| 2009-12-01 12:24:59 | BUILDING PLAN REVIEW |
| | PERMIT: 07100001 |
| | ADD: 1501 N AUSTRALIAN AVE |
| | CONT: BRADANNA INC. |
| | TEL: (561)722-1425 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION REVIEW OF THE EXISTING NORTH WING |
| | DATED 10-12-09 |
| | |
| | BUILDING PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) SHEET LS-100, A-101 & A-700 INDICATE A REVISION IN |
| | DOORS 6, 8,9,10 & 35 ALL BEING REVISED TO NEW 45 MINUTE |
| | DOORS, THE ISSUE IS THEY ARE EXISTING 2'-6" WIDE. |
| | PLEASE REVIEW SECTION 11-4.6(1)(B)IF EXISTING ELEMENTS, |
| | SPACES, OR COMMON AREAS ARE ALTERED, THEN EACH SUCH |
| | ALTERED ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY |
| | WITH THE APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO |
| | SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW |
| | CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW |
| | CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON |
| | AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT, |
| | SPACE, OR COMMON AREA IS NOT REQUIRED TO BE ON AN |
| | ACCESSIBLE ROUTE EXCEPT AS PROVIDED IN SECTION |
| | 11-4.1.6(2), ALTERATIONS TO AN AREA CONTAINING A |
| | PRIMARY FUNCTION. |
| | |
| | 11-4.1 MINIMUM REQUIREMENTS. |
| | 11-4.1.1 APPLICATION. |
| | (1) GENERAL. THIS CODE ESTABLISHES THE MINIMUM |
| | STANDARDS FOR THE ACCESSIBILITY OF BUILDINGS AND |
| | FACILITIES BUILT OR ALTERED WITHIN THE STATE. |
| | (B) REMOVAL OF ARCHITECTURAL BARRIERS FROM BUILDINGS, |
| | STRUCTURES, OR FACILITIES SHALL COMPLY WITH SECTION |
| | 11-4.1.8 OF THIS CODE UNLESS COMPLIANCE WOULD RENDER |
| | THE REMOVAL NOT READILY ACHIEVABLE. IN NO INSTANCE |
| | SHALL THE REMOVAL OF AN ARCHITECTURAL BARRIER CREATE A |
| | SIGNIFICANT RISK TO THE HEALTH OR SAFETY OF AN |
| | INDIVIDUAL WITH A DISABILITY OR OTHERS. |
| | |
| | 11-4.1.3 ACCESSIBLE BUILDINGS: NEW CONSTRUCTION. |
| | THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS, |
| | STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER |
| | CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON (OR |
| | BEFORE) OCTOBER 1, 1997. |
| | (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH |
| | SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR FACILITY. |
| | |
| | ARCHITECTURAL SHEETS SUBMITTED: |
| | LS-1 |
| | A-101 |
| | A-102 |
| | A-700 |
| | |
| | |