Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop M
Sequence Number 3
Notes
Date Text
2008-07-17 16:56:51REVIEW #: 3RD. **PLAN REVIEW**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. SOME OF THE COMBINATION FIRE/SMOKE DAMPERS WHICH
 HAVE BEEN ADDED TO THE CORRIDOR WALLS AT HALLWAY 152
 ARE NOT SHOWN AT THE LOCATION OF THE RATED WALL
 ASSEMBLIES AS SHOWN ON PAGE LS-1.0. SOME ARE SHOWN AT A
 SOFFIT RATHER THAN BEING SET-BACK IN THE ALCOVE WHERE
 THE RATED WALL ASSEMBLY IS LOCATED. ALSO, HALL 165 IS
 SHOWN ON LS-1.0 AS BEING ON THE CORRIDOR SIDE OF THE
 RATED WALL ASSEMBLY. THE RESULT IS THERE ARE NO DAMPERS
 SHOWN ON PAGE M-2 WHERE THE DUCTS ACTUALLY PENETRATE
 THE RATED WALLS. PLEASE COORDINATE MECHANICAL PLANS
 WITH ARCHITECTURAL AND LIFE SAFETY PLANS TO SHOW DUCT
 PENETRATIONS LOCATED AT THE ACTUAL WALL ASSEMBLIES IN
 ACCORDANCE WITH FBCM 607.5.
  
 3 THROUGH 5: OK
  
 6. IS THIS DESIGN WITH TEK (SHEET METAL) SCREWS INTO
 WOOD AND ONLY ATTACHING TO CORRUGATED DECKING INTENDED
 AND DESIGNED FOR WIND RESISTANCE? PLEASE CLARIFY AND
 COORDINATE WITH STRUCTURAL DRAWINGS. ALSO, NO
 INFORMATION WAS PROVIDED REGARDING THE WIND RESISTANCE
 OF THE GREENHECK ROOF CAP. SHOW COMPLIANCE WITH FBCM
 301.13 AS STATED IN PREVIOUS REVIEW COMMENT #6.
  
 7. OK PENDING BUILDING REVIEW.
  
 8. OK
  
 9A. OK
  
 9B. OK
  
 9C. THE IDR HAS BEEN CORRECTED FOR MECHANICAL ITEMS.
 HOWEVER, COOLING LOAD CALCULATION HAVE NOT BEEN
 ATTACHED TO THE ENERGY CALCULATIONS AS REQUIRED BY FBCB
 13-407.1.ABC.1.
 NOTE: SOME VALUES OF THE OLD COOLING LOAD CALCULATIONS
 MAY HAVE CHANGED SINCE THE ADDITION OF THE ERV AND
 NEWLY CALCULATED VENTILATION RATES. PLEASE UPDATE
 COOLING LOAD CALCULATIONS TO REFLECT THESE NEW VALUES
 PRIOR TO RESUBMITTING.
  
 9D. OK
  
 10. OK
  
 NEW COMMENTS RELATED TO NEW INFORMATION ON PLANS:
  
 11. A NEW ERV UNIT HAS BEEN ADDED TO THE MECHANICAL
 PLANS. NO INFORMATION WAS PROVIDED REGARDING WIND
 MOUNTING AND WIND RESISTANCE FOR THIS OUTDOOR
 APPLIANCE. PROVIDE INSTALLATION DETAIL AND
 MANUFACTURER'S DATA SHOWING COMPLIANCE WITH THE WIND
 RESISTANCE REQUIREMENTS OF FBCM 301.13.
  
 12. PAGE A-101 AND LS-1.0 CONTINUE TO HAVE COORDINATION
 PROBLEMS. EXAMPLE: STORAGE ROOM 151AND MULTI-PURPOSE
 ROOM 146 ARE SHOWN ON LS-1.0 TO BE SEPARATED BY 1-HOUR
 CONSTRUCTION. PAGE A-101 WALL TAG AND A-600 WALL TYPES
 SHOW THIS WALL AS CARRYING NO FIRE RATING. THE NEW DUCT
 FOR THE ERV SYSTEM IS SHOWN PENETRATING THIS WALL WITH
 NO PROTECTION. ALSO, THE WALLS AT MECHANICAL ROOM 150
 AND PANTRY 147 ARE ALSO SHOWN WITH FIRE RATED WALLS.
 THERE ARE MULTIPLE DUCT PENETRATIONS IN THESE AREAS
 WITHOUT PROTECTION. PLEASE COORDINATE ALL AEAS OF
 MECHANICAL, ARCHITECTURAL AND LIFE SAFETY PLANS AND
 SHOW EACH DUCT PENETRATION TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.
 NOTE: SMOKE DAMPERS ARE ONLY REQUIRED AT THE CORRIDOR
 PENETRATIONS.
  