Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2008-08-07 15:18:18*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 00. THE ACTUAL PROJECT LOCATION SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. AMEND/CORRECT SHEET
 L-4.1 & L-4.2, L-5.1 THRU L-5.3, L-6.1, A-103, A-200,
 A-300, A-400 THRU A-402, A-601, A-603, A-900, A-901,
 S-1.2 & S--2, S-3.3 THRU S-4.2, M-1 THRU M-3, E-1 THRU
 E-10, P-1 THRU P-5, AND FP-1 & FP-2.
  
 03. UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO
 ANY EXCAVATING. COMMENT NOT ADDRESSED ON SHEET D-100 AS
 INDICATED IN YOUR RESPONSE
  
 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE
 BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE. COMMENT
 NOT ADDRESSED ON SHEET E-9 AS INDICATED IN YOUR
 RESPONSE
  
 29. STAIRS TO COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE. NOT ADDRESSED ON SHEET
 A-301 AS INDICATED IN YOUR RESPONSE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722