Date Text
2008-10-10 15:15:20 
 ** DENIED 4TH REVIEW**
  
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 NOT FOR PERMIT.
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 DO NOT COORDINATE WITH PLANS. THERE ARE SEVERAL
 INCONSISTENCIES WITH THE SQ FOOTAGE ETC. PLEASE SEE
 COMMENTS FOR OTHER TRADES FOR ITEMS SUCH AS FLOORING
 ETC.
 LS SAFETY PLANS FOR NEW BUILDING SHOW IN EXCESS OF
 11,000 SQ FT, A-1000 STATES 10,000 SQ FT AS TOTAL
 BUILDING FOOT-PRINT YET THE CALCULATIONS STATE A TOTAL
 OF 8913.
 PLEASE BE SURE ALL LIGHTING AS SHOWN ON PLANS FOR TYPE
 OF FIXTURES, WATTAGE OF FIXTURES AND THE NUMBER OF
 FIXTURES COORDINATE WITH THE INPUT DATA REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS.
 FOR EXAMPLE: SEE EXTERIOR LIGHTING, SOME OF THE
 FIXTURES AS SHOWN ON THE EXTERIOR OF THE BUILDING
 INCLUDING SITE ARE NOT ON THE IDR AT ALL.
 FOR EXAMPLE: ONE WOULD BE THE 175 WATT SITE LIGHTS.
 THERE ARE NO 175W FIXTURES ON THE IDR AT ALL.
  
 FOR EXAMPLE: ANOTHER WOULD BE THE *Y* FIXTURES. THESE
 ARE NOTED ON THE FIXTURE LEGEND AND ON PLANS IN MANY
 LOCATIONS. THE FIXTURE LEGEND MENTIONS TO SEE LANDSCAPE
 PLANS. THE LANDSCAPE PLANS CALLS FOR THESE SAME ITEMS
 AS BOLLARDS. ARE THEY BOLLARDS WITH LIGHTING FIXTURES?
 IF SO HOW IS IT POSSIBLE THAT THEY ARE SHOWN AS A *Y*
 FIXTURE WHEN THE SAME DESIGNATION IS USED FOR OTHER
 FIXTURES WHICH ARE CLEARLY NOT BOLLARDS? THE SHEET E-6
 DOES SHOW BOLLARDS AS PART OF THE SCHEDULE. NO BOLLARDS
 ARE SHOWN ON FIXTURE LEGEND. COORDINATION, AND
 DESIGNATIONS IS NEEDED.
 ** COMPLETE LEGEND WITH FIXTURES. (((AS LONG AS PLANS
 COORDINATE AND SHOW A ***MINIMUM*** CODE COMPLIANCE
 THEY MAY ALWAYS BE REVISED AT A LATER DATE))).
  
 FOR EXAMPLE: PLEASE SEE THE IDR, THE AMOUNT OF *S*
 FIXTURES NEED COORDINATING.
  
 FOR EXAMPLE: AS NOTED ABOVE FOR THE *Y* FIXTURES WHICH
 ARE NOTED AS 50W/55W FIXTURES THE *U* FIXTURES ARE ALSO
 SHOWN AS 50W/55W FIXTURES. BETWEEN BOTH OF THESE
 FIXTURES WHICH ARE NOTED AS 50W/55W THERE SHOULD BE A
 NUMBER FIXTURE FAR GREATER THAN WHAT IS SHOWN ON THE
 IDR. IN FACT THE IDR ONLY INDICATES A TOTAL OF 27 -55W
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A
 FAR GREATER NUMBER OF *Y* AND *U* FIXTURES WHICH ARE
 THE SAME WATTAGE. THIS IS ACCORDING TO THE LIGHTING
 PLANS SUBMITTED SIGNED, DATED AND SEALED ON 9/28/08,
 THE FIXTURE LEGEND SIGNED DATED AND SEALED 6/26/08 AND
 CALCULATIONS SIGNED, DATED AND SEALED 9/29/08.
  
 FOR EXAMPLE: PLEASE TAKE A LOOK AT THE LIGHTING FOR
 INTERIOR AND GO OVER ALL FIXTURES IN ALL
 ZONES/SPACES/AREAS. NOT ALL FIXTURES ARE IN CONFERENCE
 MEETING ROOMS ALTHOUGH IN THE SAME ZONE. *C*?
  
 13-400.3.A, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WHICH GAVE
 INFORMATION TO THE FACT THE SITE LIGHTING POLES WERE
 NOTING SBCCI FOR DESIGN HOWEVER SBCCI HAS NOT BEEN AN
 ADOPTED CODE IN THE STATE OF FLORIDA SINCE MARCH 1ST OF
 2002. SEE E-1 *PARKING LOT LIGHT POLE DETAIL*. THIS HAS
 BEEN CIRCLED ON PREVIOUS PLANS AS WELL ON THESE PLANS
 ONCE AGAIN.
 PLEASE SEE FBC 2004W/2007 REVISIONS AS ADOPTED BY FS
 553.73.
  
