| 2008-07-28 13:03:56 | |
| | ** DENIED3RD REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL ITEMS STILL FROM |
| | PREVIOUS REVIEWS WHICH ARE IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | AND THE INPUT DATA REPORT IS NOT CODE COMPLIANT AND |
| | DOES NOT COORDINATE WITH THE SUBMITTED PLANS. |
| | PLEASE SEE THAT THE NUMBER OF FIXTURES AND THE WATTAGES |
| | OF FIXTURES IS REQUIRED TO MEET 13-415.2.ABC.1.1,.1.2 |
| | AND .1.3. |
| | THESE ARE ALL REQUIRED TO BE LOCATED IN THE IDR FOR |
| | ENERGY CODE COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS SHOWN ON |
| | PLANS ARE NOT CODE COMPLIANT. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4. |
| | THERE ARE AREAS WITH STILL NO LIGHTING CONTROLS AND |
| | OVER RIDES WHICH ARE REQUIRED. MAY NOT USE A SINGLE |
| | POLE SWITCH TO OVER RIDE TIMED SCHEDULING? THIS DOES |
| | NOT PROVIDE ANY WAY OF AUTOMATICALLY SHUTTING OFF THE |
| | LIGHTING ONCE OVER RIDDEN. HOW CAN A SINGLE POLE SWITCH |
| | IN AREAS SUCH AS CLASSROOM, COMPUTER LAB BE AN |
| | AUTOMATED OVER RIDE? |
| | THE RESPONSE LETTER MENTIONS THE KITCHEN LIGHTING IS |
| | EXEMPT PER 13-415.1.ABC.1.1. (NUMBER 3) THERE IS NO |
| | EXEMPTION #3 IN THIS SECTION OF THE CODE AND KITCHEN |
| | LIGHTING IS NOT EXEMPT FROM THE REQUIRED AUTOMATED |
| | CONTROLS OF SOME KIND. PLEASE ADJUST PLANS. |
| | PLEASE SEE OTHER AREAS AS THE MULTI-GANG BATHS WILL BE |
| | NOTED BELOW. |
| | PLEASE PROVIDE A WIRING DIAGRAM ON HOW THE NEW |
| | OCCUPANCY SENSORS WILL BE WIRED WITH THE STANDARD |
| | SINGLE POLE SWITCHES WHICH ARE STILL SHOWN ON PLANS. |
| | THE CODE REQUIRES OVER RIDE OF SOME TYPE AT THE POINT |
| | OF ENTRANCE INTO ANY ONE SPACE IF USING TIMED |
| | SCHEDULING. THIS ALSO REQUIRES THE OCCUPANT TO VISUALLY |
| | SEE *ALL* LIGHTING WHICH IS BEING OVER RIDDEN OR MEET |
| | THE EXCEPTION WHICH IS AN INDICATOR PANEL OF SOME TYPE. |
| | |
| | AN EXAMPLE IS THE POINT OF ENTRANCE IN NEW BUILDING |
| | HALLWAY. THERE IS ONLY OVER RIDES AT ONE END AND NOT |
| | BOTH. THERE ARE NO INDICATORS NOTED. PLEASE SEE COMMENT |
| | BELOW WITH RESPECT TO THE TWIST TIMERS SHOWN. |
| | PLEASE SEE THE EXTERIOR LIGHTING IS NOT COMPLETE. THERE |
| | ARE ITEMS SUCH AS EXTERIOR LIGHTING (L4-36) WHICH IS |
| | NOT LISTED ON SCHEDULE. THIS CIRCUIT IS ACTUALLY LISTED |
| | AS *PROJECTION SCREEN* ON PANEL SCHEDULE. |
| | |
| | ** AS SYSTEM IS NOT COMPLETE, THE ABOVE SECTIONS NEED |
| | TO BE MET. |
| | |
| | 3) NOTE: PLEASE PROVIDE THE WIRING DIAGRAM FOR |
| | OCCUPANCY SENSORS AS NOTED ABOVE FOR THE GANG BATHS. IF |
| | THE SINGLE POLE SWITCH AS SHOWN ALLOWS AN OCCUPANT TO |
| | TURN THE LIGHTING OFF IN THE BATHROOMS WHILE ANOTHER |
| | OCCUPANT IS STILL OCCUPYING THE BATHROOM THIS WILL NOT |
