2007-10-23 16:50:29CANNES RESIDENCES
 410 N ROSEMARY ST
 OCT. 24,2007
  
 BUILDING PLAN REVIEW/ FOUNDATION ONLY
 PERMIT: 07090838
 ADD: 410 N ROSEMARY
 CONT: TRENTO CONSTRUCTION CO.
 TEL: (786)271-9448
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 1F) THE PERMIT APPLICATION DESCRIPTION OF PROJECT
 INDICATES FOUNDATION PERMIT ONLY, DOES THE SHEET PILING
 TO BE UNDER THIS REVIEW, IS THE 18 INCH FLOOR SLAB TO
 BE PART OF THIS PERMIT.
  
 2A) PEDISTAL TYPE BUILDING. TABLE 601 THE PROPOSED
 BUILDING IS INDICATED TO PASS OVER PROPERTY LINES WITH
 CONSTRUCTION. THE PERMIT APPLICATION REQUEST THE
 PROPERTY CONTROL NUMBER FOR THE PROPERTY FOR THIS
 STRUCTURE TO BE BUILT UPON AND NUMEROUS LOTS AND A
 STREET RIGHT OF WAY ARE INVOLVED. PLANS INDICATE A
 PARKING GARAGE BASEMENTBENEATH 4TH STREET BETWEEN N.
 ROSEMARY AND WEST RAILROAD AVENUE. PLEASE PROVIDE A
 UNITY OF PROPERTY AND OR A RESTRICTIVE COVANENT WITH
 THE LOTS ON BOTH SIDES OF 4TH ST AND ALSO INDICATE THE
 ABANDOMENT OF 4TH ST BETWEEN WEST RAILROAD AVENUE AND
 ROSEMARY.
  
 2B) PEDISTAL TYPE BUILDING. THE SECOND ISSUE IS WITH
 THE ELECTRICAL PLANS WITH TWO SERVICES, PLEASE SEE
 ELECTRICAL COMMENTS DEALING WITH THIS ISSUE. NOTE A
 SINGLE BUILDING ONLY RECEIVES ONE SEREVICE, WITH
 SPECIAL APPROVAL 2 ELECTRIC SERVIVES CAN BE REVIEWED
 AND INSTALLED SEE ELECTRICAL REQUIREMENTS.TABLE 601. A
 MEETING WILL NEED TO BE CALLED TO DISCUSS HOW THE MEP
 SERVICES , FIRE ALARM, FIRE COMMAND ROOMS &GENERATORS
 WILL INTERACT IN THE FOUNDATION AND TWO TOWERS. NOTE AT
 THIS TIME THE FOUNDATION PERMIT MAY NOT BE EFFECTED BUT
 BUILDING PERMIT WOULD BE EFFECTED.
  
 3)SOILS REPORTS SUBMITTED FROM ARDAMAN & ASSOCIATES,
 INC FILE # 07-2085 INDICATES SHEET PILE WILL BE
 REQUIRED AROUND THE PERIMETER OF THE SITE, PLEASE
 PROVIDE SOILS INFORMATION AS TO HOW DEEP THE SHEET PILE
 WILL NEED TO GO.SHEET S1.1 NOTE 2 INDICATES SHEET
 PILE CALCULATIONS ARE TO BE SIGNED AND SEALED FOR
 REVIEW AND APPROVAL OF THE DESIGNPROFESSIONAL. NO SUCH
 PLAN NOR CALCULATION HAS BEEN SUBMITTED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 4) THE SOILS REPORTCOMPLETED BY ARDAMAN RAISES A
 CONCERN WHERE SOILS SETTLEMENT MAY DROP TO 12 INCHES
 WITHIN A FOOT OF THE SHEETPILE AND TWO INCHES WWITH IN
 FIVE FEET OF THE DRIVEN SHEET PILE.
 PLEASE TAKE NOTE OF THE CITIES CONCERNS, SEE
 ENGINEERING COMMENTS.WILL SOILS PINS BE INCORPORATED
 IN TO THE CITY RIGHT OF WAY?
  
 5) NOTE, FPL VAULT, 3202.1.2 VAULTS AND OTHER ENCLOSED
 SPACES. THE CONSTRUCTION AND UTILIZATION OF VAULTS AND
 OTHER ENCLOSED SPACE BELOW GRADE SHALL BE SUBJECT TO
 THE TERMS AND CONDITIONS OF THE AUTHORITY OR
 LEGISLATIVE BODY HAVING JURISDICTION. PLEASE SEE FPL
 REQUIREMENTS FOR HR RATINGS FOR WALLS AND ROOF SLAB.
  
 6)THRESHOLD BUILDING PLEASE SEE SHEET S1.1(F) NOTE
 REFERS TO SHEET S4.3 REFERS TO THE REQUIRED THRESHOLD
 INSPECTION PLAN REQUIREMENTS. THE FOUNDATION PLANS
 SUBMITTED STOP AT S4.2(F).FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 7)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S AND OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR WIND
 LOADS,2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10) PLEASE SEE ATTACHED SHEET FOR REMAINDER OF PERMIT
 FEES AND STATE RADON FEES TO BE PAID BEFORE THE
 ISSUANCE OF THE PERMIT.FL S S 166.201/ 166.222/ WPB
 ADMINISTRATIVE3333.00.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
 NOTE: PROVIDED COPY OF GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 CONFORMING TO 468, PARTXII FL S S & WPB AMENDMENTS
  
  
  