Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop B
Sequence Number 2
Notes
Date Text
2008-05-30 13:39:15BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MAY 30,2008
 2NDREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL,WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.7*.
  
 1C)COMPLIED.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS. NOTE IF THE PLANS
 SUBMITTED AS A MAJOR WORKING DRAWING HAVE NOT BEEN
 CONVERTED INTO A PERMIT APPLICATION BEFORE OCT. 1,2008
 THE PLANS WILL NEED TO BE REDESIGNED TO THE 2007
 FLORIDA BUILDING CODE.
  
 1E) 2ND REQUEST,THE MAJOR WORKING DRAWING REVIEW
 UNDER SCOPE OF PROJECT INDICATES A 10,000 SQ FT
 MULTIPURPOSE BUILDING, PLEASE ADD THE RENOVATION TO THE
 EXISTING BUILDING TO THE APPLICATION.
  
 2) DESIGN PROFESSIONAL REQUIREMENTS:
  
 2A)PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 IN BOTH SETS OF PLANS FOR THE NEW GAINES PARK COMMUNITY
 CENTER AND THE NORTHWEST WING RENOVATIONS THE
 COVERSHEETS ARE NOTSIGNED, SEALED OR DATED.
  
  
 2B) 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 LANDSCAPE ARCHITECT
 BA ARCHITECTURAL
 PLEASE PROVIDE DOCUMENTATION FROM THE DEPARTMENT OF
 BUSSINESS AND PROFESSIONAL REGULATION OF YOUR
 CERTIFICATE OF AUTHORIZATION, I CAN NOT FIND IT ON THE
 WEBSITE.
  
 2C)COMPLIED.
  
 3) 2ND REQUEST, NEW BUILDING CONSTRUCTION. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.A THOROUGH REVIEW CAN
 NOT BE MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 3A) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 PLEASE SEE SHEET A-100 PROJECT CRITERIA DOES NOT
 INDICATE TO WHAT CODE THIS BUILDING IS DESIGNED TOO.
 PLEASE SEE STRUCTURAL SHEET S-3.1 STILL INDICATES THE
 2004 FBC WITH 2006 AMENDMENTS. THE 2007 AMENDMENTS
 CLEARLY ARE AFFECTED BY WIND.
  
 B) COMPLIED.
 C) 2ND REQUEST,THE TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 5 & 6, TABLE 503 & 601. 106.3.5(3) MINIMUM TYPE
 OF CONSTRUCTION SEE TABLE 503 PLANS INDICATE TYPE I
 CONSTRUCTIONTHERE IS NO CONFIRMATION AS TO TYPE 1A 3HR
 FIRE RATINGS OR TYPE 1B 2HR FIRE RATINGS,NOTE SEE
 TABLE 601 FOR FIRE RATINGS.
  
 D) COMPLIED.
  
 E)2ND REQUEST, IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED NEITHER SHEET G-100 THE INDEX OF DRAWINGS,
 LS-1.0 NOR A-100 PROJECT CRITERIA LIST THE REQUIRED
 FIRE SPRINKLER PLANS NOR THE INSTALATION OF A NFPA 13
 SYSTEM. SECTION 903.2.1.3 (2) REQUIRES A SPRINKLER
 SYSTEM WHEN IN A A-3 OCCUPANCYWHEN THERE IS A
 OCCUPANCY EQUAL TO OR GREATER THAN 300. THIS IS A
 REQUIRED SYSTEM.
 F)2ND REQUESTWHETHER THE SPRINKLER SYSTEM IS
 REQUIRED. SEE SECTION 903.2.1.3(2).
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) COMPLIED.
  
 3B) 2ND REQUEST, THE S-3.1 INDICATES THE WIND DESIGN
 FROM ASCE 7-02FOR THE BUILDING, PLEASE REVIEW THE
 BUILDINGS CATEGORY AND IMPORTANCE FACTOR. PLEASE REVIEW
 SHEET A-101 & A-102 FOR OCCUPANCY. AS INDICATED THESE
 SHEETS INDICATE THE CAPABILITY OF 300 PEOPLE WITH THE
 ACTUAL OCCUPANT LOAD BEING QUIET HIGHER. PLEASE SEE
 ASCE 7-02 TABLE 1-1 BUILDING CATEGORY III,WITH A
 IMPORTANCE FACOR OF 1.15 BUILDINGS AND OTHER STRUCTURES
 WHERE MORE THAN 300 PEOPLE CONGREGATE IN ONE AREA.
 PLEASE REVISE THE BUILDING CATEGORY AND IMPORTANCE
 FACTOR. SEE UPPER LEFT HAND PORTION OF THE SHEET STILL
 INDICATES 1.0 IMPORTANCE FACTOR.
  
 3C) COMPLIED.
  
 4) 2ND REQUEST, THE LIFE SAFETY SHEET LS-100 INDICATES
 FOR THE MULTI-PURPOSE ROOM THE USE OF 15 NET. TABLE
 1004.1.2 ESTABLISHES THE MINIMUM OCCUPANT LOAD FOR
 WHICH THE EGRESS FACILITIES MUST BE DESIGNED. THE
 FACTORS ARE NOT BASED ON THE NORMAL OCCUPANCY, BUT , ON
 THE MAXIMUM OCCUPANT LOAD SCENARIO, A WORST CASE
 PROBABILITY. IT SHOULD ALSO BE NOTED THE FACTORS ARE
 NOT BASED ON THE OCCUPANCY CLASS OF THE BUILDING, BUT ,
 ON THE USE OF THE AREA OR SPACE. PLEASE RECALCULATE THE
 EGRESS CAPACITIES FOR THE MULTI-PURPOSE ROOM AT THE
 WORST CASE SCENARIO @ 5 AND ASSOCIATED EXITS.
  
 5A) COMPLIED.
  
 5B)2ND REQUEST, AT THIS TIME BECAUSE OF THE UNKNOWN
 BUILDING FACTORS THIS COMMENT MAY OR MAY NOT APPLY IN
 FUTURE REVIEWS:FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO
 HAROLD PISKURA, DIRECTOR OF THE RESIDENT INSPECTOR
 PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 XXX - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS XXX - STRUCTURES IN
 WHICH THE CONCRETEDESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI - PILE DRIVING
 COLUMNS, WALLS, BEAMS 4,000 PSI S-3.1.
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 FORMS FOR THE RESIDENT INSPECTOR WILL BE ATTACHED AND
 WILL NEED TO BE FILED OUT AND RETURNED TO HAROLD
 PISKURA DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.
  
 6)2ND REQUEST,L-3.0 LANDSCAPE PAVING PLAN PLEASE
 PROVIDE AN ACCESSIBLE ROUTE WITHIN THEBOUNDARY OF THE
 SITE TO PUBLIC TRANSPORTATION, ACCESSIBLE PARKING,
 PASSENGER LOADING ZONES SIDEWALKS TO AN ACCESSIBLE
 ENTRANCE. 11-4.1.2(1)-(5). SHEET A-100 & L-3.0 DO NOT
 REFLECT THE SAME ROUTE FROM THE ACCESSIBLE PARKING TO
 THE NEW BUILDING. A-100 INDICATES A SIDEWALK THAT
 ALLOWS WHEELCHAIRS TO TRAVEL INFRON T OF THE PARKED
 VEHICLES WHILE L-3.0 STILL FORCES THE WHEELCHAIR USER
 TO TRAVEL BEHIND THE PARKED VEHICLE, PLEASE COORDINATE
 PLANS.11-4.6.2.
  
 7) 2ND REQUEST, THE RESPONCE SHEET INDICATED TO REFER
 TO CIVIL AND LANDSCAPE NOTES, WHERE. SHET L-3.0 PAVING
 MATERIALSSCHEDULE DOES NOT INDICATE THE USE OF
 DETECTABLE WARNING TEXTURES11-4.29.2. INDICATE
 COMPLIANCE WITH: 11-4.29.5 DETECTABLE WARNINGS AT
 HAZARDOUS VEHICULAR AREAS.
  
 8)COMPLIED.
  
 9) 2ND REQUEST, RESPONCE SHEET REFERS TO CIVIL SHEET
 C-4 , PLEASE INDICATE COMPLIANCE WITH : PASSENGER
 LOADING ZONES PLEASE PROVIDE ACCESS AISLE FOR PASSENGER
 LOADING ZONE SEE FIGURE 10, AND COMPLIANCE WITH
 11-4.29.5/ 11-4.6.6.
  
 10) SEMI-COMPLIED. SHEET A-1.00 INDICATES A CUT SECTION
 THROUGH THE DISABLED PARKING SPOTS DETAIL# 1 SHEET
 A-603, SHEET IS MISSING. THE RESPONCE SHEET INDICATES
 TO SEE A-605 DETAIL# 1. THE HANDICAPPED SIGNAGE
 INDICATES 2 AREAS TO LOCATE THIS SECTION :
 10A) DETAIL 16 A-603
 10B) DETAIL 5 A-604
 NEITHER OF THESE SECTION PORVIDE THE HANDICAPPED SIGN
 HEIGHTS.
  
 11-12) COMPLIED.
  
 13)2ND REQUEST, SHEET A-1 DOES INDICATE WALL TAGS
 INDICATING WALLS BUT THE PLANS DO NOT PROVIDE A DETAIL
 SHEET IDENTIFYING WALL TYPES, THE INDEX LIST A-600 FOR
 WALL DETAILS , THERE ARE NO WALL DETAILS PROVIDING WALL
 TYPES AND FIRE RATING, PLEASE SEE TABLE 1016.1. FOR
 ASSEMBLY OCCUPANCY AND FIRE RATING OF CORRIDOR.
 ENTRANCE HALLWAY 152 IS THE EXIT ACCESS CORRIDOR FOR
 THE MULTI-PURPOSE ASSEMBLY ROOM 146 , SEE TABLE 1016.1
 REQUIRES A 1 HR RATED CORRIDOR FOR EITHER
 NON-SPRINKLERED OR SPRINKLERED BUILDINGS.
  
 14) SEMI-COMPLIED, PLANS ARE INCOMPLETE AND A THROUGH
 REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS
 REQUIRED FOR REVIEW.
  
 15) SEMI-COMPLIED.
  
 16-17) COMPLIED.
  
 18)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3COPIES OF ALL REPORTSFORTHRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL
 B) WINDOWSOPERABLE WINDOWS: SINGLE HUNG, CASEMENT
 C) MULLIONS
 D) GLASS BLOCK
 E) GLAZED SWING DOORS
 F) AUTOMATIC SLIDING DOORS
 G) HOLLOW METAL DOORS EXTERIOR
 H) OVERHEAD DOORS
 I) TRUSS ANCHORS
 J) ROOF HATCHES
 K) ROOF ASSEMBLIES
 L) PRE-ENGINEERED A/C STANDS
  
 19)2ND REQUEST,106.3PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 20) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATEDBY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) 2ND REQUEST,THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCEDFASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) 2ND REQUEST,A-104 ROOF PLAN FAILS TO IDENTIFY
 ROOF DRAINAGE SYSTEM AND OR DETAILS, THE ROOF DRAIN
 SIZE IS NOT PROVIDED, WHAT TYPE OF SECONDARY DRAINAGE
 AND VERTICAL CONTRIBUTING AREAS, THIS INFORMATION IS
 ALSO MISSING FROM THE PLUMBING PLAN. 106.3.5.1.1(8).
 OVERFLOWS ARE NOT SIZED, FBC BUILDING 1503.4.3 OVERFLOW
 SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH THE FBC
 PLUMBING CODE.
  
 24) 2ND REQUEST,ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 25) COMPLIED.E
  
  
 RENOVATION OF EXISTING NORTH WING :
  
  
 26A)SEMI-COMPLIED,SHEET A-100 PROJECT CRITERIA
 INDICATES THIS BUILDING IS TO BE CLASSIFIED AS A TYPE I
 BUILDING, IS THIS A TYPE IA BUILDING WITH 3HR FIRE
 PROTECTION OR TYPE IB WITH A 2 HR FIRE PROTECTION OF
 STRUCTURAL ELEMENTS, IN EITHERCASE THERE WOULD BE NO
 WOOD TRUSSES AND OR ROOF SHEATHING. PLEASE INDICATE
 MINIMUMBUILDING TYPE.
  
 THE OTHER ISSUE IS THIS BUILDING BE FIRE SPRINKLERED ?
 IS THE FIRE SPRINKLER REQUIRED?
 THESE QUESTIONS NEED TO BE ANSWERED TO KNOW IF THE
 CORRIDORS WILL REQUIRE RATED CORRIDORS,SEE TABLE 1016.1
 FOR DAY CARE OCCUPANCIES.
 THE PLANS INDICATE SOME OF THE DOORS BEING RATED BUT
 THERE ARE MANY NEW DOORS AND EXISTING DOOR FRAMES AND
 THE NEW DOORS ARE NOT RATED. WE STILL CAN NOT DO A
 COMPLETE REVIEW WITHOUT THE
 ABOVE INFORMATION PROVIDED.
  
 26B) SEMI- COMPLIED. SEE THE ABOVE STATEMENTS.
  
 26C) 2ND REQUEST, PLEASE ALSO INDICATE TO WHAT LEVEL
 ALTERATION WORK WILL ACCOMPLISHED UNDER THIS PERMIT.
 PLEASE SEE 2004 FBC EXISTING BUILDING CODE 301.1.THE
 WORK PREFORMED ON AN EXISTING BUILDING SHALL BE
 CLASSIFIED IN ACCORDANCE WITH THIS CHAPTER.RESPONCE
 INDICATES NOTES ON G-100 & A-101.PLANS DO NOT INDICATE
 LEVEL OF ALTERATION IN EITHER THE APPLICABLE CODE OR
 PROJECT CRITERIA.
  
 27) SEMI-COMPLIED THE DOOR SCHEDULE DOES NOW INDICATES
 ALOT OF NEW DOORS WITH EXISTING DOOR FRAMES BUT NO FIRE
 RATING, WITH NOT HAVING INFORMATION IF THERE IS FIRE
 SPRINKLERS OR IF THERE WILL BE FIRE SPRINKLERS ADDED,
 WE NEED TO KNOW THIS INFORMATION TO DETERMINE THROUGH
 TABLE 1016.1 FIRE RATINGS FOR CORRIDORS.
  
 28) COMPLIED- NO ROOF WORK UNDER THIS PERMIT FOR THIS
 BUILDING.
  
 29) NEW COMMENT DOOR # 5 IS A NEW OPENING, WILL NEED TO
 COMPLY WITH 11-4.13.6 MANEUVERING CLEARENCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL. REQUIRES 18" ON THE
 LATCH SIDE.
  
 BUILDING PLAN REVIEW
 JIM WITMER CBO
 PLAN REVIEW II
 TEL:(561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]