Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop M
Sequence Number 12
Notes
Date Text
2009-12-01 16:46:11REVIEW #: REVISION
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS WITH SPACE-BY-SPACE
 REQUIREMENTS FOR OCCUPANCY CLASSIFICATION, OCCUPANT
 LOAD AND VENTILATION RATES TO BE PROVIDED IN ACCORDANCE
 WITH FBC-M SECTION 403.
  
 2. PLANS AND NOTE #5 ON PAGE M-1 INDICATE NEW AHUS TO
 BE INSTALLED AND CONNECTED TO EXISTING CONDENSING
 UNITS. PROVIDE SUPPORTING DOCUMENTATION SHOWING THESE
 TO BE MATCHED SYSTEMS IN ACCORDANCE WITH FBC-B
 13-101.6.
  
 3. PROVIDE ATTACHMENT DETAIL ALONG WITH MANUFACTURER'S
 DATA FOR WIND RESISTANT INSTALLATION OF OUTDOOR
 CONDENSING UNITS IN ACCORDANCE WITH FBC-M 301.13.
  
 4. SYSTEM SIZING SUMMARIES WERE SUBMITTED FOR NEW
 SYSTEMS IN LIEU OF FULL COOLING LOAD CLACULATIONS.
 SYSTEM SIZING SUMMARIES SHALL BE SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH FBC-B
 13-407.AB.1.
  
 5. AHU 4 SHALL BE PROVIDED WITH DUCT SMOKE DETECTOR IN
 ACCORDANCE WITH FBC-M 606.2.1.
  
 6. THE SCOPE OF WORK RELATED TO THIS REVISION
 REPRESENTS A SIGNIFICANT EXPANSION FROM THE SCOPE
 COVERED BY THE PERMIT AT TIME OF ISSUANCE. THE
 VALUATION OF WORK SHALL BE ADJUSTED TO REFLECT AND
 INCLUDE THE VALUE OF THE EXPANDED SCOPE.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATION SHALL BE
 SUBMITTED FOR KITCHEN EXHAUST AND VENTILATION SYSTEM.
 THE KITCHEN EXHAUST/VENTILATION SYSTEMS ARE NOT PART OF
 THIS REVIEW AND HAVE NOT BEEN EVALUATED FOR CODE
 COMPLIANCE.
  