Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop M
Sequence Number 6
Notes
Date Text
2008-12-20 09:17:38REVIEW #: 6TH
 ACTION: PASSED W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 BASED ON THE BUILDING PLAN REVIEW, THE ENERGY
 CALCULATIONS ARE BEING CORRECTED AND RESUBMITTED.
 MECHANICAL REVIEW WILL BE IN TEMPORARY FAIL STATUS
 PENDING RECEIPT OF THE CORRECTED ENERGY CALCULATIONS.
 ONCE ENERGY CALCULATIONS ARE RECEIVED, REVIEWED AND
 PASSED, THE MECHANICAL REVIEW STATUS WILL BE CHANGED TO
 PASS STATUS WITH THE FOLLOWING PROVISO:
  
 ***********PROVISO************
  
 PROVIDE MANUFACTURER'S SUBMITTAL OR OTHER SUPPORTING
 DATA SHOWING THE OUTDOOR APPLIANCES WHICH ARE EXPOSED
 TO WIND ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13. THIS INFORMATION SHALL BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION AND
 INSPECTION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
 NOTE: DESIGNER'S WRITTEN RESPONSES DATED 12/4/08
 INDICATE THAT ONE OF THE MECHANICAL REVIEW COMMENTS
 [COMMENT 2(D) DATED 11/24/08] WAS "BASED ON THE PLAN
 REVIEWER VALUE ENGINEERING THE PLANS." THIS RESPONSE IS
 NEITHER HELPFUL NOR ACCURATE. IN A PREVIOUS REVIEW IT
 WAS ASKED FOR PURPOSES OF CLARIFICATION WHETHER ALL
 FIRE DAMPERS WERE INTENDED TO BE FIRE/SMOKE DAMPERS, OR
 IF THERE WOULD BE STANDARD FIRE DAMPERS WHERE THE
 COMBINATION DAMPERS WERE NOT REQUIRED BY CODE. THE
 RESPONSE FROM STEVE HOCKMAN WAS THAT THE PLANS WOULD BE
 CHANGED TO REFLECT FIRE/SMOKE DAMPERS ONLY IN LOCATIONS
 REQUIRED BY CODE. WHEN THE PLANS WERE RESUBMITTED AND
 THIS CHANGE WAS NOT MADE, DESPITE A WRITTEN RESPONSE
 INDICATING THAT THE CHANGE WAS MADE, COMMENT 2(D)
 REQUESTED CLARIFICATION AGAIN. THIS WAS NOT AN ATTEMPT
 AT "VALUE ENGINEERING" AND AT NO TIME DID ANY REVIEW
 COMMENTS INSTRUCT ANYONE TO CHANGE FIRE/SMOKE DAMPERS
 TO FIRE DAMPERS TO SAVE MONEY.