Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop B
Sequence Number 4
Notes
Date Text
2008-10-09 09:38:33BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 OCTOBER 09,2008
 4TH REVIEW- MAJOR WORKING DRAWING REVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
  
 1B) MULTIPLE REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*.
  
 PLANS SUBMITTED THIS REVIEW:
 (2) SET OF NEW CONSTRUCTION PLANS FOR COMMUNITY CENTER
 (2) SETS OF PLANS FOR RENOVATIONS OF NORTH WING
 (2) SETS OF PRODUCT APPROVALS
 (2) SETS SOILS REPORT
 (2) ENERGY CALCULATIONS
 (2) SETS STORM WATER MANAGEMENT SYSTEM CALCULATIONS
 (2) SETS OF RESPONCE COMMENTS FROM WHAT APPEARS TO BE
 2ND & 3RD ROUND COMMENT
  
  
  
 1C) COMPLIED.
  
 1D) COMPLIED.
  
 1E) COMPLIED
  
 2) COMPLIED
  
 3-4) COMPLIED.
  
 5A) COMPLIED.
  
 5B) 3RD REQUEST, WHILE MEETING WITH JEFF HALVERSON
 ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE
 ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S
 S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS
 WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR
 WERE PROVIDED TO MR. HALVERSON . NOTE THE FOUNDATION
 PERMIT IS A AT RISK, STAND ALONE PERMIT AND THE PROPER
 FORMS FOR THE THRESHOLD BUIULDING PERMIT WILL ALSO NEED
 TO BE SUPPLIED:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR: MEETING HAS ALREADY TAKEN PLACE.
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
  
 6-12) COMPLIED.
  
 13) 4TH REQUEST, SEMI-COMPLIED. SHEET A-1 DOES INDICATE
 WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE
 OPENING PROTECTIVES IN THE RATED WALLS TO THE
 MULTIPURPOSE ROOM. SHEET A101
 INDICATES THE DOUBLE DOORS AS DOOR# 98 AND DOOR # 42.
 SEE 715.3.SEE SHEET A-7.00
  
 14) FIRST REVIEW STATED THAT A THOROUGH REVIEW CAN NOT
 BE MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
 THERE ARE STILL SOME ISSUES OUTSTANDING AS LISTED
 BELOW.
  
 15) COMMENT FROM FIRST REVIEW, SEMI-COMPLIED, THERE ARE
 NUMEROUS A-SHEETS THAT HAVE ARCHITECTURAL DETAILS BUT
 THERE IS NO WRITTEN INFORMATION PROVIDED, PLANS ARE
 INCOMPLETE.106.3.5.1.1(4) SEE FIRE RESISTANCE
 CONSTRUCTION REQUIREMENTS.PLANS FAIL TO INDICATE FIRE
 RESISTANCERATING OF BAR JOIST SYSTEM TABLE 601 BAR
 JOIST 2 HR FOOTNOTE "B" ALLOWS FOR A 1 HOUR REDUCTION.
 SEE SHEET A602.
  
 16-17) COMPLIED.
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 G) ROOF ASSEMBLIES- FIBERTITE SINGLE PLY, SUB-SYSTEM
 NOT IDENTIFIED
 H) TRUSS ANCHORS SEE COMMENT #22
  
 NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS
 (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE
 LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH
 VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC
 GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A
 COMPENENT OF THIS BUILDING.
  
 19) COMPLIED.
  
  
 20) COMPLIED.
  
 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) 2ND REQUEST, THE TOTAL SQUARE FOOTAGE OF THE
 BUILDING DOES NOT CALCULATE, THE TOTAL GROSS AREA TAKEN
 FROM LS1.0 EQUALLS 11,159 SQ FT NOT THE 9854 LISTED.
 SHEET A-700 ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE
 THE TOTAL AREA ON THE ENERGY CALCULATION AS 8913 SQUARE
 FEET. PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE
 GROSS FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED
 SPACES CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO
 OUTSIDE AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY
 SHALL INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT
 MAY FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED
 SPACE ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA
 TO REFLECT THE TOTAL GROSS AREA. STATE RADON FEES WILL
 NOT BE ESSESSED UNTIL SQUARE FOOTAGE IS RESOLVED.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2AB
  
 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY
 WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS
 CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL
 DOORS.
  
 24E) ROOF INSULATION, PLANS DOES CALL OUT THE ACTUAL
 THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO
 BE INSTALLED. THE ROOFING NOAS HAS BEEN PROVIDED, IN
 THIS REVIEW THE SUB-SYSTEM HAS NOT BEEN IDENTIFIED
 WHERE AS IN THE LAST REVIEW THE SUB-SYSTEM WAS CIRCLED.
 THE UNKNWON ROOFING SUB-SYSTEM AND INSULATION TYPE WILL
 MAKE IT IMPOSSIBLE TO VERIFY THE ASSUMPTIONS PROVIDED
 IN THE ENERGY INPUT DATA REPORT. A-602.SECTION
 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) COMPLIED.
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved