| Date |
Text |
| 2007-10-21 08:54:03 | 2007-10-21 08:54:03 |
| | |
| | *** DENIED *** |
| | |
| | FOUNDATION PERMIT REVIEW |
| | CANNES @ WPB. |
| | |
| | 410 N ROSEMARY AVE. |
| | |
| | ** PLEASE SEE THE BELOW COMMENTS AS PLANS WILL BE |
| | COMING BACK FOR SOME CORRECTIONS. PLEASE ADDRESS THE |
| | FOLLOWING AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE ADDRESSING OF PROJECT IS TO BE |
| | DETERMINED BY THE ADDRESSING REVIEWER ALONG WITH THIS |
| | WILL BE DONE UNDER TWO SEPARATE PERMITS OR ONE. |
| | BY THE PLANS SUBMITTED THE TITLE BLOCKS NEED TO BE |
| | COMPLETED FOR ADDRESS WHICH AS APPLIED IS 410 N |
| | ROSEMARY. THIS ADDRESS IS TO DETERMINED ONCE THE |
| | ADDRESSING REVIEWER, BUILDING REVIEW AND FIRE MARSHAL |
| | HAS REVIEW SAID PLANS AND DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE CLARIFY THE LOCATION OF THE MAIN |
| | ELECTRICAL ROOM. |
| | PLEASE SUBMIT A GROUNDING ELECTRODE SYSTEM WHICH IS |
| | SHOW THE MINIMUM REQUIRED PER 250.50 OF THE NEC. PLEASE |
| | BE SURE THE PLANS SUBMITTED CONTAIN THE TITLE BLOCKS, |
| | ADDRESS OF PROJECT, SIGNED, DATED AND SEALED AS |
| | REQUIRED UNDER FAC 61G15-23.002, FS 471.025. |
| | |
| | |
| | 3) NOTE: PLEASE SEE THE SURVEY SHEETS SUBMITTED DO NOT |
| | CONTAIN THE ORIGINAL SIGNATURE AND DATE AS REQUIRED |
| | UNDER FS 472.025. |
| | PLEASE SEE THE STATEMENT ON SHEET WHICH IS REQUIRED BY |
| | THE FLORIDA ADMINISTRATIVE CODE STATES NOT VALID |
| | WITHOUT SIGNATURE AND SEAL. THE SIGNATURE ON SHEETS IS |
| | IN FACT A PHOTO-COPY AND NOT ORIGINAL. |
| | PLEASE BE SURE ALL ARE ORIGINAL AS REQUIRED. |
| | |
| | 4) NOTE: PLEASE SEE THE PERMIT APPLICATION PACKAGE |
| | CONTAINS NUMEROUS SHEETS AND DOCUMENTATION FOR LEED |
| | CERTIFICATIONS AND DOCUMENTATION OF OTHER BUILDING |
| | DEPARTMENTS, STATES, CITIES, NEWS PAPER ARTICLES ETC. |
| | PLEASE KNOW ONLY DOCUMENTATION WHICH IS RELEVANT TO |
| | BUILDING CONSTRUCTION OF THE STRUCTURE SHOULD BE |
| | SUBMITTED. THESE OTHER SHEETS WERE REVIEWED ARE NOT |
| | NEEDED AND SHOULD NOT BE SUBMITTED. IF BUILDING *HAS* A |
| | LEED CERTIFICATION AND DESIGN CRITERIA IS RELEVANT THEN |
| | PLEASE ONLY SUBMIT THOSE DOCUMENTS SHOULD BE IN PACKAGE |
| | UNDER THE ACTUAL BUILDING PERMIT APPLICATION FOR |
| | CONSTRUCTION OF BUILDING. |
| | |
| | 5) NOTE: PLEASE SEE SOME ARCHITECTURAL SHEETS SEEM TO |
| | INDICATE SLAB/FOUNDATION WORK. WILL ANY SLABS BE PART |
| | OF THIS PERMIT? WILL THERE BE ANY UNDERGROUND/SLAB |
| | CONDUITS NEEDED IN THIS SCOPE OF WORK. |
| | IF WORK IS ONLY FOR PADS/COLUMNS ONLY PLEASE PROVIDE |
| | LEGEND/DESCRIPTION FOR THESE ITEMS. |
| | |
| | 6) NOTE: PLEASE SEE BUILDING REVIEWER COMMENTS WITH |
| | RESPECT TO REQUIRED IMPACT FEES FOR PALM BEACH COUNTY |
| | BEFORE FOUNDATION PERMIT CAN BE ISSUED. |
| | |
| | 7) NOTE: PLEASE SEE THE FOLLOWING CODES WILL BE |
| | REQUIRED AS PART OF THE TITLE/COVER SHEETS FOR |
| | REFERENCING PROJECT CODES. |
| | PLEASE SEE THE FOLLOWING IS FOR THIS REVIEWER AND SOME |
| | OF THESE WILL BE THE SAME AS REQUIRED BY OTHER TRADES. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | 2003 NFPA-20 |
| | |
| | |
| | 8) NOTE: PLEASE ALSO SEE NOTES FROM BUILDING REVIEWER |
| | AS FOR THE REQUIRED STATEMENT FOR ALL DESIGNERS. PLEASE |
| | SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH |
| | REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON ALL |
| | ARCH AND ENG SHEETS. |
| | THIS WAS DONE ON THE ARCHITECTS SHEETS HOWEVER NOT |
| | ALL. |
| | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 OF THE FLORIDA STATUTES". |
| | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| | PLANS. |
| | |
| | ** PLEASE BE SURE THAT THREE SETS OF ALL |
| | PLANS/DOCUMENTS ARE SUBMITTED FOR REVIEW AND STAMPING. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-21 07:57:42 | 2001-10-21 07:57:42 |
| | |
| | REVIEW IN PROGRESS |
| 2007-10-20 19:48:33 | 2007-10-20 19:48:33 |
| | |
| | IN ELECTRICAL FOR REVIEW. |