| Plan Review Notes For Permit 07100039 |
| Permit Number |
07100039 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-04 11:25:57 | ***DENIED*** | | | | | | 1) MORE INFORMATION IS REQUIRED REGARDING THE REAR | | | EXIT. MEANS OF EGRESS WOULD SUGGEST PERSONS PASSING | | | THROUGH TWO (2) STORAGE ROOMS WITH THE POSSIBILITY OF | | | BATHROOM DOORS CAUSING AN OBSTRUCTION. PLEASE SHOW | | | COMPLIANCE WITH NFPA 101, SEC. 7.5.1.6. | | | | | | 2) ILLUSTRATE AN ADDRESS ON THE BUILDING NEW OR | | | EXISTING THAT COMPLIES WITH CITY OF WEST PALM BEACH | | | REQUIREMENTS FOR COMMERCIAL BUILDINGS. CHARACTERS TO BE | | | MINIMUM OF 6"IN HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. SUITE NUMBERS TO BE AT LEAST 3" IN HEIGHT. | | | SHEET A3.1 | | | | | | 3) DUCT SMOKE DETECTORS TO BE LOCATED IN SUPPLY DUCT | | | AND SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE | | | WITH LOCAL REQUIREMENTS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) PLEASE INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS | | | A,B OR C. | | | | | | 6) BUILDING FIRE PROTECTION EQUIPMENT SHALL BE | | | MAINTAINED DURING WORK. | | | | | | 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. PLANS MENTION FIRE | | | ALARM EQUIPMENT BUT THIS IS NOT SHOWN ON DRAWINGS. | | | SHEET E1.1 | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|