| Date |
Text |
| 2007-10-27 14:04:19 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS CODE |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BUILDING CODE |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | 1. ALL SHEETS. PLANS SHALL BE SIGNED, SEALED, & DATED |
| | AS REQUIRED BY SECTION 106.1, FAC 61G1-16.003, FAC |
| | 61G1-16.004(5), FAC 61G15-23.002(1)(2) & FS 471.025, FS |
| | 481.2055. |
| | |
| | 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT, |
| | ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL |
| | CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS |
| | REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA |
| | STATUTES. |
| | |
| | 3. SHT G-100 GENERAL NOTES 32 INDICATES THE BUILDING |
| | WAS DESIGNED UNDER THE 2001 CODE. ALSO APPLICABLE CODES |
| | #1 INDICATES BUILDING, MECHANICAL, PLUMBING & FUEL GAS |
| | CODE IN EFFECT AS 2001 WITH 2003 REVISIONS. AT PRESENT |
| | THE STATE HAS ADOPTED THE FBC-2004 WITH 2006 & 2006 |
| | REVISIONS. PLEASE UPDATE THE DESIGN & CODE REFERENCE. |
| | |
| | 4. SHT G-100 THE INDEX OF DRAWINGS INDICATES AN |
| | EXISTING BUILDING. THE DESCRIPTION OF THE PROJECT SHALL |
| | REFLECT THE PROJECT IN DETAIL. PLEASE HAVE THE |
| | DESCRIPTION INDICATE AN EXISTING BUILDING, IF IT AN |
| | ALTERATION, RENOVATION ETC. AND IF IT IS A CHANGE OF |
| | OCCUPANCY OR NOT AS REQUIRED ON THE APPLICATION. ALSO |
| | THE TITLE BLOCK PROJECT NAME, "GAINES PARK COMMUNITY |
| | CENTER EXPANSION" & THE "NEW FACILITY" ON SHT A-100 IS |
| | NOT INDICATED IN THE PROJECT DESCRIPTION. PLEASE |
| | CLARIFY. SECTION 105.3. |
| | |
| | 5. SHT D-100 GENERAL DEMOLITION LEGEND NOTE #3 STATES, |
| | "CONTRACTOR IS RESPONSIBLE FOR CAPPING & SECURING ALL |
| | EXISTING UNDER GROUND UTILITIESPRIOR TO COMMENCEMENT |
| | OF CONSTRUCTION". THESE INCLUDE WATER, SEWER & GAS. |
| | PLEASE SHOW THE LOCATION WHERE ALL THESE SYSTEMS WILL |
| | BE CAPPED ON THE DEMO SHEET. SECTION 106.1.2. DEAD ENDS |
| | WILL BE PROHIBITED PER SECTION 704.5. |
| | |
| | 6. NO NEW WORK IS SHOWN ON THE PLANS FOR THE EXISTING |
| | BUILLDING. EXISTING FLOOR PLANS, EXISTING REFLECTED |
| | CEILING PLAN, EXISTING ELEVATIONS ETC. WERE SUBMITTED |
| | AND NO PLUMBING SHEETS. PLEASE SUBMIT PLANS SHOWING THE |
| | EXTENT OF THE WORK BEING DONE IN THE EXISTING BUILDING. |
| | SECTION 106.1.2 (MORE INFORMATION REQUIRED). |
| | |
| | 7. NINE SHEETS WERE SUBMITTED WITH DIFFERENT |
| | INFORMATION BUT THE SAME SHEET NUMBERS. THIS IS NOT |
| | APPROVED. (SEE SHEETS G-100, A-101, A-102, A-401 THRU |
| | A-405 & A-700) SECTION 106.1.3. PLEASE SUBMIT 2 |
| | COMPLETE SETS OF PLANS FOR ALL WORK TO REFLECT THE |
| | DESCRIPTION OF WORK DETAILED ON THE PERMIT APPLICATION. |
| | SHEET NUMBERS SHALL NOT DUPLICATE WITH DIFFERENT |
| | INFORMATION. |
| | |
| | 8. INDICATE THE LEVEL OF ALTERNATION FOR THE EXISTING |
| | BUILDING PER CHAPTER 3 OF THE EXISTING BUILDING CODE. |
| | |
| | 9. SHT G-100 INDEX OF DRAWINGS DOES NOT REFLECT THE |
| | SHEET SUBMITTED. SHT A-800 NOT SUBMITTED. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 10. SUBMIT NEW BUILDING DATA. SHOW THE SQUARE FOOTAGE |
| | OF THE BUILDING AND DECLARE THE OCCUPANCY. IF ASSEMBLY, |
| | POTTY PARITY MAY BE IN EFFECT. SECTIONS 106.1.2 & |
| | P-104.3.1.1. |
| | |
| | 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY |
| | HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR |
| | REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN |
| | REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE |
| | HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION |
| | 102.2.1. |
| | |
| | 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE |
| | PREPARED?A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE |
| | CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL |
| | [email protected] OR CALVIN WILLIAMS, (561) 822-2284, |
| | E-MAIL [email protected]. THEIR FAX NUMBER IS (561) |
| | 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL |
| | COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS |
| | REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE |
| | III SECTION 90-124(7)(F). |
| | |
| | 13. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES S-1004.1.2& P-403.1. |
| | |
| | 14. SHT A-104 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS FOR ALL ROOFS. SHOW THE SQUARE |
| | FOOTAGE AREA FOR EACH ROOF DRAIN WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO THE ROOF |
| | DRAIN AREA AS WELL AS ANY ARE OF ROOF THAT DRAINS ONTO |
| | THE ROOF FROM ABOVE. SHOW THE LOCATION OF ALL ROOF |
| | DRAINS AND SECONDARY ROOF DRAINS/SCUPPERS REQUIRED BY |
| | SECTION 1107. SECTION 1106. |
| | |
| | 15. SHT A-501 SOME ACCESSIBLITY INFORMATION IS NOT |
| | LEGIBLE NOR COMPLETE. PLEASE MAKE SURE INFORMATION IS |
| | LEGIBLE. SECTION 106.1.1. |
| | |
| | 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR ACCESS. STALL: |
| | A. 11-4.17.3 EXCEPTION(2) THE W/C SHALL BE LOCATED IN |
| | THE CORNER DIAGONAL TO THE DOOR. |
| | ___FOR URINALS: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ___FOR LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES. |
| | |
| | 17. SUBMIT A DETAIL/ELEVATION FOR THE DRINKING FOUNTAIN |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 18. SHT A-700 FINISH SCHEDULE FOR ROOMS 164 & 166. THE |
| | WALLS WITHIN 2 FEET OF WATER CLOSETS AND URINALS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. SECTION |
| | S-1210.2. PLEASE INDICATE HOW PAINT COMPLIES WITH THESE |
| | REQUIREMENTS. |
| | |
| | 19. SHT A-800 IS BLANK, NO INFORMATION. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 20. SHT P-1 THE WATER HEATER INDICATES AN 80 GAL. W/H, |
| | BUT SHT P-2 ENLARGED PANTRY DETAIL INDICATES A 60 GAL. |
| | W/H. PLEASE CORRELATE INFORMATION. SECTION 106.1.1. |
| | |
| | 21. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM. A |
| | CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING |
| | DRAIN AND THE BUILDING SEWER & AT ALL CHANGES OF |
| | DIRECTION GREATER THAN 45 DEGREES. PLEASE SHOW ON THE |
| | RISER. SECTIONS 708.3.5 & 708.3.3. |
| | |
| | 22. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM IS NOT |
| | COMPLETE. SHOW ALL PIPING TO ALL FIXTURES ON THE RISER. |
| | SECTION 106.3.5.1.3(4)(6)(13). |
| | |
| | 23. SHT P-3 DOMESTIC WATER ISOMETRIC RISER DIAGRAM IS |
| | NOT COMPLETE. SHOW ALL PIPE SIZES, VALVES AND WATER |
| | HAMMER ARRESTORS THAR ARE REQUIRED ON QUICK CLOSING |
| | VALVES. (DISH WASHER, ICE MAKER ETC.). SECTION 604.9. |
| | --SHOW ALL PIPING TO ALL FIXTURES. SECTION |
| | 106.3.5.1.3(3)(10)(13). |
| | |
| | 24. SUBMIT STORM PIPING INFORMATION. SHOW THE LOCATION |
| | OF ALL PRIMARY AND SECONDARY ROOF DRAINS. SUBMIT A |
| | STORM ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | OFFSETS & TERMINATION POINT. SECTION |
| | 106.3.5.1.3(7)(13). |
| | |
| | 25. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM SHOWING |
| | ALL PIPE SIZES, OFFSETS, TRAPS AND TERMINATION POINT |
| | FOR ALL CONDENSATE PIPING TO REFLECT THE FLOOR PLAN. |
| | SECTION 106.3.5.1.3(13). |
| | |
| | 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION |
| | INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED. |
| | |
| | 27. PLANS DO NOT APPEAR TO BE 100% COMPLETE AND MORE |
| | COMMENTS MAY BE FORTHCOMING ACCORDING TO COMMENT |
| | RESPONSES AND NEW INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |