| 2008-07-15 16:57:51 | BUILDING PLAN REVIEW |
| | PERMIT: 07100001 |
| | ADD: 1505 N AUSTRALIAN AVE. |
| | CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING) |
| | TEL: (561644-7416 JEFF HALVERSON |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | JULY 15,2008 |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL,WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. YOUR PROJECT IS A THRESHOLD BUILDING |
| | REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE SETS OF |
| | ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| | BEACH ADMINISTRATIVE CODE. |
| | THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE |
| | IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*. |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D) COMPLIED. |
| | |
| | 1E) COMPLIED |
| | |
| | 2) COMPLIED |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B) 2ND REQUEST, WHILE MEETING WITH JEFF HALVERSON |
| | ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE |
| | ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S |
| | S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS |
| | WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR |
| | WERE PROVIDED TO MR. HALVERSON AT THE END OF THE |
| | MEETING. |
| | |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | |
| | 6-12) COMPLIED. |
| | |
| | 13) 3RD REQUEST, SEMI-REPLIED. SHEET A-1 DOES INDICATE |
| | WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE |
| | OPENING PROTECTIVES IN THE RATED WALLS SEE 715.3. |
| | NOTE SHEET A101 CLASSROOMS AND THE STORAGE CLOSETS |
| | WITHIN THE CLASSROOMS ARE NOT MARKED OR MISS MARKED ON |
| | THE DOOR SCHEDULE SHEET A-700. |
| | |
| | 14) SEMI-COMPLIED, PLANS ARE INCOMPLETE AND A THROUGH |
| | REVIEW CAN NOT BE COMPLETED AT THIS TIME. |
| | 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS |
| | REQUIRED FOR REVIEW. |
| | |
| | 15) SEMI-COMPLIED. |
| | |
| | 16-17) COMPLIED. |
| | |
| | 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING |
| | REPORTS ,MISSING REPORTS ARE AS FOLLOWS: |
| | A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL |
| | B) WINDOWS OPERABLE WINDOWS: SINGLE HUNG, CASEMENT C) |
| | MULLIONS |
| | D) GLASS BLOCK |
| | E) GLAZED SWING DOORS |
| | F) AUTOMATIC SLIDING DOORS |
| | G) HOLLOW METAL DOORS EXTERIOR (INSULATED) |
| | H) OVERHEAD DOORS |
| | I) TRUSS ANCHORS |
| | J) ROOF HATCHES |
| | K) ROOF ASSEMBLIES |
| | L) PRE-ENGINEERED A/C STANDS |
| | |
| | NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS |
| | (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE |
| | LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH |
| | VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC |
| | GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A |
| | COMPENENT OF THIS BUILDING. |
| | |
| | |
| | 19) 2ND REQUEST, 106.3 PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED |
| | TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 20) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT |
| | COMPLIANCE REPORTS WITH THE FOLLOW ITEMS: |
| | __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES |
| | LIMITATION# 9, NO ENHANCED FASTENING ALLOWED. |
| | |
| | 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS |
| | ASSEMBLY AND NOA'S: |
| | USP C88 NOA 07-0306.06 |
| | USP RT7 NOA07-0306.10 |
| | USPKCB88 FL 822.149 |
| | ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE |
| | REQUIREMENTS OF 18-20. |
| | |
| | 23) COMPLIED. |
| | |
| | 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN |
| | INFORMATION FOR THE ENERGY CODE AND CALCULATIONS, |
| | 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE |
| | CRITERIA. |
| | |
| | 24A) THE TOTAL SQUARE FOOTAGE OF THE BUILDING DOES NOT |
| | CALCULATE, THE TOTAL GROSS AREA TAKEN FROM LS1.0 |
| | EQUALLS 11,159 SQ FT NOT THE 9854 LISTED. SHEET A-700 |
| | ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE THE TOTAL |
| | AREA ON THE ENERGY CALCULATION AS 8913 SQUARE FEET. |
| | PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE GROSS |
| | FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED SPACES |
| | CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO OUTSIDE |
| | AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY SHALL |
| | INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT MAY |
| | FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED SPACE |
| | ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA TO |
| | REFLECT THE TOTAL GROSS AREA. |
| | |
| | 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF |
| | FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A |
| | INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY |
| | CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC |
| | ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED |
| | VALUE WAS TAKEN. 13-405.2AB |
| | |
| | 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY |
| | WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS |
| | 25,26 & 27. 13-401.2AB.2 |
| | |
| | 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS |
| | INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS |
| | CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL |
| | DOORS. |
| | |
| | 24E) ROOF INSULATION, PLANS DO NOT CALL OUT THE ACTUAL |
| | THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO |
| | BE INSTALLED. NOR HAS THE ROFING NOAS BENN PROVIDED AND |
| | SUB-SYSTEMS CIRCLED INDICATING THE TYPE OF ROOFING AND |
| | APPROPRIATE INSULATION PROVIDED. SEE A-602. |
| | 13-404.1AB.1/ 13-404.2AB.3. |
| | |
| | 25) COMPLIED. |
| | |
| | RENOVATIONS TO THE EXISTING NORTH WING |
| | |
| | 26A) THE DESIGN TEAM HAS DRAWWN AN ASSUMED PROPERTY |
| | LINE BETWEEN THE TWO BUILDINGS AND DECLARED THE |
| | BUILDING WITH RENOVATION TO BE A A-3 OCCUPANCY AND |
| | BUILDING TYPE III-B WITH ALLOWABLE AREA OF 9500 SQ FT. |
| | SHEET A-100 PROJECT DATA INDICATES THE FOOTPRINT TO BE |
| | 17, 600 SQ FT EVEN WITH COMPUTING AREA INCREASES WITH |
| | F/P THE ALLOWABLE INCREASE OF 5903 BRINGS THE ALLOWABLE |
| | AREA UP TO 15,403. NO AREA INCREASES WERE TAKEN FOR |
| | FIRE SPRINKLERS, AT A MINIMUM THIS BUILDING WOULD NEED |
| | TO BE A TYPE III-A SEE TABLE 601AND 602.3. INTERIOR |
| | BUILDING ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS |
| | CODE. |
| | |
| | |
| | 26B) COMPLIED. |
| | |
| | 26C) COMPLIED. |
| | |
| | 27-29) COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |