2008-11-18 16:25:59BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 NOVEMBER 18,2008
 5TH REVIEW- MAJOR WORKING DRAWING REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 1B-E)COMPLIED.
  
 217) COMPLIED
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 G) ROOF ASSEMBLIES-NOA 05-1220.07 FIBERTITE SINGLE PLY,
 SUB-SYSTEM PAGE 19, DECK TYPE 4: LIGHTWEIGHT CONCRETE,
 NON-INSULATED PLEASE SEE A-602 DETAIL# 1 AS WELL AS THE
 ENERGY CALCULATION INPUT DATA SHEETS BOTH INDICATING
 THERE TO BE A MINIMUM OF 6" OF INSULATION. PLEASE
 PROVIDE THE RIGHT SUB-SYSTEM (INSULATED )INDICATING A
 MINIMUM OF -89 FOR ZONE 3 OR ENHANCED FASTENING BY
 EITHER A ARCHITECT OR ENGINEEER.
  
 H) ENGLERT 2000 SERIES METAL ROOF PANEL OVER STEEL
 DECKDECK TYPE NOT INDICATED DECK TYPE A-1 MAXIMUM
 PRESSURE OF 62.5 PSF, 18 INCH PANELS, DECK TYPE A-2 A
 14" WIDE PANEL MAXIMUM UPLIFT -144.25
 NEITHER THE DETAIL# 1 ON A-602 NOR DETAIL2 0N A-603
 INDICATE THE THICKNESS OF THE RIGID FOAM INSULATION.
 THE ENGLERT PRODUCT APPROVAL DOES REQUIRE A PRODUCT
 APPROVAL FOR THE RIGID BOARD INSULATION PLEASE SEE
 INSULATION OPTIONAL REQUIREMENTS.
  
 19-20) COMPLIED.
  
  
 21) SEE 18G ABOVE.2ND REQUEST,
  
 22-23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) COMPLIED.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2ABENERGY CALCS DATED 11-14-08
  
  
  
  
  
 24C)2ND REQUEST, ZONE AC-3 WINDOWS ARE MISSING THE
 CLERESTORY WINDOWS NORTH ELEVATION SEE A-201, WINDOW
 SIZES (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS (2.25) WHERE AS
 THE PLANS CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW
 CORE METAL DOORS.
  
 24E)PLEASE SEE 18 G& H, ROOF INSULATION, PLANS DOES
 CALL OUT THE ACTUAL THICKNESS OF INSULATION NOR THE
 TYPE OF INSULATION TO BE INSTALLED. THE ROOFING NOAS
 HAS BEEN PROVIDED, IN THIS REVIEW THE SUB-SYSTEM HAS
 NOT BEEN IDENTIFIED WHERE AS IN THE LAST REVIEW THE
 SUB-SYSTEM WAS CIRCLED. THE UNKNWON ROOFING SUB-SYSTEM
 AND INSULATION TYPE WILL MAKE IT IMPOSSIBLE TO VERIFY
 THE ASSUMPTIONS PROVIDED IN THE ENERGY INPUT DATA
 REPORT. A-602.SECTION 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) COMPLIED.
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.