2009-11-24 10:12:43** SEPARATE NOTE FROM PROVISO**
  
 1) NOTE: SCOPE OF WORK HAS INCREASED. APPLIED VALUE FOR
 SCOPE OF WORK NEEDS TO BE INCREASED FOR ADDITIONAL
 SCOPE OF WORK NOT PART OF ORIGINAL PLANS.
 FBC 108.3
2009-11-24 10:04:41** PROVISO **
  
  
 1) NOTE: PLEASE UPDATE PANEL SCHEDULES FOR ALL
 CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS WHICH THEY
 FEED. FOR EXAMPLE.
  
 S-7, RECEPTACLES ROOM 101, ETC.
 MAY BE ALPHA OR NUMERIC.
  
 408.4
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  