Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-27 14:04:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. ALL SHEETS. PLANS SHALL BE SIGNED, SEALED, & DATED
 AS REQUIRED BY SECTION 106.1, FAC 61G1-16.003, FAC
 61G1-16.004(5), FAC 61G15-23.002(1)(2) & FS 471.025, FS
 481.2055.
  
 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT,
 ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL
 CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA
 STATUTES.
  
 3. SHT G-100 GENERAL NOTES 32 INDICATES THE BUILDING
 WAS DESIGNED UNDER THE 2001 CODE. ALSO APPLICABLE CODES
 #1 INDICATES BUILDING, MECHANICAL, PLUMBING & FUEL GAS
 CODE IN EFFECT AS 2001 WITH 2003 REVISIONS. AT PRESENT
 THE STATE HAS ADOPTED THE FBC-2004 WITH 2006 & 2006
 REVISIONS. PLEASE UPDATE THE DESIGN & CODE REFERENCE.
  
 4. SHT G-100 THE INDEX OF DRAWINGS INDICATES AN
 EXISTING BUILDING. THE DESCRIPTION OF THE PROJECT SHALL
 REFLECT THE PROJECT IN DETAIL. PLEASE HAVE THE
 DESCRIPTION INDICATE AN EXISTING BUILDING, IF IT AN
 ALTERATION, RENOVATION ETC. AND IF IT IS A CHANGE OF
 OCCUPANCY OR NOT AS REQUIRED ON THE APPLICATION. ALSO
 THE TITLE BLOCK PROJECT NAME, "GAINES PARK COMMUNITY
 CENTER EXPANSION" & THE "NEW FACILITY" ON SHT A-100 IS
 NOT INDICATED IN THE PROJECT DESCRIPTION. PLEASE
 CLARIFY. SECTION 105.3.
  
 5. SHT D-100 GENERAL DEMOLITION LEGEND NOTE #3 STATES,
 "CONTRACTOR IS RESPONSIBLE FOR CAPPING & SECURING ALL
 EXISTING UNDER GROUND UTILITIESPRIOR TO COMMENCEMENT
 OF CONSTRUCTION". THESE INCLUDE WATER, SEWER & GAS.
 PLEASE SHOW THE LOCATION WHERE ALL THESE SYSTEMS WILL
 BE CAPPED ON THE DEMO SHEET. SECTION 106.1.2. DEAD ENDS
 WILL BE PROHIBITED PER SECTION 704.5.
  
 6. NO NEW WORK IS SHOWN ON THE PLANS FOR THE EXISTING
 BUILLDING. EXISTING FLOOR PLANS, EXISTING REFLECTED
 CEILING PLAN, EXISTING ELEVATIONS ETC. WERE SUBMITTED
 AND NO PLUMBING SHEETS. PLEASE SUBMIT PLANS SHOWING THE
 EXTENT OF THE WORK BEING DONE IN THE EXISTING BUILDING.
 SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 7. NINE SHEETS WERE SUBMITTED WITH DIFFERENT
 INFORMATION BUT THE SAME SHEET NUMBERS. THIS IS NOT
 APPROVED. (SEE SHEETS G-100, A-101, A-102, A-401 THRU
 A-405 & A-700) SECTION 106.1.3. PLEASE SUBMIT 2
 COMPLETE SETS OF PLANS FOR ALL WORK TO REFLECT THE
 DESCRIPTION OF WORK DETAILED ON THE PERMIT APPLICATION.
 SHEET NUMBERS SHALL NOT DUPLICATE WITH DIFFERENT
 INFORMATION.
  
 8. INDICATE THE LEVEL OF ALTERNATION FOR THE EXISTING
 BUILDING PER CHAPTER 3 OF THE EXISTING BUILDING CODE.
  
 9. SHT G-100 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEET SUBMITTED. SHT A-800 NOT SUBMITTED. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 10. SUBMIT NEW BUILDING DATA. SHOW THE SQUARE FOOTAGE
 OF THE BUILDING AND DECLARE THE OCCUPANCY. IF ASSEMBLY,
 POTTY PARITY MAY BE IN EFFECT. SECTIONS 106.1.2 &
 P-104.3.1.1.
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
  
 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE
 PREPARED?A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE
 CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS, (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL
 COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS
 REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE
 III SECTION 90-124(7)(F).
  
 13. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES S-1004.1.2& P-403.1.
  
 14. SHT A-104 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR ALL ROOFS. SHOW THE SQUARE
 FOOTAGE AREA FOR EACH ROOF DRAIN WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THE ROOF
 DRAIN AREA AS WELL AS ANY ARE OF ROOF THAT DRAINS ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION OF ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS/SCUPPERS REQUIRED BY
 SECTION 1107. SECTION 1106.
  
 15. SHT A-501 SOME ACCESSIBLITY INFORMATION IS NOT
 LEGIBLE NOR COMPLETE. PLEASE MAKE SURE INFORMATION IS
 LEGIBLE. SECTION 106.1.1.
  
 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR ACCESS. STALL:
 A. 11-4.17.3 EXCEPTION(2) THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR.
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES.
  
 17. SUBMIT A DETAIL/ELEVATION FOR THE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 18. SHT A-700 FINISH SCHEDULE FOR ROOMS 164 & 166. THE
 WALLS WITHIN 2 FEET OF WATER CLOSETS AND URINALS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. SECTION
 S-1210.2. PLEASE INDICATE HOW PAINT COMPLIES WITH THESE
 REQUIREMENTS.
  
 19. SHT A-800 IS BLANK, NO INFORMATION. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 20. SHT P-1 THE WATER HEATER INDICATES AN 80 GAL. W/H,
 BUT SHT P-2 ENLARGED PANTRY DETAIL INDICATES A 60 GAL.
 W/H. PLEASE CORRELATE INFORMATION. SECTION 106.1.1.
  
 21. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM. A
 CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER & AT ALL CHANGES OF
 DIRECTION GREATER THAN 45 DEGREES. PLEASE SHOW ON THE
 RISER. SECTIONS 708.3.5 & 708.3.3.
  
 22. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM IS NOT
 COMPLETE. SHOW ALL PIPING TO ALL FIXTURES ON THE RISER.
 SECTION 106.3.5.1.3(4)(6)(13).
  
 23. SHT P-3 DOMESTIC WATER ISOMETRIC RISER DIAGRAM IS
 NOT COMPLETE. SHOW ALL PIPE SIZES, VALVES AND WATER
 HAMMER ARRESTORS THAR ARE REQUIRED ON QUICK CLOSING
 VALVES. (DISH WASHER, ICE MAKER ETC.). SECTION 604.9.
 --SHOW ALL PIPING TO ALL FIXTURES. SECTION
 106.3.5.1.3(3)(10)(13).
  
 24. SUBMIT STORM PIPING INFORMATION. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF DRAINS. SUBMIT A
 STORM ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES,
 OFFSETS & TERMINATION POINT. SECTION
 106.3.5.1.3(7)(13).
  
 25. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, OFFSETS, TRAPS AND TERMINATION POINT
 FOR ALL CONDENSATE PIPING TO REFLECT THE FLOOR PLAN.
 SECTION 106.3.5.1.3(13).
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
  
 27. PLANS DO NOT APPEAR TO BE 100% COMPLETE AND MORE
 COMMENTS MAY BE FORTHCOMING ACCORDING TO COMMENT
 RESPONSES AND NEW INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved