| Date |
Text |
| 2008-10-08 15:02:37 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | ********FROM PREVIOUS REVIEWS: |
| | |
| | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION |
| | INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED. |
| | ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE |
| | THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE |
| | GAS PERMIT. |
| | ******RESPONSE NOTED, SHEETS NOT SUBMITTED. |
| | ********NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 27. OK |
| | |
| | **********NEW GAS COMMENTS********** |
| | |
| | 1B. OK |
| | 2B. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION |
| | |