDE AIR CALCULATIONS STATE THAT |
| | OUTSIDE AIR FOR THE RESTROOOMS IS BEING PROVIDED VIA |
| | TRANSFER AIR. FLOOR PLAN SHOWS BATHROOMS PROVIDED WITH |
| | MECHANICAL SUPPLY AIR. WHICH IS CORRECT? SHOW |
| | COMPLIANCE WITH FBC,M 403.1. |
| | |
| | 7. OK |
| | |
| | 8. NOT FOR OUTSIDE AIR DAMPER STATES THE DAMPER IS TO |
| | BE CLOSED WHEN THE UNIT IS HOT IN USE. PLEASE CLARIFY. |
| | THIS DAMPER SHOULD REMAIN OPEN WHENEVER THE SPACE IS |
| | OCCUPIED AND BE CLOSED DURING UNOCCUPIED HOURS. IF THE |
| | AHU HAS A NIGHT MODE WHERE IT MAY BE RUNNING DURING |
| | UNOCCUPIED HOURS, THE DAMPER SHOULD BE CLOSED DURING |
| | THAT TIME IN ACCORDANCE WITH FBC 13-409.1.ABC.3.3. |
| | |
| | 9. OK |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |