| 2007-10-05 14:12:58 | REVIEW #: 1 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG TS: PROJECT INFORMATION, ITEM 4 INDICATES |
| | AIR-ZONA SYSTEMS AS THE MEP ENGINEER. HOWEVER, PG MP1.1 |
| | IS SIGNED AND SEALED BY YV KULKARNI, PE. PLEASE CORRECT |
| | INFORMATION ON FRONT PAGE. AIR-ZONA SYSTEMS |
| | ENGINEERING, INC'S CERTIFICATE OF AUTHORIZATION IS |
| | LISTED AS NULL AND VOID BY THE STATE OF FLORIDA DBPR. |
| | |
| | 2. MP1.1: UOTSIDE AIR CALCULATIONS REFERENCE THE 2003 |
| | IMC. PLEASE CORRECTLY REFERENCE 2004 FBC,M IN |
| | ACCORDANCE WITH FS 553.73. |
| | |
| | 3. MP1.1: OUTSIDE AIR CALCULATIONS REFERENCE AN EXHAUST |
| | SCHEDULE. NO SUCH SCHEDULE COULD BE FOUND ON PLANS. |
| | PROVIDE MISSING INFORMATION AS COMPLIANCE WITH FBC,M |
| | TABLE 403.3 IS REQUIRED BY FBC,EB 609.1. |
| | |
| | 4. MP1.1: EXISTING HVAC EQUIPMENT SCHEDULE LISTS A |
| | "CHILLED WATER SPLIT SYSTEM." THE EQUIPMENT SHOWN ON |
| | PLANS IS EITHER A SPLIT SYSTEM OR PART OF A CHILLED |
| | WATER SYSTEM. IT IS NOT BOTH. THE MODEL NUMBER LISTED |
| | ON PLAN FOR AH-1 INDICATES THIS IS A CHILLED WATER |
| | SYSTEM. THAT WOULD MEAN THAT THERE IS NO EXISTING ROOF |
| | MOUNTED CONDENSING UNIT INVOLVED IN THE SCOPE OF THIS |
| | WORK. ALSO, THERE IS NO AH-2 SHOWN ON PLANS. IT SHOULD |
| | NOT BE ON THE EXISTING EQUIPMENT SCHEDULE. PLEASE MAKE |
| | CORRECTIONS AND CLARIFY AS NEEDED TO ACCURATELY REFLECT |
| | THE SCOPE OF WORK AND EXISTING CONDITIONS. FBC |
| | 106.1.1. |
| | NOTE: EXISTING CU-1 IS ALSO SHOWN OP PG E1.1. |
| | COORDINATE ANY CORRECTIONS ON THIS PAGE WITH ELECTRICAL |
| | PLANS. |
| | |
| | 5. MP1.1: PLAN SHOWS DUCT SMOKE DETECTOR IN RETURN DUCT |
| | FOR UNIT SHUT DOWN. DUCT SMOKE DETECTORS SHALL BE |
| | INSTALLED IN SUPPLY AIR SYSTEMS IN ACCORDANCE WITH |
| | FBC,M 606.2.1. ALSO, DUCT DETECTOR(S) SHALL BE |
| | CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN |
| | ACCORDANCE WITH FBC,M 606.4.1. CONSULT LANDLORD |
| | REGARDING CONNECTION TO EXISTING FIRE ALARM SYSTEM. |
| | |
| | 6. MP1.1: TOILET ROOM EXHAUST FANS SHALL BE |
| | INTERCONNECTED WITH AH-1 TO ENSURE ALL AIR SUPPLIED TO |
| | THESE SPACES IS EXHAUSTED IN ACCORDANCE WITH FBC,M |
| | 403.2.1(3). PROVISIONS SHALL ALSO BE MADE TO ENSURE |
| | THAT VENTILATION IS PROVIDED WHENEVER THESE SPACES ARE |
| | OCCUPIED IN ACCORDANCE WITH FBC,M 401.3. |
| | |
| | 7. MP1.1: PROVIDE AIR BALANCE SCHEDULE SHOWING SUPPLY, |
| | RETURN AND EXHAUST TOTALS. THE SPACE SHALL BE |
| | PRESSURIZED WITH RESPECT TO THE OUTDOORS IN ACCORDANCE |
| | WITH FBC 13-409.1.ABC.2. |
| | |
| | 8. MP1.1: PROVIDE SHUTOFF DAMPER CONTROLS FOR OUTSIDE |
| | AIR INTAKE DUCT IN ACCORDANCE WITH FBC |
| | 13-409.1.ABC.3.3. |
| | |
| | 9. MP1.1: CONDENSATE IS SHOWN DISCHARGING INTO A MOP |
| | SINK. CONDENSATE DRAINS SHALL DISCHARGE TO AN APPROVED |
| | PLACE OF DISPOSAL IN ACCORDANCE WITH FBC,M 307.2.1. A/C |
| | CONDENSATE SHALL NOT DISCHARGE INTO THE SANITARY SEWER |
| | SYSTEM IN ACCORDANCE WITH WPB MUNICIPAL CODE SECTION |
| | 90-125(5). |
| | |