 4) NOTE: AS NOTED IN COMMENT NUMBER #2 ABOVE WITH
 RESPECT LIGHTING FIXTURES AND COORDINATION NEEDED.
 PLEASE SEE THE LIGHTING AS SHOWN ON THE LANDSCAPE PLANS
 DOES NOT COORDINATE WITH ELECTRICAL OR ELECTRICAL DOES
 NOT COORDINATE WITH LANDSCAPE PLANS. THE ELECTRICAL
 PLANS CONTAIN NOTES TO SEE LANDSCAPE PLANS HOWEVER
 COORDINATION OF PLANS IS ESSENTIAL.
 LOADS, CALCULATIONS, ENERGY CALCULATION, CIRCUITING ETC
 ALL NEED TO BE VERIFIED SHOWING THE MINIMUM FOR CODE
 COMPLIANCE.
 408.4,310.16,240.4, 220, ETC
 FBC 13-415 ETC
 FBC 106.1.1,106.1.2 FOR CLARITY, ADDITIONAL INFORMATION
 AND COORDINATION OF PLANS.
  
 5) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE LIGHTING CONTROLS AND PANEL SCHEDULES. ONE EXAMPLE
 WHICH WAS THE SAME EXAMPLE GIVEN ON THE PREVIOUS REVIEW
 IS CIRCUIT L4-36. THE PLANS SHOW THIS CIRCUIT FEEDING
 THE EXTERIOR LIGHTS YET THE PANEL SCHEDULE STILL SHOWS
 THIS CIRCUIT FEEDING A *PROJECTION SCREEN*.
 NO RESPONSE WAS MADE TO THIS PART OF THE PREVIOUS
 REVIEW COMMENT AS AN EXAMPLE.
  
 6) NOTE: PLEASE SEE THE LIGHTING CONTROLS AND TYPES OF
 DEVICE NEEDS SOME COORDINATION OF WHAT WILL BE
 INSTALLED AND REQUIRED. THE RESPONSE MENTIONS
 *PHOTO-SENSOR* FOR INTERIOR LIGHTING AND SHEET E-6 ALSO
 SHOWS *PHOTO-SENSOR*.
 DUAL TECHNOLOGY DEVICES FOR OCCUPANCY SENSORS AND
 PHOTO-SENSORS ARE NOT THE SAME. THE PREVIOUS NOTES GAVE
 SECTION 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING AND
 METHODS OF CONTROLS. THE PLANS CALL FOR 10HR BACK UP OF
 INTERIOR LIGHTING HOWEVER THIS SECTION OF THE CODE
 WHICH WHEN USING A TIME CLOCK, REQUIRES THAT TIME CLOCK
 TO BE ASTRONOMICAL AND WITH A 10HR BACK UP MINIMUM FOR
 PROGRAMMING. IF USING A PHOTO-SENSOR (ALSO KNOWN AS A
 PHOTO-CELL) THE ASTRONOMICAL TIME CLOCK IS NOT REQUIRED
 NOR IS THE 10HR BACK UP.
 HOW CAN THESE BE NOTED A PHOTO-SENSORS? THIS IS NOT
 POSSIBLE.
 SYMBOL LEGEND CALLS FOR MOTION SENSORS. THERE ARE
 DEVICE WHICH ARE ONLY MOTION AND DO NOT CONTAIN THE
 MULTI-LEVEL DESIGN FOR DUAL TECHNOLOGY, ULTRASONIC,
 INFRARED ETC.
 LIGHTING CONTROL SYSTEM NEEDS MEET FBC
 13-415.1.ABC.1.1,.1.2 AND .1.3.
 THE CONTROLS AND SYSTEM SHOWN ON PLANS IS CONFUSING AND
 AS SHOWN IT IS NOT POSSIBLE TO BE A WORKING SYSTEM.
  
 ** LIGHTING SYSTEM IN RENOVATED BUILDING ALSO NEEDS TO
 BE GONE OVER.
  
  
 ** THIS IS THE THIRD REVIEW IN WHICH COMMENTS HAVE BEEN
 MADE ON THE LIGHTING SYSTEM. IT IS RECOMMENDED BY THIS
 OFFICE TO HAVE A MEETING TO GO OVER THE PLANS.
  
 7) NOTE: PLANS STILL NOTE THAT 8 COPIES OF SHOP
 DRAWINGS ARE REQUIRED AND 7 COPIES WILL BE STAMPED BY
 THE REVIEWER. THIS IS A THRESHOLD PROJECT ONLY THREE
 SETS ARE NEEDED AND ONLY THREE SETS WILL BE PROCESSED
 AND STAMPED.
  
 8) NOTE: AS NOTED ON PREVIOUS REVIEW THE RENOVATED
 BUILDING SHALL CONTAIN A MAIN OR A PERMANENT DEAD FRONT
 WHICH WILL NOT PERMIT MORE THAN 6 BREAKERS TO BE
 INSTALLED. ONCE THE PHASE TWO WORK IS COMMENCED THIS
 MLO ONLY EQUIPMENT WILL HAVE A DISCONNECT AS SHOWN ON
 RISER FOR THE NEW BUILDING HOWEVER NEED TO HAVE SOME
 SORT OF DISCONNECT SHOWN AT THIS TIME FOR PERMIT
 ISSUANCE.
 225.31-225.39
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  