| 2008-05-21 16:29:48 | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE SEVERAL ITEMS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE NEW |
| | COMMENTS AS PLANS ARE NOW MORE COMPLETE THAN SUBMITTED |
| | ON PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE BOTH SETS OF PLANS FOR BOTH |
| | BUILDING DO NOT CONTAIN AN ORIGINAL SIGNATURE BY THE |
| | ENGINEER OF RECORD. IN FACT EACH AND EVERY SIGNATURE IS |
| | A *RUBBER-STAMP* ON ALL FOUR SETS OF PLANS. THIS IS |
| | DONE IN LIEU OF THE REQUIRED ORIGINAL SIGNATURE AS |
| | REQUIRED PER FLORIDA STATUTES 471.025 AND FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002. |
| | THIS OFFICE HAS MADE THIS SAME COMMENT TO THIS DESIGNER |
| | OF RECORD ON SEVERAL OTHER REVIEWS ON OTHER PROJECTS |
| | YET PLANS ARE STILL BEING SUBMITTED WITH THE SAME |
| | *RUBBER-STAMP*. |
| | THIS OFFICE IS LEFT WITH NO CHOICE BUT TO FORWARD ALL |
| | PLANS AND DOCUMENTS TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS FOR REVIEW OF SAID STATUTORY |
| | VIOLATIONS. |
| | THESE WILL BE SENT WITH PLANS FROM OTHER PROJECT |
| | PREVIOUSLY RETAINED FOR THE SAME COMMENT. |
| | PLEASE KNOW WHEN SIGNING, DATING AND SEALING PLANS: ALL |
| | MUST BE ORIGINAL SIGNATURE. A *RUBBER-STAMP* SHALL NOT |
| | BE USED. THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD |
| | OF ENGINEERS AND LEGAL COUNSEL TO THE BOARD ON MANY |
| | OCCASIONS. |
| | |
| | 2) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF |
| | ALL DOCUMENTS INCLUDING ENERGY CALCULATIONS. ONLY ONE |
| | SET OF CALCULATIONS WERE SUBMITTED. |
| | FBC 106.1, 106.1.3, 106.5. |
| | |
| | 3) NOTE: PLEASE SEE COMPLIANCE WITH FLORIDA BUILDING |
| | CODE AND CHAPTER 13 FOR CODE REQUIRED LIGHTING CONTROLS |
| | HAS NOT BEEN MET. THIS WAS A COMMENT ON THE PREVIOUS |
| | REVIEW AS NO LIGHTING CONTROL SYSTEM WAS DESIGNED INTO |
| | THE PROJECT ON ORIGINAL PLANS SUBMITTED. RESPONSE |
| | MENTIONS TO SEE REVISED PLANS HOWEVER COMPLIANCE WITH |
| | CHAPTER 13 HAS STILL NOT BEEN MET. |
| | PLEASE SEE NOTE # 7 ON SHEET E-2: THIS NOTE SATES |
| | *LIGHTING CONTROLS SHALL BE PROVIDED TO MEET PARAGRAPH |
| | 13-415.1.ABC.1.1 OF THE FLORIDA BUILDING CODE*. THE |
| | CODE SHALL NOT BE QUOTED IN LIEU OF REQUIRED DESIGN. |
| | PLEASE SEE OTHER SECTIONS OF CHAPTER 13 FOR LIGHTING |
| | CONTROLS IS ALSO REQUIRED SUCH AS 13-415.1.ABC.1.2, |
| | 13-415.1.ABC.1.3 AND 13-415.1.ABC.1.4. |
| | PLEASE TAKE A LOOK AT SECTION 13-415.1.ABC.1.1 AND |
| | .1.2. THE LIGHTING CONTACTORS AS SHOWN DO NOT PROVIDE |
| | CODE COMPLIANCE. IN FACT ALL DEVICES IN ALL *SEPARATE |
| | SPACES* ARE STILL BEING SHOWN AS STANDARD SWITCHING |
| | DEVICES. PLEASE SEE THIS IS CLEAR ON THE SYMBOL LEGEND |
| | ON E-7 AS WELL AS NOTE #5 ON E-2. IT IS NOT POSSIBLE TO |
| | USE *STANDARD SWITCHES* WHEN MOST LIGHTING CIRCUITS ARE |
| | ALL GOING THROUGH LIGHTING CONTACTORS. |
| | PLEASE SEE THESE SAME SECTIONS OF CODES AS *ALL |
| | SEPARATE SPACES* ARE REQUIRED TO CONTAIN CONTROLS TO |
| | OVER RIDE ANY TIME OF DAY SCHEDULING. |
| | PLEASE SEE LIGHTING CONTROLS ARE REQUIRED TO BE LOCATED |
| | SO THE OCCUPANT CAN SEE THE LIGHTING IN WHICH IS BEING |
| | CONTROLLED OR MEETING THE EXCEPTIONS FOR *PILOT LIGHTS* |
| | ETC. |
| | PLEASE ALSO SEE 13-415.1.ABC.1.2 FOR OTHER TYPES OF |
| | ROOMS WHICH REQUIRE OCCUPANCY SENSOR DEVICES. THIS IS |
| | ABOVE ANY TIME OF DAY LIGHTING CONTROLS. |
| | EXAMPLES: AS LISTED IN THE CODE, CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, LUNCH, BREAK ROOMS. |
| | PLEASE THE LIGHTING CONTACTOR AND PLANS AS SHOWN DOES |
| | NOT SHOW ANY OVER RIDES, DOES NOT SHOW ANY SPACE |
| | CONTROLS ETC. |
| | PLEASE SEE 13-415.1.ABC.1.3 FOR *ADDITIONAL CONTROLS* |
| | REQUIRED. |
| | PLEASE SEE 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING |
| | CONTROLS. PLANS INDICATE LIGHTING TO BE THROUGH A TIME |
| | CLOCK HOWEVER THIS SECTION OF THE CODE REQUIRES ONE OF |
| | TWO METHODS OF CONTROL. PLEASE KNOW IF USING A TIME |
| | CLOCK THIS SHALL BE AN ASTRONOMICAL TIME CLOCK NOT A |
| | STANDARD TIME CLOCK. THIS TC MUST ALSO CONTAIN A |
| | MINIMUM BATTERY BACK UP FOR PROGRAMMING WHICH CONTAINS |
| | A MINIMUM 10 HOURS OF BACK UP. |
| | |
| | ** IT IS IMPORTANT TO KNOW AS SEVERAL DEVICES ON PLANS |
| | WILL BE REQUIRED TO BE REVISED TO MEET MINIMUM CODE |
| | COMPLIANCE THERE MAY CERTAINLY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS |
| | TIME. |
| | |
| | *** PLEASE SEE COMMENT BELOW WITH RESPECT TO HAND-WOUND |
| | TIMERS SHOWN ON SYMBOL LEGEND. |
| | |
| | 4) NOTE: PLEASE SEE FLORIDA BUILDING CODE CHAPTER 13 |
| | FOR LIGHTING PERFORMANCE AND CODE COMPLIANT ENERGY |
| | CALCULATIONS TO BE SUBMITTED. |
| | PLEASE SEE 13-400.0.A, 13-400.3.A, 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THE METHOD OF CALCULATION SUBMITTED FOR THE |
| | NEW BUILDING IS METHOD *A* HOWEVER NO CALCULATIONS WERE |
| | SUBMITTED FOR THE EXISTING SEPARATE BUILDING WHICH IS |
| | BEING RENOVATED. |
| | PLEASE SEE THE VERSION SUBMITTED IS NOT UNDER THE |
| | ADOPTION OF THE FBC 13-400.3.A. PLEASE SEE THE CODE |
| | SPECIFICALLY ADOPTS VERSION 2.5 AND THE VERSION |
| | SUBMITTED WAS 3.0. THIS HAS BEEN CONFIRMED WITH THE |
| | DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING |
| | COMMISSION ON MORE THAN ONE OCCASION. |
| | PLEASE ALSO SEE THE CERTIFICATION SHEETS LIST |
| | MECHANICAL AND ELECTRICAL DESIGNERS WHICH ARE NOT |
| | LISTED AS ENGINEERS. IN FACT THE DESIGNER WHICH IS |
| | SIGNED, DATED AND SEALED ON THE CERTIFICATIONS IS NOT |
| | EVEN LISTED WITH NAME OR LICENSE NUMBER YET THIS |
| | DESIGNER IS LISTED ON PLANS AS THE MECHANICAL DESIGNER |
| | OF RECORD. |
| | PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| | MEET THE MINIMUM FOR CODE COMPLIANCE. IN FACT THERE ANY |
| | SEVERAL ITEMS ON PLANS THAT DO NOT COORDINATE WITH THE |
| | INPUT DATA REPORT. SOME EXAMPLES WILL BE GIVEN BELOW |
| | HOW THESE ARE NOT AN EXHAUSTIVE LIST OF ALL ITEMS: THE |
| | INPUT DATA REPORT WILL BE NOTED AS IDR. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR FOR EXTERIOR LIGHTING SHOWS NO |
| | LIGHTING AND IS COMPLETELY *BLANK*. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS CLEARLY INDICATE AND SHOW |
| | DOZENS OF EXTERIOR LIGHTS? |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR FOR INTERIOR LIGHTING WHICH |
| | INDICATES *MANUAL ON/OFF* CONTROLS FOR ALL INTERIOR |
| | LIGHTING. HOW IS THIS POSSIBLE WHEN ALL INTERIOR |
| | LIGHTING IS REQUIRED TO BE UNDER SOME SORT OF AUTOMATED |
| | CONTROL? |
| | FOR EXAMPLE: |
| | PLEASE SEE THE WATER HEATER KW RATINGS SHOWN ON THE IDR |
| | DO NOT COORDINATE WITH PLANS AS THE PLANS INDICATE A |
| | HIGHER KW RATING. |
| | ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE BE |
| | SURE TO GO THROUGH ALL LIGHTING ON PLANS, METHOD OF |
| | CONTROLS, TYPES OF FIXTURES, WATTAGE OF FIXTURES AND |
| | NUMBERS OF FIXTURES. THESE WERE A FEW EXAMPLES ONLY. |
| | |
| | 5) NOTE: PLEASE SEE THE CONDUIT SIZES AS LISTED ON E-4 |
| | ON CONDUIT/WIRE NOTES. PLEASE SEE NOTES #1, 2 AND 3 |
| | WHICH INDICATE AS MANY AS 4-500MCM AND EQUIPMENT |
| | GROUNDING CONDUCTOR?S 1/0 AND 2/0 IN TWO-INCH CONDUITS. |
| | THIS IS NOT POSSIBLE AS WELL AS NOT MEETING CODE FOR |
| | DE-RATING AND MINIMUM CONDUIT SIZING. PLEASE SEE |
| | CONDUIT FILL TABLES IN CHAPTER 9 OF THE NEC AND |
| | 300.17. |
| | |
| | 6) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE STILL |
| | SHOWING THE INSTALLATION OF A NATURAL GAS GENERATOR. |
| | THIS UNIT NEEDS TO BE CLASSIFIED AS *OPTIONAL STAND-BY* |
| | ONLY AS THIS IS NOT FOR AN EMERGENCY/LIFE SAFETY OR |
| | LEGALLY REQUIRED SYSTEMS.700,701,702. |
| | PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | PROPOSED GENERATOR AND ATS AS REQUESTED ON THE PREVIOUS |
| | REVIEW. RESPONSE MENTIONS THIS WILL BE DONE UNDER SHOP |
| | DRAWING SUBMITTALS HOWEVER IF THIS SCOPE IS INCLUDED IN |
| | THIS BASE BUILDING OR AS SHOWN ANY WORK WILL BE DONE |
| | UNDER BASE BUILDING THESE SHALL BE SUBMITTED AT THIS |
| | TIME. |
| | 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | ** IT IS IMPORTANT TO KNOW IF THE GENERATOR UNIT FEEDS |
| | ANY LIFE SAFETY OR LEGALLY REQUIRED LOADS THERE MAY |
| | ALSO BE OTHER REQUIREMENT SIN NFPA-110 WHICH ARE |
| | REQUIRED TO BE MET. |
| | PLEASE SEE FBC CHAPTER 27 WHICH REFERENCES ALL BACK UP |
| | POWER SYSTEMS SHALL BE INSTALLED PER NFPA-110. AS THERE |
| | IS INFORMATION NOT YET SUBMITTED SOME COMMENTS CAN NOT |
| | BE MADE. |
| | PLEASE SEE LOCATION SHALL MEET CHAPTER 7 FOR ROOM |
| | CONSTRUCTION, VENTILATION, ELECTRICAL EQUIPMENT |
| | INSTALLATION ETC. |
| | |
| | 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE |
| | PLACE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE MAIN BREAKER DISCONNECT |
| | BEING SHOWN. THE PLANS CALL FOR A *SHUNT-TRIP* WHICH |
| | MAY NOT BE USED IN LIEU OF THE REQUIRED MANUAL MEANS OF |
| | DISCONNECT RATED FOR THE LOAD SERVED PER 230.76, |
| | 230.79. |
| | THE NOTE #14 ON PLANS ON SHEET E-4 GIVES ANY PERSON |
| | FALSE SENSE THAT THE MAIN WILL BE TURNED OFF BY USE OF |
| | SHUNT TRIP. |
| | THE MEANS OF DISCONNECTS FOR MAIN WILL BE LABELED FOR |
| | NORMAL AND EMERGENCY, NOT THE SHUNT TRIP. |
| | PLEASE SEE 230.2E, 702.8. |
| | PLEASE ALSO PLACE NOTES ON PLANS THAT OTHER BUILDINGS |
| | WHICH WILL NOW BED FED FROM TWO SOURCES OF POWER SHALL |
| | CONTAIN NOTES FOR SIGNS AT EACH OF THESE EXISTING |
| | LOCATIONS. |
| | |
| | 9) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE SYSTEMS AT |
| | EACH STRUCTURE AND SERVICE PER 250.50. THE PLANS SHALL |
| | SHOW MINIMUM REQUIRED ATTACHMENTS. QUOTING THE CODE IN |
| | LIEU OF MINIMUM REQUIRED BY CODE IS NOT ACCEPTABLE. |
| | PLEASE BE SURE TO SEE 250.32, 250.50 AT ANY DETACHED |
| | BUILDINGS. |
| | |
| | 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN ON THE LINE SIDE OF PANEL MDP TO |
| | THE THIS MDP.250.50, 250.110, 250.122, 250.32 ETC |
| | THE EQUIPMENT GROUND IS BROUGHT TO THE MAIN BUT NOT |
| | FROM MAIN TO MDP. |
| | |
| | 11) NOTE: PLEASE SEE THE CODE SECTIONS GIVEN ON THE |
| | LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70 |
| | (NEC) ADOPTED BY THE STATE OF FLORIDA. |
| | PLANS SHOW 220.35 |
| | PLEASE SUBMIT THE FPL DOCUMENTS SUPPORTING THE |
| | DE-RATING OF SOME SERVICE EQUIPMENT AS MUCH AS 600AMPS. |
| | 220.87 |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED ARC |
| | FLASH PROTECTION PER 110.16 |
| | |
| | 13) NOTE: PLEASE KNOW AT THIS POINT IN TIME THE |
| | APPLICATION CODE IS THE 2004 FBC WITH THE 2007 |
| | REVISIONS. |
| | THE STATE OF FLORIDA IS SCHEDULED TO ADOPT NEW CODE |
| | STANDARDS ON OCT 1ST, 2008. |
| | |
| | 14) NOTE: PLEASE SEE THAT ALL INFORMATION ON TITLE |
| | BLOCKS IS REQUIRED TO BE COMPLETE AND ACCURATE. PLEASE |
| | SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND |
| | 61G1-16.004, FLORIDA STATUTES 471.023 AND 481.219 FOR |
| | REQUIRED INFORMATION AND LICENSING INFORMATION TO BE ON |
| | TITLE BLOCKS. |
| | THIS COMMENT IS MADE UNDER ELECTRICAL REVIEW BASED ON |
| | THE FACT THE TITLE BLOCKS FOR ALL FIRMS ARE LISTED ON |
| | ALL SHEETS AND LICENSE INFORMATION ON AT LEAST ONE FIRM |
| | IS NOT LISTED AND CURRENT WITH THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. |
| | ** LANDSCAPE ENGINEER**. |
| | PLEASE SEE LANDSCAPE PLANS INDICATE A *LANDSCAPE |
| | ARCHITECTURAL FIRM* NOT A LANDSCAPE ENGINEERING FIRM. |
| | PLEASE SEE THE TITLE BLOCKS ON OTHER SHEETS SUCH AS |
| | LANDSCAPE SHEETS; CIVIL SHEETS ETC DO NOT CONTAIN |
| | LICENSING INFORMATION AS REQUIRED UNDER ADMINISTRATIVE |
| | CODES OR STATUTES. THIS INFORMATION MAY OR MAY NOT BE |
| | MADE UNDER OTHER TRADE REVIEWS. IN ANY CASE THESE ARE |
| | IN VIOLATION OF SECTIONS GIVEN AND SHALL BE MET WHETHER |
| | OR NOT COMMENT IS MADE BY ANY OTHER TRADE REVIEWER(S). |
| | THIS COMMENT DOES APPLY TO SMITH ENGINEERING AS THEIR |
| | INFORMATION LISTED IS CORRECT INFORMATION ON THEIR |
| | TITLE BLOCKS. |
| | THIS COMMENT DOES APPLY TO ALL MEP PLANS AS THESE OTHER |
| | FIRMS ARE LISTED ON THE MEP SHEETS. |
| | |
| | 15) NOTE: PLEASE COORDINATE ALL PLANS FOR BOTH |
| | BUILDINGS FOR SERVICE EQUIPMENT ETC. |
| | PLEASE SEE ONE EXAMPLE OF THIS IS THE RISER ON THE |
| | RENOVATED GYM BUILDING INDICATES CLEARLY THE EXISTING |
| | CT CAN IS TO REMAIN AND DOES NOT SHOWN ANY NEW MAIN |
| | DISCONNECT BEING FED FROM THE NEW DP PANEL AT THE NEW |
| | BUILDING. THE RISER ON SHEET E-4 ON THE NEW BUILDING |
| | SHOWS AND NOTES A NEW 600AMP MAIN HOWEVER THE RISER ON |
| | SHEET E-3 FOR THE RENOVATED GYM DOES NOT SHOW ANY NEW |
| | MAIN. |
| | PLEASE SEE THE EXISTING GYM BUILDING RISER ON SHEET E-3 |
| | CLEARLY INDICATES A NEW 600AMP MDP YET THE RISER ON |
| | SHEET E-4 OF NEW BUILDING SHOWS *EXISTING* 600AMP MDP. |
