Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop B
Sequence Number 6
Notes
Date Text
2008-12-19 13:17:05BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 DECEMBER 19 ,2008
 6TH REVIEW-
 ACTION: DENIED
  
  
 MET WITH ISREL ROZENTAL AIA, ABOUT PLANS,ENERGY CALCS,
 AND ROOFING PRODUCT APPROVALS, ULYSSIS WILL BRING BACK
 EITHER OR NEW ENERGY CALCS, PLANS AND ADDITIONAL
 INFORMATION AS TO WHICH SUB-SYSTEM TO BE INSTALLED ON
 THE FLAT ROOF. BY THE FIRST OF NEXT WEEK 12-22 OR
 12-23, REVIEW IS ON HOLD.
  
 1-02-09 CALLED KEN HAWKINS, KEN IS SUPPOSE TO BRING IN
 NEW A-104 & A-601 SHEETS MONDAY 1-05-09 BY 10:00AM.
  
  
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  