| 2007-10-22 11:23:34 | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 2. ALL DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 3. UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO ANY |
| | EXCAVATING. |
| | |
| | 4. ON PAGE FOUR LABELED WATER DISTRIBUTION AND |
| | WASTEWATER PLANS ONLY ONE FIRE HYDRANT, FIRE HYDRANT # |
| | 1 IS SHOWN. PLEASE DISPLAY ALL EXISTING AND NEW FIRE |
| | HYDRANTS FOR THE SITE. |
| | |
| | 5. ALL FIRE LINE BAKFLOW DEVICES SHALL BE EQUIPPED WITH |
| | TAMPER SWITCHES, CHAINS AND LOCKS. |
| | |
| | 6. ALL NEW FIRE HYDRANTS SHALL MEET UTILITY AND FIRE |
| | RESCUE STANDARDS. |
| | |
| | 7. SUITABLE FIRE AND PARAMEDICAL ACCESS SHALL BE |
| | PROVIDED DURING CONSTRUCTION. |
| | |
| | 8. PLEASE ILLUSTRATE ALL ACCESS POINTS TO THE EXISTING |
| | FACILITY THAT CAN BE USED BY FIRE RESCUE. |
| | |
| | 9. BUILDING ADDRESS REQUIRED ON NEW STRUCTURE. A |
| | MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1" |
| | WIDE SHALL BE PROVIDED. NUMBERS SHALL CONTRAST WITH THE |
| | BACKGROUND. |
| | |
| | 10. A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| | |
| | 11. KNOX-BOX LOCKING CAPS SHALL BE PROVIDED FOR THE NEW |
| | FIRE DEPARTMENT CONNECTION. |
| | |
| | 12. SEPERATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER SYSTEM INSTALLATION. |
| | |
| | 13. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| | SYSTEM EQUIPMENT INSTALLATION. |
| | |
| | 14. FIRE SPRINKLER AND FIRE ALARM SYSTEM TO BE |
| | MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 15. PLEASE EXPLAIN SINGLE EXIT DOOR LEADING FROM THE |
| | MULTI-PURPOSE ROOM INTO THE PANTRY AREA. |
| | |
| | 16. ARE ANY EMERGENCY LIGTHING FIXTURES PLANNED FOR THE |
| | RESTROOMS. |
| | |
| | 17. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED WITH |
| | PLANS. PLANS AND CALCULATIONS ARE TO BE PROVIDED. |
| | |
| | 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE |
| | BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE. |
| | |
| | 19. ARE ANY CARBON MONOXIDE DETECTORS PLANNED TO BE |
| | INSTALLED. |
| | |
| | 20. NATURAL GAS INSTALLATION TO COMPLY WITH NFPA CODES |
| | AND ALL OTHER APPLICABLE CODES AND STANDARDS. |
| | |
| | 21. WHAT IS THE PROPOSED HEIGHT OF THE PORTACACHERE. |
| | |
| | 22. LIFE SAFETY SHEET PAGE A-800 IS BLANK. |
| | |
| | 23. DOOR SCHEDULE ON PAGE A-700 DECLARES NO RATED FIRE |
| | DOORS PLANNED FOR THE SITE. |
| | |
| | 24. PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED |
| | ON ALL DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100 OR |
| | MORE PERSONS. |
| | |
| | 25. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | 26. PLEASE DECLARE CONSTRUCTION OF TRELLIS. |
| | |
| | 27. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ANY HANDRAILS OR GUARDRAILS. |
| | |
| | 29. STAIRS ARE TO COMPLY WITH THE FLORIDA BUILDING AND |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 30. ALL EXTERIOR STAIRS USED FOR EXIT DISCHARGE SHALL |
| | BE SLIP RESISTANT. |
| | |
| | 31. PLEASE DECLARE LOCATIONS OF ALL FIRE EXTINGUISHERS |
| | AND THE TYPES BEING PROPOSED. |
| | |
| | 32. PLEASE PROVIDE DETAILS ON FLAME SPREAD FOR THE |
| | DIVISING WALLS AND ANY HARDWARE ATTACHED TO THIS |
| | DEVICE. |
| | |
| | 33. PLEASE EXPLAIN PURPOSE OF CLASSROOM. WHAT AGES ARE |
| | PLANNED. |
| | |
| | 34. OCCUPANT LOAD TO BE DETERMINED BY THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | 35. TABLES AND CHAIRS APPEAR TO BE TIGHT IN SOME |
| | LOCALES IN THE MULTI-PURPOSE ROOM. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | 804-4709 PHONE |
| | 804-4774 FAX |