2007-10-16 10:51:06DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 &
 R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  