Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop G
Sequence Number 2
Notes
Date Text
2008-05-10 13:14:02DENIED
 REFERENCE: FBC-2004 FUEL GAS CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF THE CUT SECTIONS
 ARE NOT SHOWN ON THE RISER DIAGRAM.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN
 COMMENT "A" IS ADDRESSED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE "ETR"
 & WITHIN 6' OF THE GENERATOR PER SECTION 409.5. PLEASE
 INDICATED ON THE GAS RISER DIAGRAM.
  
 2B. PER TABLE 402.4(2), 2-1/2" PIPE IS REQUIRED FOR THE
 GAS LINE TO THE GENERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved