| Plan Review Notes For Permit 07100027 |
| Permit Number |
07100027 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-02 12:38:38 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO | | | ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION. | | | | | | 2}NOTE: AN ELECTRICAL PERMIT IS REQUIRED IF WIRING IS | | | TO BE DONE. 105.1 FBC AS AMENDED. | | | | | | 3} A DISCONNECTING MEANS PER 225.31 AND GROUNDING PER | | | 250.32 WOULD BE REQUIRED AT A SEPERATE STRUCTURE. | | | | | | 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS | | | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT | | | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS | | | CHANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|