Plan Review Notes
Plan Review Notes For Permit 07090838
Permit Number 07090838
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-27 13:22:20*****UNSAT*****
  
  
 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.INDICATE THE LOCATION OF THE EXISTING/PROPOSED FIRE
 HYDRANTS AND FIRE LINES FOR THIS PROJECTED SCOPE OF
 WORK.PLEASE BE ADVISED THAT FIRE LINES SHALL NOT RUN
 UNDER THE FOUNDATION OF THE STRUCTURE.
  
 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE STRUCTURE AND/OR
 THE VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722