Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop B
Sequence Number 3
Notes
Date Text
2008-07-15 16:57:51BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 15,2008
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL,WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS A THRESHOLD BUILDING
 REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE SETS OF
 ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*.
  
 1C) COMPLIED.
  
 1D) COMPLIED.
  
 1E) COMPLIED
  
 2) COMPLIED
  
 3-4) COMPLIED.
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST, WHILE MEETING WITH JEFF HALVERSON
 ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE
 ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S
 S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS
 WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR
 WERE PROVIDED TO MR. HALVERSON AT THE END OF THE
 MEETING.
  
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE
 THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
  
 6-12) COMPLIED.
  
 13) 3RD REQUEST, SEMI-REPLIED. SHEET A-1 DOES INDICATE
 WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE
 OPENING PROTECTIVES IN THE RATED WALLS SEE 715.3.
 NOTE SHEET A101 CLASSROOMS AND THE STORAGE CLOSETS
 WITHIN THE CLASSROOMS ARE NOT MARKED OR MISS MARKED ON
 THE DOOR SCHEDULE SHEET A-700.
  
 14) SEMI-COMPLIED, PLANS ARE INCOMPLETE AND A THROUGH
 REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS
 REQUIRED FOR REVIEW.
  
 15) SEMI-COMPLIED.
  
 16-17) COMPLIED.
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL
 B) WINDOWS OPERABLE WINDOWS: SINGLE HUNG, CASEMENT C)
 MULLIONS
 D) GLASS BLOCK
 E) GLAZED SWING DOORS
 F) AUTOMATIC SLIDING DOORS
 G) HOLLOW METAL DOORS EXTERIOR (INSULATED)
 H) OVERHEAD DOORS
 I) TRUSS ANCHORS
 J) ROOF HATCHES
 K) ROOF ASSEMBLIES
 L) PRE-ENGINEERED A/C STANDS
  
 NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS
 (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE
 LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH
 VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC
 GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A
 COMPENENT OF THIS BUILDING.
  
  
 19) 2ND REQUEST, 106.3 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 20) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) THE TOTAL SQUARE FOOTAGE OF THE BUILDING DOES NOT
 CALCULATE, THE TOTAL GROSS AREA TAKEN FROM LS1.0
 EQUALLS 11,159 SQ FT NOT THE 9854 LISTED. SHEET A-700
 ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE THE TOTAL
 AREA ON THE ENERGY CALCULATION AS 8913 SQUARE FEET.
 PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE GROSS
 FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED SPACES
 CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO OUTSIDE
 AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY SHALL
 INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT MAY
 FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED SPACE
 ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA TO
 REFLECT THE TOTAL GROSS AREA.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2AB
  
 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY
 WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS
 CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL
 DOORS.
  
 24E) ROOF INSULATION, PLANS DO NOT CALL OUT THE ACTUAL
 THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO
 BE INSTALLED. NOR HAS THE ROFING NOAS BENN PROVIDED AND
 SUB-SYSTEMS CIRCLED INDICATING THE TYPE OF ROOFING AND
 APPROPRIATE INSULATION PROVIDED. SEE A-602.
 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) THE DESIGN TEAM HAS DRAWWN AN ASSUMED PROPERTY
 LINE BETWEEN THE TWO BUILDINGS AND DECLARED THE
 BUILDING WITH RENOVATION TO BE A A-3 OCCUPANCY AND
 BUILDING TYPE III-B WITH ALLOWABLE AREA OF 9500 SQ FT.
 SHEET A-100 PROJECT DATA INDICATES THE FOOTPRINT TO BE
 17, 600 SQ FT EVEN WITH COMPUTING AREA INCREASES WITH
 F/P THE ALLOWABLE INCREASE OF 5903 BRINGS THE ALLOWABLE
 AREA UP TO 15,403. NO AREA INCREASES WERE TAKEN FOR
 FIRE SPRINKLERS, AT A MINIMUM THIS BUILDING WOULD NEED
 TO BE A TYPE III-A SEE TABLE 601AND 602.3. INTERIOR
 BUILDING ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS
 CODE.
  
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.