| 2007-10-30 11:53:01 | REVIEW #: 1 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: AT THIS TIME PLANS ARE SUBMITTED FOR *PLAN REVIWE |
| | ONLY.* NO PERMIT HAS BEEN APPLIED FOR AT THIS TIME. |
| | ADDITIONAL REVIEWS MAY BE POSSIBLE TO VERIFY COMPLIANCE |
| | WITH CODES IN EFFECT AT TIME OF APPLICATION. |
| | |
| | 1. PLAN ONLY SHOWS MECHANICAL SCOPE OF WORK FOR NEW |
| | BUILDING AREA. NO INFORMATION WAS PROVIDED REGARDING |
| | SCOPE OF MECHANICAL WORK IN EXISTING AREAS. WHAT IS THE |
| | LEVEL OF ALTERATION IN EXISTING BUILDING? THE DESIGN |
| | PROFESSIONAL MUST ELECT ONE OR A COMBINATION OF LEVELS |
| | OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE IN ACCORDANCE WITH FBC, EB 301.5. THIS |
| | INFORMATION MAY IMPACT THE LEVEL OF CODE COMPLIANCE |
| | REQUIRED IN EXISTING AREAS. |
| | |
| | 2. A SCHEDULE OF WALL TYPES COULD NOT BE LOCATED IN |
| | PLANS. WITHOUT THIS INFORMATION IT IS NOT POSSIBLE TO |
| | DETERMINE SOME REQUIREMENTS SUCH AS WHERE OPENING |
| | PROTECTIVES (FIRE AND/OR SMOKE DAMPERS) ME BE REQUIRED. |
| | FBC,M 607.5. PROVIDE ALL MISSING INFORMATION NEEDED TO |
| | PERFORM A COMPLETE REVIEW. FBC 106.1.1. |
| | |
| | 3. PG M-1: OUTSIDE AIR AND EXHAUST, THE CALCULATIONS |
| | STATE "BASED ON FBC2004 - MECHANICAL AND ASHRAE 62." |
| | PLEASE DECLARE WHICH METHOD IS BEING USED, EITHER FBC,M |
| | 403.3 OR ASHRAE 62.1-2004. ONE METHOD OR THE OTHER MAY |
| | BE USED BUT NOT BOTH. SEE FBC,M 403.4. VENTILATION AND |
| | EXHAUST REQUIREMENTS CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | 4. PG M-2: AHU'S 1 AND 2 SHOW A COMMON RETURN PLENUM. |
| | SAME WITH AHU'S 3 AND 4. AS SUCH, SMOKE DETECTORS ARE |
| | REQUIRED ON BOTH THE SUPPLY AND RETURN IN ACCORDANCE |
| | WITH FBC,M 606.2.2. ALSO, SMOKE DETECTORS SHALL BE |
| | CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN |
| | ACCORDANCE WITH FBC,M 606.4.1. SHOW COMPLIANCE WITH |
| | THESE SECTIONS. |
| | |
| | 5. M-3 FLEXIBLE DUCT DETAIL: |
| | A) PLEASE REFERENCE THE CORRECT CODE: FBC,M 2004, AND |
| | NOT 2001. |
| | B) FLEXIBLE DUCT SUPPORTS SHALL BE NOT LESS THAN 1 1/2 |
| | IN. WIDE PER FBC,M 603.5.6.6(6), NOT 1 IN. AS STATED IN |
| | DETAIL NOTES. |
| | |
| | 6. M-3: OA/EXHAUST VENT DETAIL, SHOW ROOF CURB AND |
| | VENTILATORS TO BE DESIGNED TO MEET 140MPH WINDS IN |
| | ACCORDANCE WITH FBC,M 301.13 AND FBC SEC 1609. SHOW |
| | SUFFICIENT DETAIL FOR CURB TO ROOF AND VENT TO CURB |
| | ATTACHMENTS ALONG WITH WIND LOAD CALCULATIONS FOR |
| | STRUCTURAL REVIEW. FBC 106.1.2. |
| | |
| | 7. M-2: KEY NOTE 1, PROVIDE DETAIL FOR CONDENSING UNIT |
| | ATTACHMENTS TO SLABS SHOWING HOW UNITS ARE TO BE |
| | ATTACHED TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE |
| | WITH FBC,M 301.13 AND FBC 1609. PROVIDE MANUFACTURER'S |
| | SUBMITTAL SHOWING EQUIPMENT DESIGNED FOR MIN. 140MPH |
| | AND WIND LOAD CALCULATIONS FOR ATTACHMENTS FOR |
| | STRUCTURAL REVIEW. FBC 106.1.2. |
| | |
| | 8. M-2: PLEASE SHOW SIZE AND ROUTING OF REFRIGERANT |
| | LINES FROM REMOTE CONDENSERS TO AHU'S AND SHOW |
| | COMPLIANCE WITH FBC,M 1107.2.1 WHERE PIPES PASS UNDER A |
| | SLAB OR THROUGH WALLS, CEILINGS, FLOORS OR BEAMS. |
| | |
| | 9. PROVIDE ENERGY CODE COMPLIANCE FORM/ CALCULATIONS TO |
| | SHOW COMPLIANCE WITH FBC CH.13 IN ACCORDANCE WITH FBC |
| | 13-400.0 AND 13-101.1. A REVIEW FOR FLORIDA ENERGY CODE |
| | COMPLIANCE CAN NOT BE PERFORMED AT THIS TIME. |
| | |
| | 10. PORVIDE SUBMITTAL FOR GENERATOR AS SHOWN ON A-101 |
| | AND P-2. GENERATORS SHALL BE IN COMPLIANCE WITH NFPA |
| | 37-02 IN ACCORDANCE WITH FBC,M 915.1. |
| | |
| | 11. A MINIMUM OF TWO SETS OF PLANS SHALL BE SUBMITTED |
| | PER FBC 106.1 AND SHALL BE SIGNED AND SEALED BY THE |
| | DESIGNER OF RECORD IN ACCORDANCE WITH FS 471 AND 481. |
| | ALSO PLEASE SEE FAC RULE 61G15-23.002 FOR ADDITIONAL |
| | REQUIREMENTS FOR DESSIGNERS PROVIDING SERVICES UNDER AN |
| | ENGINEERING BUSINESS. |
| | |
| | NOTE: DUE TO THE SIGNIFICANT VOLUME OF MISSING |
| | INFORMATION, ADDITIONAL REVIEW COMMENTS ARE LIKELY FROM |
| | SUBSEQUENT REVIEWS ONCE ALL MISSING INFORMATION IS |
| | PROVIDED. |
| | |