| | 240.4, 310.16, 225.31-225.39, 250.32 ETC. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION |
| | AND COORDINATION. |
| | |
| | |
| | 16) NOTE: PLEASE SEE AS NOTED ABOVE THIS SUPPOSED NEW |
| | 600AMP MDP AS SHOWN ON THE RENOVATED PLANS ON SHEET E-3 |
| | SHOWS EACH BREAKER AS MAIN 1 OF 4, 2 OF 4, 3 OF 4, 4 OF |
| | 4 AND THEN A 5 OF 4. HOW CAN THIS BE 5 OF 4? EACH OF |
| | THESE WOULD BE 1 OF 5 ETC. |
| | PLEASE KNOW IN ANY CASE IF THIS PANEL BOARD WILL BE A |
| | NEW MDP, THERE MAY NOT BE SPACE FOR MORE THAN 6 MAINS. |
| | THIS EQUIPMENT IS SHOWN WITH 30 SPACES AND THIS |
| | EQUIPMENT IS SHOWN AS A MLO (MAIL LUG ONLY) BOARD. |
| | THIS IS NOT PERMITTED. 225.33A |
| | PLEASE COORDINATE WITH RISER ON SHEET E-4 OF NEW |
| | BUILDING PLANS AS A MAIN IS SHOWN IN FRONT OF THIS |
| | EQUIPMENT. IF THIS IS THE CASE EACH BRANCH BREAKER |
| | WOULD NOT BE LABEL *MAINS 1 OF 4/5*. |
| | THESE WOULD NO LONGER BE MAINS. |
| | |
| | 17) NOTE: PLEASE SEE NOTES ABOVE FOR NEW BUILDING WITH |
| | RESPECT TO REQUIRED LIGHTING CONTROLS, DEVICES, OVER |
| | RIDES, SEPARATE SPACES ETC ALSO APPLIED TO THE |
| | RENOVATED BUILDING. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. |
| | |
| | 18) NOTE: PLEASE KNOW ENERGY CALCULATIONS PER |
| | 13-101.1.3, 13-400.3.B, 13-400.3.C MAY BE REQUIRED |
| | BASED ON RENOVATION VALUE. AT THIS TIME THIS CAN NOT BE |
| | CONFIRMED AS THE APPLIED VALUE HAS NOT BEEN |
| | DETERMINED. |
| | |
| | 19) NOTE: PLEASE SEE FBC CHAPTER 11, AS SPRING WOUND |
| | TIMERS IN ACCESSIBLE AREAS ARE NOT PERMITTED. THESE DO |
| | NOT MEET THE FOLLOWING SECTION. |
| | 11-4.27.4 CONTROLS AND OPERATING MECHANISMS SHALL BE |
| | OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN |
| | 5 LBF (22.2 N). |
| | |
| | 20) NOTE: PLEASE SEE THE POWER PLANS AND PLANS IN |
| | GENERAL NEED TO SHOW THE LOCATION OF ALL PANELS AND |
| | SERVICE EQUIPMENT. |
| | PLEASE SEE RISER WHICH INDICATES A NEW BACK FEED FROM |
| | NEW *DP* TO EXISTING *SW* HOWEVER COULD NOT LOCATE THE |
| | LOCATION OF THIS EXISTING *SW*. |
| | NOTE ON RISER MENTIONS TO GROUND PER 250 OF THE NEC |
| | HOWEVER AS NOTED ABOVE, MAY NOT QUOTE CODE IN LIEU OF |
| | REQUIRED DETAIL. |
| | PLEASE SHOW LOCATION OF *SW*, COULD NOT LOCATE THIS ON |
| | THE GYM BUILDING PLANS AS SHEET E-4 ON NEW BUILDING DP |
| | NOTES THIS IS THE LOCATION. HOWEVER THIS CAN NOT BE |
| | CONFIRMED. |
| | 110.26, 240.24 ETC |
| | |
| | 21) NOTE: PLEASE KNOW PLANS ARE BEING RETAINED AT THIS |
| | TIME. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |