| 2008-12-20 09:17:38 | REVIEW #: 6TH |
| | ACTION: PASSED W/ PROVISO |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | BASED ON THE BUILDING PLAN REVIEW, THE ENERGY |
| | CALCULATIONS ARE BEING CORRECTED AND RESUBMITTED. |
| | MECHANICAL REVIEW WILL BE IN TEMPORARY FAIL STATUS |
| | PENDING RECEIPT OF THE CORRECTED ENERGY CALCULATIONS. |
| | ONCE ENERGY CALCULATIONS ARE RECEIVED, REVIEWED AND |
| | PASSED, THE MECHANICAL REVIEW STATUS WILL BE CHANGED TO |
| | PASS STATUS WITH THE FOLLOWING PROVISO: |
| | |
| | ***********PROVISO************ |
| | |
| | PROVIDE MANUFACTURER'S SUBMITTAL OR OTHER SUPPORTING |
| | DATA SHOWING THE OUTDOOR APPLIANCES WHICH ARE EXPOSED |
| | TO WIND ARE DESIGNED TO RESIST WIND PRESSURES IN |
| | ACCORDANCE WITH FBCM 301.13. THIS INFORMATION SHALL BE |
| | PROVIDED FOR REVIEW PRIOR TO INSTALLATION AND |
| | INSPECTION OF OUTDOOR APPLIANCES. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |
| | |
| | NOTE: DESIGNER'S WRITTEN RESPONSES DATED 12/4/08 |
| | INDICATE THAT ONE OF THE MECHANICAL REVIEW COMMENTS |
| | [COMMENT 2(D) DATED 11/24/08] WAS "BASED ON THE PLAN |
| | REVIEWER VALUE ENGINEERING THE PLANS." THIS RESPONSE IS |
| | NEITHER HELPFUL NOR ACCURATE. IN A PREVIOUS REVIEW IT |
| | WAS ASKED FOR PURPOSES OF CLARIFICATION WHETHER ALL |
| | FIRE DAMPERS WERE INTENDED TO BE FIRE/SMOKE DAMPERS, OR |
| | IF THERE WOULD BE STANDARD FIRE DAMPERS WHERE THE |
| | COMBINATION DAMPERS WERE NOT REQUIRED BY CODE. THE |
| | RESPONSE FROM STEVE HOCKMAN WAS THAT THE PLANS WOULD BE |
| | CHANGED TO REFLECT FIRE/SMOKE DAMPERS ONLY IN LOCATIONS |
| | REQUIRED BY CODE. WHEN THE PLANS WERE RESUBMITTED AND |
| | THIS CHANGE WAS NOT MADE, DESPITE A WRITTEN RESPONSE |
| | INDICATING THAT THE CHANGE WAS MADE, COMMENT 2(D) |
| | REQUESTED CLARIFICATION AGAIN. THIS WAS NOT AN ATTEMPT |
| | AT "VALUE ENGINEERING" AND AT NO TIME DID ANY REVIEW |
| | COMMENTS INSTRUCT ANYONE TO CHANGE FIRE/SMOKE DAMPERS |
| | TO FIRE DAMPERS TO SAVE MONEY. |