| 2007-10-26 14:15:06 | BUILDING PLAN REVIEW |
| | PERMIT: 07100001 |
| | ADD: 1505 N AUSTRALIAN AVE. |
| | CONT: :?PLAN REVIEW/ MAJOR WORKING DRAWING? |
| | TEL: (561644-7416 JEFF HALVERSON |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS. |
| | |
| | 1E) THE MAJOR WORKING DRAWING REVIEW UNDER SCOPE OF |
| | PROJECT INDICATES A 10,000 SQ FT MULTIPURPOSE BUILDING, |
| | PLEASE ADD THE RENOVATION TO THE EXISTING BUILDING TO |
| | THE APPLICATION. |
| | |
| | 2) DESIGN PROFESSIONAL REQUIREMENTS: |
| | |
| | 2A) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 2B) 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE |
| | TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| | ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | LANDSCAPE ARCHITECT |
| | BA ARCHITECTURAL |
| | |
| | 2C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE |
| | TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY |
| | HAND. |
| | STRUCTURAL ENGINEER |
| | MEP ENGINEER |
| | CIVIL ENGINEER |
| | |
| | 3) NEW BUILDING CONSTRUCTION. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. A THOROUGH REVIEW CAN NOT BE MADE |
| | AT THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION |
| | REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT |
| | PART OF THIS REVIEW. |
| | |
| | 3A) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3& 106.3.5.1.1(3). |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5 & |
| | 6, TABLE 503 & 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED F) |
| | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | H) SQ. FT. FOOTPRINT |
| | |
| | 3B) THE S-3.1 INDICATES THE WIND DESIGN FROM ASCE |
| | 7-02FOR THE BUILDING, PLEASE REVIEW THE BUILDINGS |
| | CATEGORY AND IMPORTANCE FACTOR. PLEASE REVIEW SHEET |
| | A-101 & A-102 FOR OCCUPANCY. AS INDICATED THESE SHEETS |
| | INDICATE THE CAPABILITY OF 350 PEOPLE WITH THE ACTUAL |
| | OCCUPANT LOAD BEING QUIET HIGHER. PLEASE SEE ASCE 7-02 |
| | TABLE 1-1 BUILDING CATEGORY III, |
| | BUILDINGS AND OTHER STRUCTURES WHERE MORE THAN 300 |
| | PEOPLE CONGREGATE IN ONE AREA. PLEASE REVISE THE |
| | BUILDING CATEGORY AND IMPORTANCE FACTOR. |
| | |
| | 3C) THE ABOVE CORRECTION OF BUILDING CATEGORY AND |
| | IMPORTANCE FACTOR WILL ALSO EFFECT THE |
| | COMPONENTS AND CLADDING PRESSURES FOR THE WINDOWS AND |
| | DOORS AS WELL AS THE ROOF ASSEMBLIES. ASCE 7-02 |
| | COMPONENTS & CLADDING ?METHOD 1FIGURE 6-3, WALLS & |
| | ROOFS, |
| | AND HEIGHT ADJUSTMENT FACTORS FOR A MEAN ROOF HEIGHT OF |
| | 18?-3? , ADJUSTMENT FACTOR 1.29 FOR 20 FT. . |
| | |
| | 4) THE LIFE SAFETY SHEET A-800 IS TOTALLY |
| | BLANK!!!!!!!!!!!!!!!!! PLEASE PROVIDE A MEANS OF EGRESS |
| | PLAN LIFE SAFETY PLAN AND PROVIDE THE OCCUPANT LOADS |
| | THAT WILL BE GOING THROUGH EACH OF THE EGRESSES. SEE |
| | TABLE 1004.1.2, TABLE 1005. |
| | |
| | 5A) ONE CONCERN IS THE ANSWER TO QUESTION 3C, THE PLANS |
| | ARE NOT CLEAR AS TO THE DISTANCE BETWEEN THE NEW |
| | BUILDING AND EXISTING BUILDINGS, WHERE IF NEEDED, |
| | ASSUMED PROPERTY LINES WOULD BE PLACED FOR THE AMOUNT |
| | OF ALLOWABLE OPENINGS, WITH OR WITHOUT OPENING |
| | PROTECTIVE?S FOR EACH BUILDING. |
| | |
| | THE OTHER UNKNOWN AT THIS TIME IS IF THE DESIGN TEAM |
| | WERE TO DESIGN THIS UNDER THE CODE SECTION 503.1.3, TWO |
| | BUILDINGS ON THE SAME LOT, THESE TYPE ISSUES NEED TO BE |
| | ADDRESSED BEFORE WE CAN REVIEW FOR ALLOWABLE AREAS, |
| | FIRE RESISTANCE, TABLE 601, TABLE 602 AND TABLE 704.8. |
| | |
| | 5B) AT THIS TIME BECAUSE OF THE UNKNOWN BUILDING |
| | FACTORS THIS COMMENT MAY OR MAY NOT APPLY IN FUTURE |
| | REVIEWS: FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT |
| | INSPECTOR RESUME' AND LICENSE DOCUMENTS TO HAROLD |
| | PISKURA, DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. A |
| | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS |
| | PROJECT, DUE TO ONE OR MORE OF |
| | THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION - |
| | ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI - PILE |
| | DRIVING |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION |
| | |
| | 6) L-3.0 LANDSCAPE PAVING PLAN PLEASE PROVIDE AN |
| | ACCESSIBLE ROUTE WITHIN THE BOUNDARY OF THE SITE TO |
| | PUBLIC TRANSPORTATION, ACCESSIBLE PARKING, PASSENGER |
| | LOADING ZONES SIDEWALKS TO AN ACCESSIBLE ENTRANCE. |
| | 11-4.1.2(1)-(5) |
| | |
| | 7) INDICATE COMPLIANCE WITH: 11-4.29.5 DETECTABLE |
| | WARNINGS AT HAZARDOUS VEHICULAR AREAS. |
| | |
| | 8) SHEET L-3 AND A-1.00 BOTH INDICATE A COVERED DROP |
| | OFF OR PASSENGER LOADING ZONE, PLEASE PROVIDE THE CLEAR |
| | ELEVATION UNDERNEATH THE CANOPY. 11-4.6.5. |
| | |
| | 9) PASSENGER LOADING ZONES PLEASE PROVIDE ACCESS AISLE |
| | INDICATE CONDITIONS AT CURB OR DROPPED CURB AND |
| | COMPLIANCE WITH 11-4.29.5/ 11-4.6.6. |
| | |
| | 10) SHEET A-1.00 INDICATES A CUT SECTION THROUGH THE |
| | DISABLED PARKING SPOTS DETAIL# 1 SHEET |
| | A-603, SHEET IS MISSING. PLANS ARE NOT COMPLETE, |
| | ADDITIONAL INFORMATION REQUIRED 106.1.2. |
| | |
| | 11) SHEET L-5.0 & E-1 INDICATES LIGHT POLES TO BE USED |
| | IN THE PARKING LOT, FOR EACH TYPE OF LIGHT POLE AND |
| | CONFIGURATION OF LIGHTS SUPPLY CALCULATIONS FOR |
| | INSTALLATION TO 140 MPH WIND ZONE: 1805.7 DESIGNS |
| | EMPLOYING LATERAL BEARING. DESIGNS TO RESIST BOTH AXIAL |
| | AND LATERAL LOADS EMPLOYING POSTS OR POLES AS COLUMNS |
| | EMBEDDED IN EARTH OR EMBEDDED IN CONCRETE FOOTINGS IN |
| | THE EARTH SHALL CONFORM TO THE REQUIREMENTS OF SECTIONS |
| | 1805.7.1 THROUGH 1805.7.3 . |
| | |
| | 12) SHEET A-1 IN ROOM # 148 INDICATES THIS TO BE A |
| | GENERATOR ROOM. PLEASE PROVIDE CUT SHEETS FOR THE |
| | GENERATOR, TYPE OF FUEL, TANK SIZE AND REQUIREMENTS |
| | INDICATE LOCATION ON SITE PLAN, IS THIS A ABOVE THE |
| | GROUND TYPE TANK OR BURIED. WILL THIS BUILDING EVER BE |
| | USED FOR A HURRICANE SHELTER, THIS MAY EFFECT AMOUNTS |
| | OF FUEL TO BE REQUIRED.\ |
| | |
| | 13) SHEET A-1 DOES INDICATE WALL TAGS INDICATING WALLS |
| | BUT THE PLANS DO NOT PROVIDE A DETAIL SHEET IDENTIFYING |
| | WALL TYPES, THE INDEX LIST A-600 FOR WALL DETAILS , |
| | THERE ARE NO WALL DETAILS PROVIDING WALL TYPES AND FIRE |
| | RATING, PLEASE SEE TABLE 1016.1. FOR ASSEMBLY OCCUPANCY |
| | AND FIRE RATING OF CORRIDOR. |
| | |
| | 14) PLANS ARE INCOMPLETE AND A THROUGH REVIEW CAN NOT |
| | BE COMPLETED AT THIS TIME. |
| | 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS |
| | REQUIRED FOR REVIEW. |
| | |
| | 15) THERE ARE NUMEROUS A-SHEETS THAT HAVE ARCHITECTURAL |
| | DETAILS BUT THERE IS NO WRITTEN INFORMATION PROVIDED, |
| | PLANS ARE INCOMPLETE.106.3.5.1.1(4) SEE FIRE RESISTANCE |
| | CONSTRUCTION REQUIREMENTS. |
| | |
| | 16) SHEET A-101 INDICATES WHAT APPEARS TO BE A STAGE |
| | AND STAIRS ON THE WEST END OF THE MULTI-PURPOSE ROOM, |
| | SEE SECTION# 7 SHEET A-800 FOR DETAIL, SHEET A-800 IS A |
| | BLANK SHEET THAT IS SUPPOSE TO BE THE LIFE SAFETY |
| | SHEET. IF THIS IS A STAGE PLEASE PROVIDE VERTICAL |
| | ACCESSIBILITY, AND ALSO PROVIDE DETAILS FOR STAIRS AND |
| | HANDRAIL. 11-4.1.3(5). |
| | |
| | 17) NEW BUILDING STRUCTURAL, S 3-1 PLANS ARE MISSING |
| | INFORMATION ON THE MASONRY WALL SCHEDULE 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 18) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL |
| | B) WINDOWS OPERABLE WINDOWS: SINGLE HUNG, CASEMENT C) |
| | MULLIONS |
| | D) GLASS BLOCK |
| | E) GLAZED SWING DOORS |
| | F) AUTOMATIC SLIDING DOORS |
| | G) HOLLOW METAL DOORS EXTERIOR |
| | H) OVERHEAD DOORS |
| | I) TRUSS ANCHORS |
| | J) ROOF HATCHES |
| | K) ROOF ASSEMBLIES |
| | L) PRE-ENGINEERED A/C STANDS |
| | |
| | 19) 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 20) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 21) THIS ROOF IS MISSING PRODUCT COMPLIANCE REPORTS |
| | WITH THE FOLLOW ITEMS: |
| | __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES |
| | LIMITATION# 9, NO ENHANCED FASTENING ALLOWED. |
| | |
| | 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS |
| | ASSEMBLY AND NOA?S: |
| | NOA 03-0508.05 POST CAPS EXPIRED |
| | NOA 05-0105.05 RAFTER CLIPS EXPIRED |
| | |
| | 23) A-104 ROOF PLAN FAILS TO IDENTIFY ROOF DRAINAGE |
| | SYSTEM AND OR DETAILS, THE ROOF DRAIN SIZE IS NOT |
| | PROVIDED, WHAT TYPE OF SECONDARY DRAINAGE AND VERTICAL |
| | CONTRIBUTING AREAS, THIS INFORMATION IS ALSO MISSING |
| | FROM THE PLUMBING PLAN. 106.3.5.1.1(8). |
| | |
| | 24) ARCHITECTURAL PLANS ARE DEFICIENT IN INFORMATION |
| | FOR THE ENERGY CODE AND CALCULATIONS, |
| | 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE |
| | CRITERIA. |
| | |
| | 25) ELEVATIONS OF THE BREAK ROOM ARE NOT SHOWN, PLEASE |
| | PROVIDE COMPLIANCE WITH : |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK |
| | |
| | RENOVATION OF EXISTING NORTH WING : |
| | |
| | 26A) UNTIL THE DESIGN TEAM INDICATES UNDER THE NEW |
| | BUILDING PORTION OF THIS REVIEW COMMENT# 5, A REVIEW |
| | CAN NOT TAKE PLACE WITH ANY ACCURACY, IF THE NEW |
| | CONSTRUCTION IS TO BE CONSIDERED AN ADDITION TO THE |
| | EXISTING BUILDING, OR IF THE TWO BUILDINGS ARE GOING TO |
| | BE CONSIDERED ONE LARGE BUILDING OR IF A ASSUMED |
| | PROPERTY LINE WILL BE ASSUMED BETWEEN THE TWO |
| | BUILDINGS. TABLE 503, TABLE 601, TABLE 602 & TABLE |
| | 704.8. |
| | |
| | 26B) THE D-100 PLAN APPEARS THE ONLY WORK TO BE |
| | COMPLETED IN THE NORTH WING IS IN CLASSROOM# 140. |
| | PLEASE PROVIDE A DETAILED ACCOUNTING OF WHAT WORK WILL |
| | BE COMPLETED UNDER THE RENOVATION PORTION OF THE |
| | PERMIT. |
| | |
| | 26C) PLEASE ALSO INDICATE TO WHAT LEVEL ALTERATION WORK |
| | WILL ACCOMPLISHED UNDER THIS PERMIT. PLEASE SEE 2004 |
| | FBC EXISTING BUILDING CODE 301.1.THE WORK PREFORMED ON |
| | AN EXISTING BUILDING SHALL BE CLASSIFIED IN ACCORDANCE |
| | WITH THIS CHAPTER. |
| | |
| | 27) INCOMPLETE PLANS SHEET A-700 FINISH SCHEDULE IS |
| | BLANK FOR CEILING AND WALLS, THE DOOR SCHEDULE IS BLANK |
| | TO DOOR TYPE, FRAMES AND DOOR LABELS. WINDOW SCHEDULE |
| | DOESN?T INDICATE |
| | WHAT WINDOWS ARE TO BE REPLACED ON THE FLOOR PLAN AND |
| | WHICH ARE EXISTING. |
| | |
| | 28) PLEASE INDICATE IF ANY ROOFING WORK WILL TAKE PLACE |
| | ON THE EXISTING BUILDING. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER CBO |
| | PLAN REVIEW II |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |