Plan Review Notes
Plan Review Notes For Permit 07100024
Permit Number 07100024
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-06 13:50:05 
 *** DENIED ***
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE INDICATE THE REQUIRED AUTOMATED
 LIGHTING CONTROLS FOR NEW SWITCHING DEVICES BEING
 INSTALLED PER 13-415.1.ABC.1.1, .1.2.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES ON DEVICES.
 PLEASE EXPLAIN HOW IT IS ENERGY CALCULATIONS ARE BEING
 SUBMITTED UNDER METHOD *A* WHEN THE SCOPE OF WORK BEING
 DONE IS NOT FOR WHOLE BUILDING?
 METHOD *A* MAY NOT BE USED AND PLEASE SEE MECHANICAL
 REVIEW COMMENTS.
 THIS REVIEWER ONLY NEEDS LIGHTING PERFORMANCE LEVELS
 PER 13-415.2, TABLE B OR C.
 PLEASE CALL TO GO OVER ANY OF THIS.
  
 3) NOTE: PLEASE SEE THE NEW STAIRS BEING INSTALLED ARE
 NOT SHOWING ANY LIGHTING WHICH IS REQUIRED PER NFPA-101
 7.8 AND 7.9.
 PLEASE SUBMIT AND SHOW THE MINIMUM PHOTO-METRIC LEVELS
 UNDER NORMAL AND EMERGENCY CONDITIONS FOR NEW STAIRS.
 7.8.1.3, 7.9.2.2
 EVEN AS PLANS MENTIONS THESE STAIRS ARE NOT PART OF THE
 *REQUIRED EGRESS*, THESE WILL STILL BE SUED FOR EGRESS
 IN ANY EVENT AND LIGHTING LEVELS ARE REQUIRED WHETHER
 OR NOT PART OF THE *REQUIRED EGRESS STAIRS*,
 FAC 61G15-33.004.
 FBC 106.1.2.
  
 4) NOTE: PLEASE SHOW THE TOTAL LOADS ON PANEL NLA.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 220, 215.5, 230.42 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE KNOW EVEN AS THE FIRE ALARM DEVICES ARE
 REQUIRED TO BE UNDER SEPARATE PERMITS, THE BASE BUILD
 OUT/REMODEL PLANS WILL STILL BE REQUIRED TO SHOW
 LOCATIONS FOR ADA COMPLIANCE ALONG WITH THE MINIMUM
 REQUIRED LEVELS PER FBC 11-4.28.1,.2 AND .3(4).
 PLEASE DO NOT QUOTE THE CODE AS THE REQUIRED MINIMUM
 LOCATIONS AND LEVELS ARE NEEDED ON PLANS.
  
  
 ** PLEASE KNOW AS NO LIGHTING OR INFORMATION WAS
 SUBMITTED FOR NEW STAIRS, THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED AT THIS TIME AND THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER DIRECTLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]