2008-11-24 18:43:10REVIEW #: 5TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2 AND 12: COMMENT #2 AND #12 ARE BEING COMBINED IN THIS
 REVIEW AS THEY DEAL WITH THE SAME SUBJECT. THERE
 CONTINUES TO BE COORDINATION PROBLEMS BETWEEN
 ARCHITECTURAL, LIFE SAFETY AND MECHANICAL PLANS RELATED
 TO WALL TYPES, RATINGS AND DUCT PENETRATIONS OF WALLS:
  
 A) **THIS COMMENT NOT ADDRESSED** THE LOCATION OF RATED
 WALL ASSEMBLIES ON LS-1.0 AND A-102 DO NOT CORRESPOND.
 EXAMPLE: THE WALLS ON THE EAST AND WEST SIDE OF
 CLASSROOM 160 ARE SHOWN TO BE 1-HOUR RATED (WALL TAG
 1A) ON PAGE A-102 BUT NO RATING IS SHOWN OB PAGE LS
 1.0. THERE ARE MULTIPLE DUCT PENETRATIONS OF THESE
 WALLS SHOWN ON PAGE M-2 WITH NO PROTECTION. IT WILL NOT
 BE CLEAR ON PLANS IF ALL DUCT PENETRATIONS WHICH
 REQUIRE PROTECTION ARE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 UNTIL ALL PLANS ARE COORDINATED.
  
 B) **PARTIALLY ADDRESSED** THE 30X14 SUPPLY DUCT FROM
 AHU-3 IS PENETRATING A 1-HOUR CORRIDOR WALL AS IT
 ENTERS CLASSROOM 160 WITH NO PROTECTION OF THIS
 PENETRATION SHOWN ON FLOOR PLAN. SHOW HOW THIS OPENING
 IS TO BE PROTECTED IN ACCORDANCE WITH FBCM 607.5.
 **PLEASE ADDRESS: THERE IS STILL NO INDICATION ONPLANS
 WHETHER THIS IS A FIRE DAMPER OR A FIRE/SMOKE DAMPER. A
 FIRE/SMOKE DAMPER IS REQUIRED AT THIS LOCATION IN
 ACCORDANCE WITH FBCM 607.5 AND 607.5.4.
  
 C) OK
  
 D) **THIS COMMENT NOT ADDRESSED** MECHANICAL
 SPECIFICATIONS NOTE #10 ON PAGE M-1 INDICATES ALL FIRE
 DAMPERS ARE TO BE CORRIDOR COMBINATION FIRE/SMOKE
 DAMPERS. FLOOR PLAN ONLY HAS ONE SYMBOL USED FOR FIRE
 DAMPERS AT ALL LOCATIONS. IS THE DESIGN INTENT THAT ALL
 FIRE DAMPERS REGARDLESS OF LOCATION BE COMBINATION
 FIRE/SMOKE DAMPERS? NOT ALL FIRE DAMPERS ON PLANS ARE
 LOCATED AT A CORRIDOR WALL PENETRATION AND THERE IS NO
 MEANS ON PLANS TO DIFFERENTIATE BETWEEN CORRIDOR TYPE
 COMBINATION DAMPERS AND STANDARD FIRE DAMPERS. PLEASE
 CLARIFY, SHOWING COMPLIANCE WITH FBCM 607.5.3 AND
 607.5.4.
  
 3 THROUGH 7: OK
  
 8. OK
  
 9. **THIS COMMENT NOT ADDRESSED** NEW COOLING LOAD
 CALCULATIONS HAVE STILL NOT BEEN PROVIDED WITH ENERGY
 CALCULATIONS AS REQUIRED BY FBCB 13-407.1.ABC.1.
 **PLEASE ADDRESS: ONE SYSTEM SIZING SUMMARY SET WAS
 SUBMITTED WITH ORIGINAL SEAL AND SIGNATURE. THE OTHER
 TWO SETS HAVE PHOTOCOPIED SIGNATURES AND NO SEALS.
 PLEASE ATTACH A SIGNED AND SEALED SYSTEM SIZING SUMMARY
 SET TO EACH SET OF ENERGY CALCULATIONS SUBMITTED IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1 AND FBCB 106.1.
  
 10. OK
  
 11. **PARTIALLY ADDRESSED** THIS COMMENT HAS NOT BEEN
 ADDRESSED. THERE IS NO INSTALLATION ATTACHMENT DETAIL
 FOR WIND RESISTANCE FOR THE OUTDOOR INSTALLED ERV AND
 NO INFORMATION ON THE CONSTRUCTION OF THE ERV SHOWING
 IT IS DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH FBCM 301.13.
 **PLEASE ADDRESS: ATTACHMENT INFORMATION ON PLANS OK.
 HOWEVER, NO INFORMATION WAS PROVIDED REGARDING WIND
 RESISTANCE OF THE ERV ITSELF. APPLIANCES EXPOSED TO
 WIND SHALL BE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13.
  
 12. SEE COMMENT #2 ABOVE.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE PROVIDED INFORMATION CAN BE FOUND.
 THIS WILL ASSIST IN PROVIDING A TIMELY REVIEW WITH AS
 FEW DELAYS AS POSSIBLE.
  