| | MEET MINIMUM REQUIRED FOR LIFE SAFETY. AS NO DETAIL FOR |
| | THE TYPE OF DEVICE AND HOW A SINGLE POLE SWITCH WILL BE |
| | CONNECTED IN THIS SCENARIO THIS DOES NOT MINIMUM. |
| | LS 101 7.8, FBC 13-415.1.ABC.1.2, .1.1. |
| | PLEASE PROVIDE SPEC/CUT SHEET FOR THESE DEVICES. 110.3 |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR A GENERATOR AND ATS AS PREVIOUSLY REQUESTED. A |
| | MINIMUM CODE REQUIRED ATS AND GENERATOR WILL BE PART OF |
| | THE PERMITTED SET OF PLANS AND DOCUMENTS. THIS CAN |
| | ALWAYS BE REVISED AT A LATER DATE IF THE MANUFACTURE OR |
| | EQUIPMENT CHANGES. |
| | 110.3,90.7, 702.6 ETC |
| | FBC 106.1.1,106.1.2 |
| | *** IF NOT PART OF THE SCOPE OF WORK THEN DELETE ALL |
| | REFERENCE AND INDICATE AS FUTURE. SEPRATE PERMIT |
| | APPLICATION, PLANS, FEES ECT WILL BE REQUIRED AT A |
| | LATER DATE. |
| | ** IF ATS IS INSTALLED AT THIS TIME WITH SERVICE |
| | EQUIPMENT THEN SUBMIT A CODE COMPLIANT ATS AT THIS |
| | TIME. |
| | |
| | *** RESPONSE LETTER NOTES THIS IS AN OPTIONAL STAND-BY |
| | SYSTEM. IT HAS NO BEARING ON OPTIONAL OR NOT, THE CODE |
| | DOES NOT STATE IF *OPTIONAL* THEN THE EQUIPMENT DOES |
| | NOT NEED TO BE LISTED ETC. |
| | |
| | 5) NOTE: AS NOTED ON PREVIOUS REVIEW PANEL MDP SHALL |
| | CONTAIN A MAIN OR A MAIN DISCONNECTING MEANS AHEAD OF |
| | THIS MLO.THE CODE ADDRESSES THE NUMBER OF MEANS OF |
| | DISCONNECT PERMITTED AND THE PERMITTED SPACES IN THE |
| | EQUIPMENT. THIS INSTALLATION WHICH IS NOTED AS |
| | TEMPORARY DUE TO PHASING HAS NO BEARING ON WHAT *MAY* |
| | OR *MAY NOT* BE PERMITTED IN THE FUTURE. PLANS ARE |
| | REQUIRED TO SHOWN MINIMUM CODE COMPLIANCE AT THIS TIME |
| | OR WILL NOT BE PERMITTED. LIFE SAFETY DOES NOT RELY ON |
| | WHAT MAY BE PERMITTED IN PHASES. THE FACT IS PHASE TWO |
| | MAY NEVER HAPPEN AND THE SERVICE AS SHOWN WOULD BE |
| | NON-CODE COMPLIANT. |
| | CODE SECTIONS 225 FOR DETACHED BUILDINGS ARE INTENDED |
| | TO FOLLOW REQUIREMENTS OF 230 EVEN IF NOT SERVICE |
| | ENTRANCE RATED EQUIPMENT. AS THERE ARE NO PROVISIONS TO |
| | PREVENT THIS HAZARD AS NOTED ABOVE A MAIN IS REQUIRED |
| | AT THIS TIME IN FIRST PHASE. |
| | THIS IS SERVICE ENTRANCE RATED EQUIPMENT AT THIS TIME. |
| | 230 SECTIONS APPLY ALSO.230.70, 230.71, 230.72, 230.76, |
| | 230.79 ETC. |
| | *** NOTE, PHASE ONE OR PHASE TWO HAS NOT APPLIED FOR |
| | ANY PERMIT. |
| | |
| | 6) NOTE: PLEASE SEE NEW RULE 69A-60.004 FOR ADOPTION OF |
| | THE 2006 NFPA-101. AS THIS HAS NOT APPLIED FOR PERMIT. |
| | ** IT WAS NOTED THIS RULE MAY BE GETTING A CHANGE |
| | HOWEVER AT THIS TIME IT IS ADOPTED. |
| | |
| | 7) NOTE: WIND LOADS REFERENCE BOTH THE FBC AND SBCCI. |
| | |
| | ** PLEASE COMPLETE PLANS. |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |