2008-10-11 13:58:13REVIEW #: 4TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
 NO WRITTEN RESPONSE TO PREVIOUS MECHANICAL REVIEW
 COMMENTS WERE PROVIDED. WHILE THIS IS NOT A CODE
 REQUIREMENT, IT DOES ASSIST THE REVIEWER IN
 UNDERSTANDING HOW THE COMMENTS HAVE BEEN ADDRESSED,
 SAVES UNNECCESARY REVIEW TIME AND AVOIDS DELAYS.
  
 1. OK
  
 2 AND 12: COMMENT #2 AND #12 ARE BEING COMBINED IN THIS
 REVIEW AS THEY DEAL WITH THE SAME SUBJECT. THERE
 CONTINUES TO BE COORDINATION PROBLEMS BETWEEN
 ARCHITECTURAL, LIFE SAFETY AND MECHANICAL PLANS RELATED
 TO WALL TYPES, RATINGS AND DUCT PENETRATIONS OF WALLS:
  
 A) THE LOCATION OF RATED WALL ASSEMBLIES ON LS-1.0 AND
 A-102 DO NOT CORRESPOND. EXAMPLE: THE WALLS ON THE EAST
 AND WEST SIDE OF CLASSROOM 160 ARE SHOWN TO BE 1-HOUR
 RATED (WALL TAG 1A) ON PAGE A-102 BUT NO RATING IS
 SHOWN OB PAGE LS 1.0. THERE ARE MULTIPLE DUCT
 PENETRATIONS OF THESE WALLS SHOWN ON PAGE M-2 WITH NO
 PROTECTION. IT WILL NOT BE CLEAR ON PLANS IF ALL DUCT
 PENETRATIONS WHICH REQUIRE PROTECTION ARE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5 UNTIL ALL PLANS ARE
 COORDINATED.
  
 B) THE 30X14 SUPPLY DUCT FROM AHU-3 IS PENETRATING A
 1-HOUR CORRIDOR WALL AS IT ENTERS CLASSROOM 160 WITH NO
 PROTECTION OF THIS PENETRATION SHOWN ON FLOOR PLAN.
 SHOW HOW THIS OPENING IS TO BE PROTECTED IN ACCORDANCE
 WITH FBCM 607.5.
  
 C) THE 14X10 SUPPLY DUCT BRANCH COMING FROM AHU-3 IS
 SHOWN ON FLOOR PLAN WITH A FIRE DAMPER WHERE THERE IS
 NO WALL ASSEMBLY. FIRE DAMPERS SHALL BE INSTALLED AT
 RATED WALL ASSEMBLIES IN ACCORDANCE WITH FBCM 607.2.
  
 D) MECHANICAL SPECIFICATIONS NOTE #10 ON PAGE M-1
 INDICATES ALL FIRE DAMPERS ARE TO BE CORRIDOR
 COMBINATION FIRE/SMOKE DAMPERS. FLOOR PLAN ONLY HAS ONE
 SYMBOL USED FOR FIRE DAMPERS AT ALL LOCATIONS. IS THE
 DESIGN INTENT THAT ALL FIRE DAMPERS REGARDLESS OF
 LOCATION BE COMBINATION FIRE/SMOKE DAMPERS? NOT ALL
 FIRE DAMPERS ON PLANS ARE LOCATED AT A CORRIDOR WALL
 PENETRATION AND THERE IS NO MEANS ON PLANS TO
 DIFFERENTIATE BETWEEN CORRIDOR TYPE COMBINATION DAMPERS
 AND STANDARD FIRE DAMPERS. PLEASE CLARIFY, SHOWING
 COMPLIANCE WITH FBCM 607.5.3 AND 607.5.4.
  
 3 THROUGH 7: OK
  
 8. NOTE 13 ON PAGE M-2 HAS BEEN MODIFIED TO SHOW TWO
 LINE SETS PER CONDENSING UNIT FOR AHU-1 AND AHU-2. DOES
 THIS MEAN THERE ARE TWO CONDENSING UNITS PER AHU? THERE
 IS ONLY ONE CONDENSING UNIT PER AHU SHOWN ON PLANS.
 PLEASE CLARIFY PER FBCM 304.1 AND FBCB 106.1.1.
  
 9. NEW COOLING LOAD CALCULATIONS HAVE STILL NOT BEEN
 PROVIDED WITH ENERGY CALCULATIONS AS REQUIRED BY FBCB
 13-407.1.ABC.1. ALSO, PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS RELATED TO DISCREPANCIES BETWEEN BUILDING
 PLANS AND SQUARE FOOTAGE SHOWN ON ENERGY CALCULATIONS.
 PLANS AND CALCULATIONS SHALL CORRESPOND IN ACCORDANCE
 WITH FBCB 13-103.2.
  
 10. OK
  
 11. THIS COMMENT HAS NOT BEEN ADDRESSED. THERE IS NO
 INSTALLATION ATTACHMENT DETAIL FOR WIND RESISTANCE FOR
 THE OUTDOOR INSTALLED ERV AND NO INFORMATION ON THE
 CONSTRUCTION OF THE ERV SHOWING IT IS DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 12. SEE COMMENT #2 ABOVE.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE PROVIDED INFORMATION CAN BE FOUND.
 THIS WILL ASSIST IN PROVIDING A TIMELY REVIEW WITH AS
 FEW DELAYS AS POSSIBLE.
  