Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop P
Sequence Number 2
Notes
Date Text
2008-05-10 13:09:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT,
 ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL
 CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA
 STATUTES.
 ****RESPONSE NOTED, BUT THE BUSINESS LICENSE,
 (CERTIFICATE OF AUTHORIZATION), IS NOT INDICATED IN THE
 TITLE BLOCK FOR THE ARCHITECT. FAC 61G1-16.004(2) & FS
 481.219. (THIS FOR LANDSCAPE AND IRRIGATION SHEETS
 ALSO).
  
 3. OK
  
 4. SHT G-100 THE INDEX OF DRAWINGS INDICATES AN
 EXISTING BUILDING. THE DESCRIPTION OF THE PROJECT ON
 THE PERMIT APPLICATION SHALL REFLECT THE PROJECT IN
 DETAIL. PLEASE HAVE THE DESCRIPTION INDICATE AN
 EXISTING BUILDING, IF IT AN ALTERATION, RENOVATION ETC.
 AND IF IT IS A CHANGE OF OCCUPANCY OR NOT AS REQUIRED
 ON THE APPLICATION. ALSO THE TITLE BLOCK PROJECT NAME,
 "GAINES PARK COMMUNITY CENTER EXPANSION" & THE "NEW
 FACILITY" ON SHT A-100 IS NOT INDICATED IN THE PROJECT
 DESCRIPTION ON THE PERMIT APPLICATION. PLEASE CLARIFY.
 SECTION 105.3.
 ****RESPONSE NOTED, BUT THE PERMIT APPLICATION
 DESCRIPTION OF WORK STILL DOES NOT REFLECT THE SCOPE OF
 WORK OF THE PLANS.
  
 5. OK
 6. OK
  
 7. NINE SHEETS WERE SUBMITTED WITH DIFFERENT
 INFORMATION BUT THE SAME SHEET NUMBERS. THIS IS NOT
 APPROVED. (SEE SHEETS G-100, A-101, A-102, A-401 THRU
 A-405 & A-700) SECTION 106.1.3. PLEASE SUBMIT 2
 COMPLETE SETS OF PLANS FOR ALL WORK TO REFLECT THE
 DESCRIPTION OF WORK DETAILED ON THE PERMIT APPLICATION.
 SHEET NUMBERS SHALL NOT DUPLICATE WITH DIFFERENT
 INFORMATION.
 ****RESPONSE NOTED, BUT THIS IS NOT REFLECTED ON THE
 PERMIT APPLICATION DESCRIPTION OF WORK AS REQUIRED.
  
 8. INDICATE THE LEVEL OF ALTERNATION FOR THE EXISTING
 BUILDING PER CHAPTER 3 OF THE EXISTING BUILDING CODE.
 ****RESPONSE NOTED, BUT LEVEL OF ALTERATION IS NOT
 INDICATED ON THE PLANS. INDICATE LEVEL 1, LEVEL 2, OR
 LEVEL 3.
  
 9. SHT G-100 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEET SUBMITTED. SHT A-800 NOT SUBMITTED. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHTS 11, 12, 13, L-5.2, L-5.3
 P-4 & P-5 WERE SUBMITTED BUT ARE NOT SHOWN ON THE INDEX
 OF DRAWINGS. PLEASE CORRELATE. SECTION 106.1.3.
  
 10. OK
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT IF FOOD IS BEING SERVED THEN A
 REVIEW BY THE COUNTY HEALTH DEPT. IS REQUIRED.
  
 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE
 PREPARED?A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE
 CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS, (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL
 COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS
 REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE
 III SECTION 90-124(7)(F).
 ****RESPONSE NOTED, BUT NO EVIDENCE OF CONTACT WITH
 ENVIRONMENTAL COMPLIANCE. PLEASE COMPLY WITH INITIAL
 REQUEST.
  
 13. OK
 14. OK
 15. OK
  
 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED.
 ___FOR ACCESS. STALL:
 A. 11-4.17.3 EXCEPTION(2) THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR.
 ****NOT ADDRESSED.
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED.
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. OK
  
 17. SUBMIT A DETAIL/ELEVATION FOR THE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 18. SHT A-700 FINISH SCHEDULE FOR ROOMS 164 & 166. THE
 WALLS WITHIN 2 FEET OF WATER CLOSETS AND URINALS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. SECTION
 S-1210.2. PLEASE INDICATE HOW PAINT COMPLIES WITH THESE
 REQUIREMENTS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 19. OK
 20. OK
 21. OK
  
 22. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM IS NOT
 COMPLETE. SHOW ALL PIPING TO ALL FIXTURES ON THE RISER.
 SECTION 106.3.5.1.3(4)(6)(13).
 ****RESPONSE NOTED, BUT FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR THE ICE MAKER IN THE PANTRY. SECTIONS
 802.3 & 802.3.2.
  
 23. OK
  
 24. SUBMIT STORM PIPING INFORMATION. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF DRAINS. SUBMIT A
 STORM ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES,
 OFFSETS & TERMINATION POINT. SECTION
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE PIPING SHALL BE INSTALLED
 WITH A UNIFORM SLOPE. ONE RISER HAS THE HORIZONTAL
 PIPING FROM THE FIRST ROOF DRAIN AT 1/4"/FT THEN
 CHANGES TO 1/8"/FT AFTER THE SECOND ROOF DRAIN AND THEN
 CHANGES BACK TO 1/4"/FT AFTER THE THIRD ROOF DRAINL.
 THE PIPING SHALL BE 1/4"/FT THROUGHOUT THE RUN. SECTION
 7-4.1. (THIS SHALL BE CHANGED ON THE ROOF PLAN ALSO).
  
 25. OK
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF THE CUT SECTIONS
 ARE NOT SHOWN ON THE RISER DIAGRAM.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN COMMENT
 "A" IS ADDRESSED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE "ETR"
 & WITHIN 6' OF THE GENERATOR PER SECTION 409.5. PLEASE
 INDICATE ON THE GAS RISER DIAGRAM.
  
 2B. PER TABLE 402.4(2), 2-1/2" PIPE IS REQUIRED FOR THE
 GAS LINE TO THE GENERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved