Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-21 16:29:48** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SEVERAL ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE NEW
 COMMENTS AS PLANS ARE NOW MORE COMPLETE THAN SUBMITTED
 ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE BOTH SETS OF PLANS FOR BOTH
 BUILDING DO NOT CONTAIN AN ORIGINAL SIGNATURE BY THE
 ENGINEER OF RECORD. IN FACT EACH AND EVERY SIGNATURE IS
 A *RUBBER-STAMP* ON ALL FOUR SETS OF PLANS. THIS IS
 DONE IN LIEU OF THE REQUIRED ORIGINAL SIGNATURE AS
 REQUIRED PER FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 THIS OFFICE HAS MADE THIS SAME COMMENT TO THIS DESIGNER
 OF RECORD ON SEVERAL OTHER REVIEWS ON OTHER PROJECTS
 YET PLANS ARE STILL BEING SUBMITTED WITH THE SAME
 *RUBBER-STAMP*.
 THIS OFFICE IS LEFT WITH NO CHOICE BUT TO FORWARD ALL
 PLANS AND DOCUMENTS TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF SAID STATUTORY
 VIOLATIONS.
 THESE WILL BE SENT WITH PLANS FROM OTHER PROJECT
 PREVIOUSLY RETAINED FOR THE SAME COMMENT.
 PLEASE KNOW WHEN SIGNING, DATING AND SEALING PLANS: ALL
 MUST BE ORIGINAL SIGNATURE. A *RUBBER-STAMP* SHALL NOT
 BE USED. THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD
 OF ENGINEERS AND LEGAL COUNSEL TO THE BOARD ON MANY
 OCCASIONS.
  
 2) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF
 ALL DOCUMENTS INCLUDING ENERGY CALCULATIONS. ONLY ONE
 SET OF CALCULATIONS WERE SUBMITTED.
 FBC 106.1, 106.1.3, 106.5.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FLORIDA BUILDING
 CODE AND CHAPTER 13 FOR CODE REQUIRED LIGHTING CONTROLS
 HAS NOT BEEN MET. THIS WAS A COMMENT ON THE PREVIOUS
 REVIEW AS NO LIGHTING CONTROL SYSTEM WAS DESIGNED INTO
 THE PROJECT ON ORIGINAL PLANS SUBMITTED. RESPONSE
 MENTIONS TO SEE REVISED PLANS HOWEVER COMPLIANCE WITH
 CHAPTER 13 HAS STILL NOT BEEN MET.
 PLEASE SEE NOTE # 7 ON SHEET E-2: THIS NOTE SATES
 *LIGHTING CONTROLS SHALL BE PROVIDED TO MEET PARAGRAPH
 13-415.1.ABC.1.1 OF THE FLORIDA BUILDING CODE*. THE
 CODE SHALL NOT BE QUOTED IN LIEU OF REQUIRED DESIGN.
 PLEASE SEE OTHER SECTIONS OF CHAPTER 13 FOR LIGHTING
 CONTROLS IS ALSO REQUIRED SUCH AS 13-415.1.ABC.1.2,
 13-415.1.ABC.1.3 AND 13-415.1.ABC.1.4.
 PLEASE TAKE A LOOK AT SECTION 13-415.1.ABC.1.1 AND
 .1.2. THE LIGHTING CONTACTORS AS SHOWN DO NOT PROVIDE
 CODE COMPLIANCE. IN FACT ALL DEVICES IN ALL *SEPARATE
 SPACES* ARE STILL BEING SHOWN AS STANDARD SWITCHING
 DEVICES. PLEASE SEE THIS IS CLEAR ON THE SYMBOL LEGEND
 ON E-7 AS WELL AS NOTE #5 ON E-2. IT IS NOT POSSIBLE TO
 USE *STANDARD SWITCHES* WHEN MOST LIGHTING CIRCUITS ARE
 ALL GOING THROUGH LIGHTING CONTACTORS.
 PLEASE SEE THESE SAME SECTIONS OF CODES AS *ALL
 SEPARATE SPACES* ARE REQUIRED TO CONTAIN CONTROLS TO
 OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLEASE SEE LIGHTING CONTROLS ARE REQUIRED TO BE LOCATED
 SO THE OCCUPANT CAN SEE THE LIGHTING IN WHICH IS BEING
 CONTROLLED OR MEETING THE EXCEPTIONS FOR *PILOT LIGHTS*
 ETC.
 PLEASE ALSO SEE 13-415.1.ABC.1.2 FOR OTHER TYPES OF
 ROOMS WHICH REQUIRE OCCUPANCY SENSOR DEVICES. THIS IS
 ABOVE ANY TIME OF DAY LIGHTING CONTROLS.
 EXAMPLES: AS LISTED IN THE CODE, CLASSROOMS,
 CONFERENCE/MEETING ROOMS, LUNCH, BREAK ROOMS.
 PLEASE THE LIGHTING CONTACTOR AND PLANS AS SHOWN DOES
 NOT SHOW ANY OVER RIDES, DOES NOT SHOW ANY SPACE
 CONTROLS ETC.
 PLEASE SEE 13-415.1.ABC.1.3 FOR *ADDITIONAL CONTROLS*
 REQUIRED.
 PLEASE SEE 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING
 CONTROLS. PLANS INDICATE LIGHTING TO BE THROUGH A TIME
 CLOCK HOWEVER THIS SECTION OF THE CODE REQUIRES ONE OF
 TWO METHODS OF CONTROL. PLEASE KNOW IF USING A TIME
 CLOCK THIS SHALL BE AN ASTRONOMICAL TIME CLOCK NOT A
 STANDARD TIME CLOCK. THIS TC MUST ALSO CONTAIN A
 MINIMUM BATTERY BACK UP FOR PROGRAMMING WHICH CONTAINS
 A MINIMUM 10 HOURS OF BACK UP.
  
 ** IT IS IMPORTANT TO KNOW AS SEVERAL DEVICES ON PLANS
 WILL BE REQUIRED TO BE REVISED TO MEET MINIMUM CODE
 COMPLIANCE THERE MAY CERTAINLY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS
 TIME.
  
 *** PLEASE SEE COMMENT BELOW WITH RESPECT TO HAND-WOUND
 TIMERS SHOWN ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SEE FLORIDA BUILDING CODE CHAPTER 13
 FOR LIGHTING PERFORMANCE AND CODE COMPLIANT ENERGY
 CALCULATIONS TO BE SUBMITTED.
 PLEASE SEE 13-400.0.A, 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THE METHOD OF CALCULATION SUBMITTED FOR THE
 NEW BUILDING IS METHOD *A* HOWEVER NO CALCULATIONS WERE
 SUBMITTED FOR THE EXISTING SEPARATE BUILDING WHICH IS
 BEING RENOVATED.
 PLEASE SEE THE VERSION SUBMITTED IS NOT UNDER THE
 ADOPTION OF THE FBC 13-400.3.A. PLEASE SEE THE CODE
 SPECIFICALLY ADOPTS VERSION 2.5 AND THE VERSION
 SUBMITTED WAS 3.0. THIS HAS BEEN CONFIRMED WITH THE
 DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING
 COMMISSION ON MORE THAN ONE OCCASION.
 PLEASE ALSO SEE THE CERTIFICATION SHEETS LIST
 MECHANICAL AND ELECTRICAL DESIGNERS WHICH ARE NOT
 LISTED AS ENGINEERS. IN FACT THE DESIGNER WHICH IS
 SIGNED, DATED AND SEALED ON THE CERTIFICATIONS IS NOT
 EVEN LISTED WITH NAME OR LICENSE NUMBER YET THIS
 DESIGNER IS LISTED ON PLANS AS THE MECHANICAL DESIGNER
 OF RECORD.
 PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS DO NOT
 MEET THE MINIMUM FOR CODE COMPLIANCE. IN FACT THERE ANY
 SEVERAL ITEMS ON PLANS THAT DO NOT COORDINATE WITH THE
 INPUT DATA REPORT. SOME EXAMPLES WILL BE GIVEN BELOW
 HOW THESE ARE NOT AN EXHAUSTIVE LIST OF ALL ITEMS: THE
 INPUT DATA REPORT WILL BE NOTED AS IDR.
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR EXTERIOR LIGHTING SHOWS NO
 LIGHTING AND IS COMPLETELY *BLANK*. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY INDICATE AND SHOW
 DOZENS OF EXTERIOR LIGHTS?
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR INTERIOR LIGHTING WHICH
 INDICATES *MANUAL ON/OFF* CONTROLS FOR ALL INTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN ALL INTERIOR
 LIGHTING IS REQUIRED TO BE UNDER SOME SORT OF AUTOMATED
 CONTROL?
 FOR EXAMPLE:
 PLEASE SEE THE WATER HEATER KW RATINGS SHOWN ON THE IDR
 DO NOT COORDINATE WITH PLANS AS THE PLANS INDICATE A
 HIGHER KW RATING.
 ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE BE
 SURE TO GO THROUGH ALL LIGHTING ON PLANS, METHOD OF
 CONTROLS, TYPES OF FIXTURES, WATTAGE OF FIXTURES AND
 NUMBERS OF FIXTURES. THESE WERE A FEW EXAMPLES ONLY.
  
 5) NOTE: PLEASE SEE THE CONDUIT SIZES AS LISTED ON E-4
 ON CONDUIT/WIRE NOTES. PLEASE SEE NOTES #1, 2 AND 3
 WHICH INDICATE AS MANY AS 4-500MCM AND EQUIPMENT
 GROUNDING CONDUCTOR?S 1/0 AND 2/0 IN TWO-INCH CONDUITS.
 THIS IS NOT POSSIBLE AS WELL AS NOT MEETING CODE FOR
 DE-RATING AND MINIMUM CONDUIT SIZING. PLEASE SEE
 CONDUIT FILL TABLES IN CHAPTER 9 OF THE NEC AND
 300.17.
  
 6) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE STILL
 SHOWING THE INSTALLATION OF A NATURAL GAS GENERATOR.
 THIS UNIT NEEDS TO BE CLASSIFIED AS *OPTIONAL STAND-BY*
 ONLY AS THIS IS NOT FOR AN EMERGENCY/LIFE SAFETY OR
 LEGALLY REQUIRED SYSTEMS.700,701,702.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED GENERATOR AND ATS AS REQUESTED ON THE PREVIOUS
 REVIEW. RESPONSE MENTIONS THIS WILL BE DONE UNDER SHOP
 DRAWING SUBMITTALS HOWEVER IF THIS SCOPE IS INCLUDED IN
 THIS BASE BUILDING OR AS SHOWN ANY WORK WILL BE DONE
 UNDER BASE BUILDING THESE SHALL BE SUBMITTED AT THIS
 TIME.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** IT IS IMPORTANT TO KNOW IF THE GENERATOR UNIT FEEDS
 ANY LIFE SAFETY OR LEGALLY REQUIRED LOADS THERE MAY
 ALSO BE OTHER REQUIREMENT SIN NFPA-110 WHICH ARE
 REQUIRED TO BE MET.
 PLEASE SEE FBC CHAPTER 27 WHICH REFERENCES ALL BACK UP
 POWER SYSTEMS SHALL BE INSTALLED PER NFPA-110. AS THERE
 IS INFORMATION NOT YET SUBMITTED SOME COMMENTS CAN NOT
 BE MADE.
 PLEASE SEE LOCATION SHALL MEET CHAPTER 7 FOR ROOM
 CONSTRUCTION, VENTILATION, ELECTRICAL EQUIPMENT
 INSTALLATION ETC.
  
 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 8) NOTE: PLEASE CLARIFY THE MAIN BREAKER DISCONNECT
 BEING SHOWN. THE PLANS CALL FOR A *SHUNT-TRIP* WHICH
 MAY NOT BE USED IN LIEU OF THE REQUIRED MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76,
 230.79.
 THE NOTE #14 ON PLANS ON SHEET E-4 GIVES ANY PERSON
 FALSE SENSE THAT THE MAIN WILL BE TURNED OFF BY USE OF
 SHUNT TRIP.
 THE MEANS OF DISCONNECTS FOR MAIN WILL BE LABELED FOR
 NORMAL AND EMERGENCY, NOT THE SHUNT TRIP.
 PLEASE SEE 230.2E, 702.8.
 PLEASE ALSO PLACE NOTES ON PLANS THAT OTHER BUILDINGS
 WHICH WILL NOW BED FED FROM TWO SOURCES OF POWER SHALL
 CONTAIN NOTES FOR SIGNS AT EACH OF THESE EXISTING
 LOCATIONS.
  
