| Date |
Text |
| 2007-10-21 16:09:05 | 2007-10-21 16:09:05 |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED |
| | FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT. |
| | PLEASE ALSO SEE THAT PLANS AS SUBMITTED ARE NOT |
| | COMPLETE AND A COMPLETE REVIEW CAN NOT BE DONE. SOME |
| | SHEETS ARE 60 PERCENT AND SOME SHEETS LIKE THE LIFE |
| | SAFETY PLANS ARE BLANK WITH NO INFORMATION. |
| | PLEASE SEE THERE IS NUMEROUS SUPPORTING DOCUMENTATION |
| | NEEDED FOR REVIEW WHICH WAS NOT SUBMITTED. |
| | ** PLEASE KNOW THAT REVIEW NOTES CAN ONLY BE MADE ON |
| | PLANS AND DOCUMENTS SUBMITTED. THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| | POSSIBLY BE MADE AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE |
| | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC |
| | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE |
| | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL |
| | TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | ** PLEASE SEE SOME CODES ARE SHOWN ON COVER SHEETS |
| | WHICH ARE NO LONGER IN AFFECT IN THE STATE OF FLORIDA |
| | PLEASE SEE FOR EXAMPLE THE 2002 NFPA-70 AND 2000 |
| | NFPA-101 WHICH IS REFLECTED ON PLANS. |
| | |
| | 3) NOTE: PLEASE BE SURE WHEN PLANS ARE SUBMITTED THAT |
| | ALL SHEETS CONTAIN COMPLETED TITLE BLOCKS ON ALL SHEETS |
| | AND FOR ALL TRADES ON THE RESPECTIVE SHEETS. PLEASE SEE |
| | FAC 61G1-16.004, 61G15-23.002 ETC AS THIS INCLUDES |
| | ARCHITECTURAL, LANDSCAPE, MEP ETC. |
| | |
| | 4) NOTE: PLEASE BE SURE ALL PLANS ARE SIGNED, DATED AND |
| | SEALED AS REQUIRED PER THE SAME SECTIONS ON THE FAC AND |
| | FLORIDA STATUTES 471.025, 481.221 ETC. |
| | |
| | 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC |
| | CHAPTER 13. |
| | PLEASE BE SURE TO SEE THE FACT THAT THIS NEW BUILDING |
| | ELECTRICAL SERVICE WILL FEED EXISTING BUILDING WHICH |
| | WILL HAVE ENERGY USE. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.1.ABC.1.2, |
| | 13-415.2.ABC.1.3 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 ETC |
| | |
| | 6) NOTE: PLEASE SUBMIT MORE INFORMATION ON COMPLETE |
| | LIGHTING CONTROLS AND SYSTEM PER 13-415.1.1, .1.2, .1.3 |
| | AND .1.4. |
| | NOT ENOUGH INFORMATION SUBMITTED FOR COMPLETE REVIEW. |
| | PLANS APPEARS TO SHOW STANDARD SWITCHING DEVICES. FBC |
| | 106.1.23 FOR ADDITIONAL INFORMATION. |
| | |
| | 7) NOTE: PLEASE SHOW ALL FIRE ALARM DEVICE LOCATIONS |
| | AND MINIMUM LEVELS FOR ADA COMPLIANCE. |
| | PLEASE SEE FBC 11-4.28.1,.2, AND .3(4) |
| | ** THIS IS REQUIRED EVEN AS THE FIRE ALARM PLANS ARE |
| | UNDER SEPARATE PERMITS AND PLANS. |
| | |
| | 8) NOTE: PLEASE PROVIDE INFORMATION ON ANY EMERGENCY |
| | AND/OR LIFE SAFETY SYSTEMS OR DEVICES IN THE EXISTING |
| | BUILDINGS WHICH MAY BE FED FROM THIS NEW GENERATOR. |
| | THIS MAY AFFECT THE RISER AND SYSTEM AS SHOWN. 700.1, |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 9) NOTE: PLEASE SEE KEY NOTES ON E-1 ARE NOT COMPLETE |
| | ON PLANS. |
| | PLEASE SHOW AND LABEL ALL SERVICE EQUIPMENT ON PLANS. |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | NEC 240.24, 110.26 ETC |
| | |
| | 10) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT |
| | SHEETS FOR THE PROPOSED GENERATOR AND ATS. |
| | 110.3, 90.7. |
| | FBC 106.1.2 ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE INDICATE THE MINIMUM LIGHTING LEVELS |
| | FOR EGRESS PATHS TO PUBLIC RIGHT OF WAY/EXIT |
| | DISCHARGE. |
| | PLEASE SEE FOR EXAMPLE THE ENTRANCE HALLWAY WHICH DOES |
| | NOT SHOW ANY EMERGENCY LIGHTING. |
| | LS-101 7.8, 7.9. |
| | FAC 61G15-33.004. |
| | PLEASE SEE AS THE LIFE SAFETY PLANS ARE NOT COMPLETE, |
| | PLEASE BE SURE TO SEE NFPA-101 7.10.1.6 AND 12.4.7.7.2 |
| | IN ASSEMBLY AREAS FOR POSSIBLE FLOOR PROXIMITY EXIT |
| | LIGHTING. |
| | PLEASE ALSO SEE FBC CHAPTER 1006.3.8.2, 1006.3.8.3. |
| | |
| | 12) NOTE: PLEASE SEE 2005 NEC FOR LOAD CALCULATIONS. |
| | PLEASE SEE FOR EXAMPLE ELECTRICAL WATER HEATER LOADS |
| | ARE NOW CONSIDERED CONTINUOUS IN THE NEW CODE. THIS |
| | REQUIRES THE LOADS TO BE SHOWN AND FIGURED AT 125%. |
| | PLEASE ALSO SEE THE LOAD SHOWN *PER FPL* FOR THE |
| | EXISTING PANEL SW EXCEEDS THAT OF THE RATING OF THE NEW |
| | FEEDERS AND OVER CURRENT PROTECTION FEEDING THIS |
| | EXISTING EQUIPMENT. 240.4, 310.16 ETC. |
| | PLEASE THE SECTION OF THE CODE REFLECTED ON |
| | CALCULATIONS IS FROM THE PREVIOUS CODE. |
| | ** PLEASE PROVIDE MORE INFORMATION ON THE EXISTING |
| | LOADS ON THE EXISTING BUILDINGS. *SW* IS GOING FROM A |
| | 1200AMP SERVICE DOWN TO A 600AMP FEEDER WHICH CREATES |
| | SOME QUESTIONS. |
| | NEC 220. |
| | FBC 106.3.5.1.2 |
| | |
| | 13) NOTE: PLEASE PLACE NOTE(S) ON RISER/PLANS FOR |
| | DISCONNECTS AT THE EXISTING BUILDINGS WHICH WILL NOW |
| | BED FROM THE NEW SERVICE. |
| | PLEASE SE THAT ALL NEUTRAL AND GROUNDING CONNECTIONS AT |
| | THE FIRST MEANS OF DISCONNECT MUST BE SEPARATED. THIS |
| | IS FOR MAIN DISCONNECTS 8/10/ AND 12 AS LABELED WITH |
| | NOTES ON RISER. |
| | ** OCTAGONAL NOTE #12 DOES CONTAIN A MENTION OF |
| | REMOVING BONDING JUMPER. |
| | 250.6, 250.24 ETC |
| | |
| | 14) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR |
| | WORST CASE ON FEEDERS PER 13-413.1.ABC.1.1 AND BRANCH |
| | CIRCUITS PER 13-413.1.ABC.1.2., |
| | **ONLY NEED TO SHOW WORST CASE FOR EACH. |
| | |
| | 15) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE |
| | BREAKER ON THE GENERATOR. WILL THIS BREAKER BE READILY |
| | ACCESSIBLE FOR DISCONNECTING THE EMERGENCY POWER? AS |
| | THIS CAN NOT BE CONFIRMED, THE DP MAY BE REQUIRED TO |
| | CONTAIN A DISCONNECTING MEANS SUCH AS A MAIN CIRCUIT |
| | BREAKER OR DISCONNECT ON THE LOAD SIDE OF THE GENERATOR |
| | MAY BE REQUIRED. |
| | IF BREAKER IS ON UNIT AND IS READILY ACCESSIBLE, THEN |
| | PLEASE PROVIDE NOTE FOR SIGNAGE REQUIRED FOR DISCONNECT |
| | MEANS DURING AND EMERGENCY SITUATION. |
| | 445.18 |
| | |
| | 16) NOTE: PLEASE KNOW THE RESTROOMS AS SHOWN ON PLANS |
| | WILL BE REQUIRED TO CONTAIN A BATTERY BACK UP LIGHTING |
| | FIXTURE OF SOME KIND FOR EGRESS LIGHTING. |
| | PLEASE BE SURE TO ALSO KNOW THAT DEPENDING ON LIGHTING |
| | CONTROL DEVICES WHICH HAVE NOT YET BEEN REVIEWED, A |
| | NIGHT LIGHT MAY BE NEEDED. |
| | PLEASE SEE NEC 700.12F, 700.16, LS 101 7.8, 7.9. PLEASE |
| | SEE NOTES ABOVE WITH RESPECT TO LIGHTING LEVELS |
| | REQUIRED FOR EGRESS. |
| | |
| | ** PLEASE KNOW AS MENTIONED ABOVE AS PLANS AND |
| | INFORMATION IS NOT COMPLETED A COMPLETE REVIEW COULD |
| | NOT BE DONE. |
| | |
| | ** PLEASE SURE TO SEE COMMENTS FROM OTHER TRADES WHICH |
| | MAY ALSO AFFECT THE ELECTRICAL PLANS/DESIGN. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |