Plan Review Notes
Plan Review Notes For Permit 07090838
Permit Number 07090838
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-21 15:45:01** DENIED 2ND REVIEW **
  
 1) NOTE:PLEASE KNOW AT THIS TIME THE ELECTRICAL
 REVIEW IS PLACED INTO A FAILED STATUS. PLEASE SEE THE
 LOCATION OF THE MAIN ELECTRICAL ROOM WILL NOT BE
 PERMITTED ON THE 2ND FLOOR WHICH IS ACTUALLY THE THIRD
 LEVEL. (GROUND, MEZZ, THEN 2ND FLR).
 PLEASE KNOW AS THIS MAY AFFECT THE STRUCTURAL
 FOUNDATION PERMIT REVIEW CAN NOT BE PASSED AT THIS
 TIME.
 THE MAIN ELECTRICAL ROOM SHALL BE A MAXIMUM OF THE
 MEZZANINE LEVEL AND SHALL CONTAIN DIRECT ACCESS FOR
 EMERGENCY PERSONNEL.
 AS THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES AT THIS TIME, PLEASE ADJUST.
 PLEASE KNOW THE PLANS COULD BE STRUCK THROUGH TO
 INCLUDE ONLY THE GROUNDING ELECTRODE SYSTEM ONLY *IF*
 THE DETAIL AS SHOWN DOES NOT AFFECT THE ELECTRICAL ROOM
 LOCATION.
  
 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, THE
 SIGNATURE ON THE SURVEY SHEETS IS *NOT* ORIGINAL AS
 REQUIRED PER FS 472.025. THIS IS NOTED AS INFORMATION
 AND NEEDS TO BE CORRECTED BEFORE PERMIT ISSUANCE.
 THIS DOES NOT AFFECT THE ELECTRICAL PLANS/REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  