| 2007-12-21 15:45:01 | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE:PLEASE KNOW AT THIS TIME THE ELECTRICAL |
| | REVIEW IS PLACED INTO A FAILED STATUS. PLEASE SEE THE |
| | LOCATION OF THE MAIN ELECTRICAL ROOM WILL NOT BE |
| | PERMITTED ON THE 2ND FLOOR WHICH IS ACTUALLY THE THIRD |
| | LEVEL. (GROUND, MEZZ, THEN 2ND FLR). |
| | PLEASE KNOW AS THIS MAY AFFECT THE STRUCTURAL |
| | FOUNDATION PERMIT REVIEW CAN NOT BE PASSED AT THIS |
| | TIME. |
| | THE MAIN ELECTRICAL ROOM SHALL BE A MAXIMUM OF THE |
| | MEZZANINE LEVEL AND SHALL CONTAIN DIRECT ACCESS FOR |
| | EMERGENCY PERSONNEL. |
| | AS THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER |
| | TRADES AT THIS TIME, PLEASE ADJUST. |
| | PLEASE KNOW THE PLANS COULD BE STRUCK THROUGH TO |
| | INCLUDE ONLY THE GROUNDING ELECTRODE SYSTEM ONLY *IF* |
| | THE DETAIL AS SHOWN DOES NOT AFFECT THE ELECTRICAL ROOM |
| | LOCATION. |
| | |
| | 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, THE |
| | SIGNATURE ON THE SURVEY SHEETS IS *NOT* ORIGINAL AS |
| | REQUIRED PER FS 472.025. THIS IS NOTED AS INFORMATION |
| | AND NEEDS TO BE CORRECTED BEFORE PERMIT ISSUANCE. |
| | THIS DOES NOT AFFECT THE ELECTRICAL PLANS/REVIEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |