Plan Review Notes
Plan Review Notes For Permit 07100001
Permit Number 07100001
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-21 16:09:052007-10-21 16:09:05
  
 *** DENIED ***
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED
 FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 PLEASE ALSO SEE THAT PLANS AS SUBMITTED ARE NOT
 COMPLETE AND A COMPLETE REVIEW CAN NOT BE DONE. SOME
 SHEETS ARE 60 PERCENT AND SOME SHEETS LIKE THE LIFE
 SAFETY PLANS ARE BLANK WITH NO INFORMATION.
 PLEASE SEE THERE IS NUMEROUS SUPPORTING DOCUMENTATION
 NEEDED FOR REVIEW WHICH WAS NOT SUBMITTED.
 ** PLEASE KNOW THAT REVIEW NOTES CAN ONLY BE MADE ON
 PLANS AND DOCUMENTS SUBMITTED. THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 POSSIBLY BE MADE AT THIS TIME.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
  
 ** PLEASE SEE SOME CODES ARE SHOWN ON COVER SHEETS
 WHICH ARE NO LONGER IN AFFECT IN THE STATE OF FLORIDA
 PLEASE SEE FOR EXAMPLE THE 2002 NFPA-70 AND 2000
 NFPA-101 WHICH IS REFLECTED ON PLANS.
  
 3) NOTE: PLEASE BE SURE WHEN PLANS ARE SUBMITTED THAT
 ALL SHEETS CONTAIN COMPLETED TITLE BLOCKS ON ALL SHEETS
 AND FOR ALL TRADES ON THE RESPECTIVE SHEETS. PLEASE SEE
 FAC 61G1-16.004, 61G15-23.002 ETC AS THIS INCLUDES
 ARCHITECTURAL, LANDSCAPE, MEP ETC.
  
 4) NOTE: PLEASE BE SURE ALL PLANS ARE SIGNED, DATED AND
 SEALED AS REQUIRED PER THE SAME SECTIONS ON THE FAC AND
 FLORIDA STATUTES 471.025, 481.221 ETC.
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC
 CHAPTER 13.
 PLEASE BE SURE TO SEE THE FACT THAT THIS NEW BUILDING
 ELECTRICAL SERVICE WILL FEED EXISTING BUILDING WHICH
 WILL HAVE ENERGY USE.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.1.ABC.1.2,
 13-415.2.ABC.1.3 ETC.
 FBC 106.1.2, 106.3.5.1.2 ETC
  
 6) NOTE: PLEASE SUBMIT MORE INFORMATION ON COMPLETE
 LIGHTING CONTROLS AND SYSTEM PER 13-415.1.1, .1.2, .1.3
 AND .1.4.
 NOT ENOUGH INFORMATION SUBMITTED FOR COMPLETE REVIEW.
 PLANS APPEARS TO SHOW STANDARD SWITCHING DEVICES. FBC
 106.1.23 FOR ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SHOW ALL FIRE ALARM DEVICE LOCATIONS
 AND MINIMUM LEVELS FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2, AND .3(4)
 ** THIS IS REQUIRED EVEN AS THE FIRE ALARM PLANS ARE
 UNDER SEPARATE PERMITS AND PLANS.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON ANY EMERGENCY
 AND/OR LIFE SAFETY SYSTEMS OR DEVICES IN THE EXISTING
 BUILDINGS WHICH MAY BE FED FROM THIS NEW GENERATOR.
 THIS MAY AFFECT THE RISER AND SYSTEM AS SHOWN. 700.1,
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 9) NOTE: PLEASE SEE KEY NOTES ON E-1 ARE NOT COMPLETE
 ON PLANS.
 PLEASE SHOW AND LABEL ALL SERVICE EQUIPMENT ON PLANS.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 NEC 240.24, 110.26 ETC
  
 10) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT
 SHEETS FOR THE PROPOSED GENERATOR AND ATS.
 110.3, 90.7.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE INDICATE THE MINIMUM LIGHTING LEVELS
 FOR EGRESS PATHS TO PUBLIC RIGHT OF WAY/EXIT
 DISCHARGE.
 PLEASE SEE FOR EXAMPLE THE ENTRANCE HALLWAY WHICH DOES
 NOT SHOW ANY EMERGENCY LIGHTING.
 LS-101 7.8, 7.9.
 FAC 61G15-33.004.
 PLEASE SEE AS THE LIFE SAFETY PLANS ARE NOT COMPLETE,
 PLEASE BE SURE TO SEE NFPA-101 7.10.1.6 AND 12.4.7.7.2
 IN ASSEMBLY AREAS FOR POSSIBLE FLOOR PROXIMITY EXIT
 LIGHTING.
 PLEASE ALSO SEE FBC CHAPTER 1006.3.8.2, 1006.3.8.3.
  
 12) NOTE: PLEASE SEE 2005 NEC FOR LOAD CALCULATIONS.
 PLEASE SEE FOR EXAMPLE ELECTRICAL WATER HEATER LOADS
 ARE NOW CONSIDERED CONTINUOUS IN THE NEW CODE. THIS
 REQUIRES THE LOADS TO BE SHOWN AND FIGURED AT 125%.
 PLEASE ALSO SEE THE LOAD SHOWN *PER FPL* FOR THE
 EXISTING PANEL SW EXCEEDS THAT OF THE RATING OF THE NEW
 FEEDERS AND OVER CURRENT PROTECTION FEEDING THIS
 EXISTING EQUIPMENT. 240.4, 310.16 ETC.
 PLEASE THE SECTION OF THE CODE REFLECTED ON
 CALCULATIONS IS FROM THE PREVIOUS CODE.
 ** PLEASE PROVIDE MORE INFORMATION ON THE EXISTING
 LOADS ON THE EXISTING BUILDINGS. *SW* IS GOING FROM A
 1200AMP SERVICE DOWN TO A 600AMP FEEDER WHICH CREATES
 SOME QUESTIONS.
 NEC 220.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE PLACE NOTE(S) ON RISER/PLANS FOR
 DISCONNECTS AT THE EXISTING BUILDINGS WHICH WILL NOW
 BED FROM THE NEW SERVICE.
 PLEASE SE THAT ALL NEUTRAL AND GROUNDING CONNECTIONS AT
 THE FIRST MEANS OF DISCONNECT MUST BE SEPARATED. THIS
 IS FOR MAIN DISCONNECTS 8/10/ AND 12 AS LABELED WITH
 NOTES ON RISER.
 ** OCTAGONAL NOTE #12 DOES CONTAIN A MENTION OF
 REMOVING BONDING JUMPER.
 250.6, 250.24 ETC
  
 14) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR
 WORST CASE ON FEEDERS PER 13-413.1.ABC.1.1 AND BRANCH
 CIRCUITS PER 13-413.1.ABC.1.2.,
 **ONLY NEED TO SHOW WORST CASE FOR EACH.
  
 15) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE
 BREAKER ON THE GENERATOR. WILL THIS BREAKER BE READILY
 ACCESSIBLE FOR DISCONNECTING THE EMERGENCY POWER? AS
 THIS CAN NOT BE CONFIRMED, THE DP MAY BE REQUIRED TO
 CONTAIN A DISCONNECTING MEANS SUCH AS A MAIN CIRCUIT
 BREAKER OR DISCONNECT ON THE LOAD SIDE OF THE GENERATOR
 MAY BE REQUIRED.
 IF BREAKER IS ON UNIT AND IS READILY ACCESSIBLE, THEN
 PLEASE PROVIDE NOTE FOR SIGNAGE REQUIRED FOR DISCONNECT
 MEANS DURING AND EMERGENCY SITUATION.
 445.18
  
 16) NOTE: PLEASE KNOW THE RESTROOMS AS SHOWN ON PLANS
 WILL BE REQUIRED TO CONTAIN A BATTERY BACK UP LIGHTING
 FIXTURE OF SOME KIND FOR EGRESS LIGHTING.
 PLEASE BE SURE TO ALSO KNOW THAT DEPENDING ON LIGHTING
 CONTROL DEVICES WHICH HAVE NOT YET BEEN REVIEWED, A
 NIGHT LIGHT MAY BE NEEDED.
 PLEASE SEE NEC 700.12F, 700.16, LS 101 7.8, 7.9. PLEASE
 SEE NOTES ABOVE WITH RESPECT TO LIGHTING LEVELS
 REQUIRED FOR EGRESS.
  
 ** PLEASE KNOW AS MENTIONED ABOVE AS PLANS AND
 INFORMATION IS NOT COMPLETED A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** PLEASE SURE TO SEE COMMENTS FROM OTHER TRADES WHICH
 MAY ALSO AFFECT THE ELECTRICAL PLANS/DESIGN.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]