Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 11:23:341. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. ALL DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO ANY
 EXCAVATING.
  
 4. ON PAGE FOUR LABELED WATER DISTRIBUTION AND
 WASTEWATER PLANS ONLY ONE FIRE HYDRANT, FIRE HYDRANT #
 1 IS SHOWN. PLEASE DISPLAY ALL EXISTING AND NEW FIRE
 HYDRANTS FOR THE SITE.
  
 5. ALL FIRE LINE BAKFLOW DEVICES SHALL BE EQUIPPED WITH
 TAMPER SWITCHES, CHAINS AND LOCKS.
  
 6. ALL NEW FIRE HYDRANTS SHALL MEET UTILITY AND FIRE
 RESCUE STANDARDS.
  
 7. SUITABLE FIRE AND PARAMEDICAL ACCESS SHALL BE
 PROVIDED DURING CONSTRUCTION.
  
 8. PLEASE ILLUSTRATE ALL ACCESS POINTS TO THE EXISTING
 FACILITY THAT CAN BE USED BY FIRE RESCUE.
  
 9. BUILDING ADDRESS REQUIRED ON NEW STRUCTURE. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1"
 WIDE SHALL BE PROVIDED. NUMBERS SHALL CONTRAST WITH THE
 BACKGROUND.
  
 10. A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
  
 11. KNOX-BOX LOCKING CAPS SHALL BE PROVIDED FOR THE NEW
 FIRE DEPARTMENT CONNECTION.
  
 12. SEPERATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM INSTALLATION.
  
 13. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM EQUIPMENT INSTALLATION.
  
 14. FIRE SPRINKLER AND FIRE ALARM SYSTEM TO BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 15. PLEASE EXPLAIN SINGLE EXIT DOOR LEADING FROM THE
 MULTI-PURPOSE ROOM INTO THE PANTRY AREA.
  
 16. ARE ANY EMERGENCY LIGTHING FIXTURES PLANNED FOR THE
 RESTROOMS.
  
 17. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED WITH
 PLANS. PLANS AND CALCULATIONS ARE TO BE PROVIDED.
  
 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE
 BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE.
  
 19. ARE ANY CARBON MONOXIDE DETECTORS PLANNED TO BE
 INSTALLED.
  
 20. NATURAL GAS INSTALLATION TO COMPLY WITH NFPA CODES
 AND ALL OTHER APPLICABLE CODES AND STANDARDS.
  
 21. WHAT IS THE PROPOSED HEIGHT OF THE PORTACACHERE.
  
 22. LIFE SAFETY SHEET PAGE A-800 IS BLANK.
  
 23. DOOR SCHEDULE ON PAGE A-700 DECLARES NO RATED FIRE
 DOORS PLANNED FOR THE SITE.
  
 24. PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED
 ON ALL DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100 OR
 MORE PERSONS.
  
 25. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 26. PLEASE DECLARE CONSTRUCTION OF TRELLIS.
  
 27. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ANY HANDRAILS OR GUARDRAILS.
  
 29. STAIRS ARE TO COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE.
  
 30. ALL EXTERIOR STAIRS USED FOR EXIT DISCHARGE SHALL
 BE SLIP RESISTANT.
  
 31. PLEASE DECLARE LOCATIONS OF ALL FIRE EXTINGUISHERS
 AND THE TYPES BEING PROPOSED.
  
 32. PLEASE PROVIDE DETAILS ON FLAME SPREAD FOR THE
 DIVISING WALLS AND ANY HARDWARE ATTACHED TO THIS
 DEVICE.
  
 33. PLEASE EXPLAIN PURPOSE OF CLASSROOM. WHAT AGES ARE
 PLANNED.
  
 34. OCCUPANT LOAD TO BE DETERMINED BY THE BUREAU OF
 FIRE PREVENTION.
  
 35. TABLES AND CHAIRS APPEAR TO BE TIGHT IN SOME
 LOCALES IN THE MULTI-PURPOSE ROOM.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX