| 2008-10-09 09:38:33 | BUILDING PLAN REVIEW |
| | PERMIT: 07100001 |
| | ADDRESS: 1505 N AUSTRALIAN AVE. |
| | CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING) |
| | TEL: (561644-7416 JEFF HALVERSON |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING TYPE: I-B |
| | OCTOBER 09,2008 |
| | 4TH REVIEW- MAJOR WORKING DRAWING REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | |
| | 1B) MULTIPLE REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE |
| | IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*. |
| | |
| | PLANS SUBMITTED THIS REVIEW: |
| | (2) SET OF NEW CONSTRUCTION PLANS FOR COMMUNITY CENTER |
| | (2) SETS OF PLANS FOR RENOVATIONS OF NORTH WING |
| | (2) SETS OF PRODUCT APPROVALS |
| | (2) SETS SOILS REPORT |
| | (2) ENERGY CALCULATIONS |
| | (2) SETS STORM WATER MANAGEMENT SYSTEM CALCULATIONS |
| | (2) SETS OF RESPONCE COMMENTS FROM WHAT APPEARS TO BE |
| | 2ND & 3RD ROUND COMMENT |
| | |
| | |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D) COMPLIED. |
| | |
| | 1E) COMPLIED |
| | |
| | 2) COMPLIED |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B) 3RD REQUEST, WHILE MEETING WITH JEFF HALVERSON |
| | ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE |
| | ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S |
| | S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS |
| | WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR |
| | WERE PROVIDED TO MR. HALVERSON . NOTE THE FOUNDATION |
| | PERMIT IS A AT RISK, STAND ALONE PERMIT AND THE PROPER |
| | FORMS FOR THE THRESHOLD BUIULDING PERMIT WILL ALSO NEED |
| | TO BE SUPPLIED: |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | THRESHOLD INSPECTOR: MEETING HAS ALREADY TAKEN PLACE. |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | |
| | 6-12) COMPLIED. |
| | |
| | 13) 4TH REQUEST, SEMI-COMPLIED. SHEET A-1 DOES INDICATE |
| | WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE |
| | OPENING PROTECTIVES IN THE RATED WALLS TO THE |
| | MULTIPURPOSE ROOM. SHEET A101 |
| | INDICATES THE DOUBLE DOORS AS DOOR# 98 AND DOOR # 42. |
| | SEE 715.3.SEE SHEET A-7.00 |
| | |
| | 14) FIRST REVIEW STATED THAT A THOROUGH REVIEW CAN NOT |
| | BE MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL |
| | INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| | THAT WERE NOT PART OF THIS REVIEW. |
| | THERE ARE STILL SOME ISSUES OUTSTANDING AS LISTED |
| | BELOW. |
| | |
| | 15) COMMENT FROM FIRST REVIEW, SEMI-COMPLIED, THERE ARE |
| | NUMEROUS A-SHEETS THAT HAVE ARCHITECTURAL DETAILS BUT |
| | THERE IS NO WRITTEN INFORMATION PROVIDED, PLANS ARE |
| | INCOMPLETE.106.3.5.1.1(4) SEE FIRE RESISTANCE |
| | CONSTRUCTION REQUIREMENTS.PLANS FAIL TO INDICATE FIRE |
| | RESISTANCERATING OF BAR JOIST SYSTEM TABLE 601 BAR |
| | JOIST 2 HR FOOTNOTE "B" ALLOWS FOR A 1 HOUR REDUCTION. |
| | SEE SHEET A602. |
| | |
| | 16-17) COMPLIED. |
| | |
| | 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING |
| | REPORTS ,MISSING REPORTS ARE AS FOLLOWS: |
| | |
| | G) ROOF ASSEMBLIES- FIBERTITE SINGLE PLY, SUB-SYSTEM |
| | NOT IDENTIFIED |
| | H) TRUSS ANCHORS SEE COMMENT #22 |
| | |
| | NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS |
| | (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE |
| | LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH |
| | VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC |
| | GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A |
| | COMPENENT OF THIS BUILDING. |
| | |
| | 19) COMPLIED. |
| | |
| | |
| | 20) COMPLIED. |
| | |
| | 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT |
| | COMPLIANCE REPORTS WITH THE FOLLOW ITEMS: |
| | __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES |
| | LIMITATION# 9, NO ENHANCED FASTENING ALLOWED. |
| | |
| | 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS |
| | ASSEMBLY AND NOA'S: |
| | USP C88 NOA 07-0306.06 |
| | USP RT7 NOA07-0306.10 |
| | USPKCB88 FL 822.149 |
| | ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE |
| | REQUIREMENTS OF 18-20. |
| | |
| | 23) COMPLIED. |
| | |
| | 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN |
| | INFORMATION FOR THE ENERGY CODE AND CALCULATIONS, |
| | 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE |
| | CRITERIA. |
| | |
| | 24A) 2ND REQUEST, THE TOTAL SQUARE FOOTAGE OF THE |
| | BUILDING DOES NOT CALCULATE, THE TOTAL GROSS AREA TAKEN |
| | FROM LS1.0 EQUALLS 11,159 SQ FT NOT THE 9854 LISTED. |
| | SHEET A-700 ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE |
| | THE TOTAL AREA ON THE ENERGY CALCULATION AS 8913 SQUARE |
| | FEET. PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE |
| | GROSS FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED |
| | SPACES CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO |
| | OUTSIDE AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY |
| | SHALL INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT |
| | MAY FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED |
| | SPACE ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA |
| | TO REFLECT THE TOTAL GROSS AREA. STATE RADON FEES WILL |
| | NOT BE ESSESSED UNTIL SQUARE FOOTAGE IS RESOLVED. |
| | |
| | 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF |
| | FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A |
| | INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY |
| | CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC |
| | ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED |
| | VALUE WAS TAKEN. 13-405.2AB |
| | |
| | 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY |
| | WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS |
| | 25,26 & 27. 13-401.2AB.2 |
| | |
| | 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS |
| | INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS |
| | CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL |
| | DOORS. |
| | |
| | 24E) ROOF INSULATION, PLANS DOES CALL OUT THE ACTUAL |
| | THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO |
| | BE INSTALLED. THE ROOFING NOAS HAS BEEN PROVIDED, IN |
| | THIS REVIEW THE SUB-SYSTEM HAS NOT BEEN IDENTIFIED |
| | WHERE AS IN THE LAST REVIEW THE SUB-SYSTEM WAS CIRCLED. |
| | THE UNKNWON ROOFING SUB-SYSTEM AND INSULATION TYPE WILL |
| | MAKE IT IMPOSSIBLE TO VERIFY THE ASSUMPTIONS PROVIDED |
| | IN THE ENERGY INPUT DATA REPORT. A-602.SECTION |
| | 13-404.1AB.1/ 13-404.2AB.3. |
| | |
| | 25) COMPLIED. |
| | |
| | RENOVATIONS TO THE EXISTING NORTH WING |
| | |
| | 26A) COMPLIED. |
| | |
| | 26B) COMPLIED. |
| | |
| | 26C) COMPLIED. |
| | |
| | 27-29) COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |