Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-15 16:44:07*****DENIED*****
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE
 HANDRAILS/GUARDRAILS.
  
 5.THE NEW STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6.THESE OUTSIDE STAIRS SHALL BE DESIGNED TO MINIMIZE
 WATER ACCUMULATION ON THEIR SURFACES.
  
 7.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THIS PREFAB OFFICE IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 8.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 MODIFICATION TO THE FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEM.AS PER WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT, SUB-PERMITS SHALL NOT BE REVIEWED AND
 ATTAINED UNTIL SUCH TIME THAT THE MASTER PERMIT HAS
 BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722