| 2007-10-10 11:17:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07100024 |
| | ADD: 3201 ELECTRONIC WAY. |
| | CONT: M.A.C. CONSTRUCTION INC. |
| | TEL: (305)598-4317 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS |
| | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF |
| | THE CODE UNDER WHICH THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | . ------------------------------------- |
| | |
| | 4)106.1.2 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY |
| | REQUIRE DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND |
| | OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR |
| | INSTALLATION AND THE BASIS OF CALCULATION. THE PLANS |
| | SUBMITTED REQUIRE MORE INFORMATION ON THE AREA FOR THE |
| | PROJECT. THE SQUARE FOOTAGE OF ROOM SHALL BE INDICATED |
| | ON THE PLANS. SUBMIT THE NORTH/ SOUTH/ EAST AND WEST |
| | ELEVATION DRAWINGS OF THE ROOM WHERE THE NEW OFFICES |
| | WILL BE INSTALLED. |
| | |
| | 5)FBC 505.2 MEZZANINES SHALL NOT EXCEED ONE-THIRD OF |
| | THE AREA OF THE ROOM OR SPACE IN WHICH THEY ARE |
| | LOCATED. PROVIDE DRAWING WHICH MEET THE REQUIREMENTS OF |
| | FBC 505. |
| | |
| | 6)INDICATE THE OCCUPANT LOAD OF THE MEZZANINE AND |
| | SHOW THE MEANS OF EGRESS. A LIFE SAFETY SHALL ALSO BE |
| | SUBMITTED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |