Plan Review Notes
Plan Review Notes For Permit 07100027
Permit Number 07100027
Review Stop E
Sequence Number 1
Notes
Date Text
2007-11-02 12:38:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO
 ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION.
  
 2}NOTE: AN ELECTRICAL PERMIT IS REQUIRED IF WIRING IS
 TO BE DONE. 105.1 FBC AS AMENDED.
  
 3} A DISCONNECTING MEANS PER 225.31 AND GROUNDING PER
 250.32 WOULD BE REQUIRED AT A SEPERATE STRUCTURE.
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]