 9) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE SYSTEMS AT
 EACH STRUCTURE AND SERVICE PER 250.50. THE PLANS SHALL
 SHOW MINIMUM REQUIRED ATTACHMENTS. QUOTING THE CODE IN
 LIEU OF MINIMUM REQUIRED BY CODE IS NOT ACCEPTABLE.
 PLEASE BE SURE TO SEE 250.32, 250.50 AT ANY DETACHED
 BUILDINGS.
  
 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN ON THE LINE SIDE OF PANEL MDP TO
 THE THIS MDP.250.50, 250.110, 250.122, 250.32 ETC
 THE EQUIPMENT GROUND IS BROUGHT TO THE MAIN BUT NOT
 FROM MAIN TO MDP.
  
 11) NOTE: PLEASE SEE THE CODE SECTIONS GIVEN ON THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC) ADOPTED BY THE STATE OF FLORIDA.
 PLANS SHOW 220.35
 PLEASE SUBMIT THE FPL DOCUMENTS SUPPORTING THE
 DE-RATING OF SOME SERVICE EQUIPMENT AS MUCH AS 600AMPS.
 220.87
 FBC 106.1.2
  
 12) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED ARC
 FLASH PROTECTION PER 110.16
  
 13) NOTE: PLEASE KNOW AT THIS POINT IN TIME THE
 APPLICATION CODE IS THE 2004 FBC WITH THE 2007
 REVISIONS.
 THE STATE OF FLORIDA IS SCHEDULED TO ADOPT NEW CODE
 STANDARDS ON OCT 1ST, 2008.
  
 14) NOTE: PLEASE SEE THAT ALL INFORMATION ON TITLE
 BLOCKS IS REQUIRED TO BE COMPLETE AND ACCURATE. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 61G1-16.004, FLORIDA STATUTES 471.023 AND 481.219 FOR
 REQUIRED INFORMATION AND LICENSING INFORMATION TO BE ON
 TITLE BLOCKS.
 THIS COMMENT IS MADE UNDER ELECTRICAL REVIEW BASED ON
 THE FACT THE TITLE BLOCKS FOR ALL FIRMS ARE LISTED ON
 ALL SHEETS AND LICENSE INFORMATION ON AT LEAST ONE FIRM
 IS NOT LISTED AND CURRENT WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 ** LANDSCAPE ENGINEER**.
 PLEASE SEE LANDSCAPE PLANS INDICATE A *LANDSCAPE
 ARCHITECTURAL FIRM* NOT A LANDSCAPE ENGINEERING FIRM.
 PLEASE SEE THE TITLE BLOCKS ON OTHER SHEETS SUCH AS
 LANDSCAPE SHEETS; CIVIL SHEETS ETC DO NOT CONTAIN
 LICENSING INFORMATION AS REQUIRED UNDER ADMINISTRATIVE
 CODES OR STATUTES. THIS INFORMATION MAY OR MAY NOT BE
 MADE UNDER OTHER TRADE REVIEWS. IN ANY CASE THESE ARE
 IN VIOLATION OF SECTIONS GIVEN AND SHALL BE MET WHETHER
 OR NOT COMMENT IS MADE BY ANY OTHER TRADE REVIEWER(S).
 THIS COMMENT DOES APPLY TO SMITH ENGINEERING AS THEIR
 INFORMATION LISTED IS CORRECT INFORMATION ON THEIR
 TITLE BLOCKS.
 THIS COMMENT DOES APPLY TO ALL MEP PLANS AS THESE OTHER
 FIRMS ARE LISTED ON THE MEP SHEETS.
  
