2008-07-28 13:03:56 
 ** DENIED3RD REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS STILL FROM
 PREVIOUS REVIEWS WHICH ARE IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 AND THE INPUT DATA REPORT IS NOT CODE COMPLIANT AND
 DOES NOT COORDINATE WITH THE SUBMITTED PLANS.
 PLEASE SEE THAT THE NUMBER OF FIXTURES AND THE WATTAGES
 OF FIXTURES IS REQUIRED TO MEET 13-415.2.ABC.1.1,.1.2
 AND .1.3.
 THESE ARE ALL REQUIRED TO BE LOCATED IN THE IDR FOR
 ENERGY CODE COMPLIANCE.
  
 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS SHOWN ON
 PLANS ARE NOT CODE COMPLIANT.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
 THERE ARE AREAS WITH STILL NO LIGHTING CONTROLS AND
 OVER RIDES WHICH ARE REQUIRED. MAY NOT USE A SINGLE
 POLE SWITCH TO OVER RIDE TIMED SCHEDULING? THIS DOES
 NOT PROVIDE ANY WAY OF AUTOMATICALLY SHUTTING OFF THE
 LIGHTING ONCE OVER RIDDEN. HOW CAN A SINGLE POLE SWITCH
 IN AREAS SUCH AS CLASSROOM, COMPUTER LAB BE AN
 AUTOMATED OVER RIDE?
 THE RESPONSE LETTER MENTIONS THE KITCHEN LIGHTING IS
 EXEMPT PER 13-415.1.ABC.1.1. (NUMBER 3) THERE IS NO
 EXEMPTION #3 IN THIS SECTION OF THE CODE AND KITCHEN
 LIGHTING IS NOT EXEMPT FROM THE REQUIRED AUTOMATED
 CONTROLS OF SOME KIND. PLEASE ADJUST PLANS.
 PLEASE SEE OTHER AREAS AS THE MULTI-GANG BATHS WILL BE
 NOTED BELOW.
 PLEASE PROVIDE A WIRING DIAGRAM ON HOW THE NEW
 OCCUPANCY SENSORS WILL BE WIRED WITH THE STANDARD
 SINGLE POLE SWITCHES WHICH ARE STILL SHOWN ON PLANS.
 THE CODE REQUIRES OVER RIDE OF SOME TYPE AT THE POINT
 OF ENTRANCE INTO ANY ONE SPACE IF USING TIMED
 SCHEDULING. THIS ALSO REQUIRES THE OCCUPANT TO VISUALLY
 SEE *ALL* LIGHTING WHICH IS BEING OVER RIDDEN OR MEET
 THE EXCEPTION WHICH IS AN INDICATOR PANEL OF SOME TYPE.
  
 AN EXAMPLE IS THE POINT OF ENTRANCE IN NEW BUILDING
 HALLWAY. THERE IS ONLY OVER RIDES AT ONE END AND NOT
 BOTH. THERE ARE NO INDICATORS NOTED. PLEASE SEE COMMENT
 BELOW WITH RESPECT TO THE TWIST TIMERS SHOWN.
 PLEASE SEE THE EXTERIOR LIGHTING IS NOT COMPLETE. THERE
 ARE ITEMS SUCH AS EXTERIOR LIGHTING (L4-36) WHICH IS
 NOT LISTED ON SCHEDULE. THIS CIRCUIT IS ACTUALLY LISTED
 AS *PROJECTION SCREEN* ON PANEL SCHEDULE.
  
 ** AS SYSTEM IS NOT COMPLETE, THE ABOVE SECTIONS NEED
 TO BE MET.
  
 3) NOTE: PLEASE PROVIDE THE WIRING DIAGRAM FOR
 OCCUPANCY SENSORS AS NOTED ABOVE FOR THE GANG BATHS. IF
 THE SINGLE POLE SWITCH AS SHOWN ALLOWS AN OCCUPANT TO
 TURN THE LIGHTING OFF IN THE BATHROOMS WHILE ANOTHER
 OCCUPANT IS STILL OCCUPYING THE BATHROOM THIS WILL NOT
 MEET MINIMUM REQUIRED FOR LIFE SAFETY. AS NO DETAIL FOR
 THE TYPE OF DEVICE AND HOW A SINGLE POLE SWITCH WILL BE
 CONNECTED IN THIS SCENARIO THIS DOES NOT MINIMUM.
 LS 101 7.8, FBC 13-415.1.ABC.1.2, .1.1.
 PLEASE PROVIDE SPEC/CUT SHEET FOR THESE DEVICES. 110.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR A GENERATOR AND ATS AS PREVIOUSLY REQUESTED. A
 MINIMUM CODE REQUIRED ATS AND GENERATOR WILL BE PART OF
 THE PERMITTED SET OF PLANS AND DOCUMENTS. THIS CAN
 ALWAYS BE REVISED AT A LATER DATE IF THE MANUFACTURE OR
 EQUIPMENT CHANGES.
 110.3,90.7, 702.6 ETC
 FBC 106.1.1,106.1.2
 *** IF NOT PART OF THE SCOPE OF WORK THEN DELETE ALL
 REFERENCE AND INDICATE AS FUTURE. SEPRATE PERMIT
 APPLICATION, PLANS, FEES ECT WILL BE REQUIRED AT A
 LATER DATE.
 ** IF ATS IS INSTALLED AT THIS TIME WITH SERVICE
 EQUIPMENT THEN SUBMIT A CODE COMPLIANT ATS AT THIS
 TIME.
  
 *** RESPONSE LETTER NOTES THIS IS AN OPTIONAL STAND-BY
 SYSTEM. IT HAS NO BEARING ON OPTIONAL OR NOT, THE CODE
 DOES NOT STATE IF *OPTIONAL* THEN THE EQUIPMENT DOES
 NOT NEED TO BE LISTED ETC.
  
 5) NOTE: AS NOTED ON PREVIOUS REVIEW PANEL MDP SHALL
 CONTAIN A MAIN OR A MAIN DISCONNECTING MEANS AHEAD OF
 THIS MLO.THE CODE ADDRESSES THE NUMBER OF MEANS OF
 DISCONNECT PERMITTED AND THE PERMITTED SPACES IN THE
 EQUIPMENT. THIS INSTALLATION WHICH IS NOTED AS
 TEMPORARY DUE TO PHASING HAS NO BEARING ON WHAT *MAY*
 OR *MAY NOT* BE PERMITTED IN THE FUTURE. PLANS ARE
 REQUIRED TO SHOWN MINIMUM CODE COMPLIANCE AT THIS TIME
 OR WILL NOT BE PERMITTED. LIFE SAFETY DOES NOT RELY ON
 WHAT MAY BE PERMITTED IN PHASES. THE FACT IS PHASE TWO
 MAY NEVER HAPPEN AND THE SERVICE AS SHOWN WOULD BE
 NON-CODE COMPLIANT.
 CODE SECTIONS 225 FOR DETACHED BUILDINGS ARE INTENDED
 TO FOLLOW REQUIREMENTS OF 230 EVEN IF NOT SERVICE
 ENTRANCE RATED EQUIPMENT. AS THERE ARE NO PROVISIONS TO
 PREVENT THIS HAZARD AS NOTED ABOVE A MAIN IS REQUIRED
 AT THIS TIME IN FIRST PHASE.
 THIS IS SERVICE ENTRANCE RATED EQUIPMENT AT THIS TIME.
 230 SECTIONS APPLY ALSO.230.70, 230.71, 230.72, 230.76,
 230.79 ETC.
 *** NOTE, PHASE ONE OR PHASE TWO HAS NOT APPLIED FOR
 ANY PERMIT.
  
 6) NOTE: PLEASE SEE NEW RULE 69A-60.004 FOR ADOPTION OF
 THE 2006 NFPA-101. AS THIS HAS NOT APPLIED FOR PERMIT.
 ** IT WAS NOTED THIS RULE MAY BE GETTING A CHANGE
 HOWEVER AT THIS TIME IT IS ADOPTED.
  
 7) NOTE: WIND LOADS REFERENCE BOTH THE FBC AND SBCCI.
  
 ** PLEASE COMPLETE PLANS.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]