 15) NOTE: PLEASE COORDINATE ALL PLANS FOR BOTH
 BUILDINGS FOR SERVICE EQUIPMENT ETC.
 PLEASE SEE ONE EXAMPLE OF THIS IS THE RISER ON THE
 RENOVATED GYM BUILDING INDICATES CLEARLY THE EXISTING
 CT CAN IS TO REMAIN AND DOES NOT SHOWN ANY NEW MAIN
 DISCONNECT BEING FED FROM THE NEW DP PANEL AT THE NEW
 BUILDING. THE RISER ON SHEET E-4 ON THE NEW BUILDING
 SHOWS AND NOTES A NEW 600AMP MAIN HOWEVER THE RISER ON
 SHEET E-3 FOR THE RENOVATED GYM DOES NOT SHOW ANY NEW
 MAIN.
 PLEASE SEE THE EXISTING GYM BUILDING RISER ON SHEET E-3
 CLEARLY INDICATES A NEW 600AMP MDP YET THE RISER ON
 SHEET E-4 OF NEW BUILDING SHOWS *EXISTING* 600AMP MDP.
 240.4, 310.16, 225.31-225.39, 250.32 ETC.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
  
 16) NOTE: PLEASE SEE AS NOTED ABOVE THIS SUPPOSED NEW
 600AMP MDP AS SHOWN ON THE RENOVATED PLANS ON SHEET E-3
 SHOWS EACH BREAKER AS MAIN 1 OF 4, 2 OF 4, 3 OF 4, 4 OF
 4 AND THEN A 5 OF 4. HOW CAN THIS BE 5 OF 4? EACH OF
 THESE WOULD BE 1 OF 5 ETC.
 PLEASE KNOW IN ANY CASE IF THIS PANEL BOARD WILL BE A
 NEW MDP, THERE MAY NOT BE SPACE FOR MORE THAN 6 MAINS.
 THIS EQUIPMENT IS SHOWN WITH 30 SPACES AND THIS
 EQUIPMENT IS SHOWN AS A MLO (MAIL LUG ONLY) BOARD.
 THIS IS NOT PERMITTED. 225.33A
 PLEASE COORDINATE WITH RISER ON SHEET E-4 OF NEW
 BUILDING PLANS AS A MAIN IS SHOWN IN FRONT OF THIS
 EQUIPMENT. IF THIS IS THE CASE EACH BRANCH BREAKER
 WOULD NOT BE LABEL *MAINS 1 OF 4/5*.
 THESE WOULD NO LONGER BE MAINS.
  
 17) NOTE: PLEASE SEE NOTES ABOVE FOR NEW BUILDING WITH
 RESPECT TO REQUIRED LIGHTING CONTROLS, DEVICES, OVER
 RIDES, SEPARATE SPACES ETC ALSO APPLIED TO THE
 RENOVATED BUILDING.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4.
  
 18) NOTE: PLEASE KNOW ENERGY CALCULATIONS PER
 13-101.1.3, 13-400.3.B, 13-400.3.C MAY BE REQUIRED
 BASED ON RENOVATION VALUE. AT THIS TIME THIS CAN NOT BE
 CONFIRMED AS THE APPLIED VALUE HAS NOT BEEN
 DETERMINED.
  
 19) NOTE: PLEASE SEE FBC CHAPTER 11, AS SPRING WOUND
 TIMERS IN ACCESSIBLE AREAS ARE NOT PERMITTED. THESE DO
 NOT MEET THE FOLLOWING SECTION.
 11-4.27.4 CONTROLS AND OPERATING MECHANISMS SHALL BE
 OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN
 5 LBF (22.2 N).
  
 20) NOTE: PLEASE SEE THE POWER PLANS AND PLANS IN
 GENERAL NEED TO SHOW THE LOCATION OF ALL PANELS AND
 SERVICE EQUIPMENT.
 PLEASE SEE RISER WHICH INDICATES A NEW BACK FEED FROM
 NEW *DP* TO EXISTING *SW* HOWEVER COULD NOT LOCATE THE
 LOCATION OF THIS EXISTING *SW*.
 NOTE ON RISER MENTIONS TO GROUND PER 250 OF THE NEC
 HOWEVER AS NOTED ABOVE, MAY NOT QUOTE CODE IN LIEU OF
 REQUIRED DETAIL.
 PLEASE SHOW LOCATION OF *SW*, COULD NOT LOCATE THIS ON
 THE GYM BUILDING PLANS AS SHEET E-4 ON NEW BUILDING DP
 NOTES THIS IS THE LOCATION. HOWEVER THIS CAN NOT BE
 CONFIRMED.
 110.26, 240.24 ETC
  
 21) NOTE: PLEASE KNOW PLANS ARE BEING RETAINED AT THIS
 TIME.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]