| Plan Review Notes For Permit 07090837 |
| Permit Number |
07090837 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-16 10:51:06 | DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 & | | | R4101 SWIMMING POOLS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA | | | ACCESSIBILITY CODE. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. | | | R4101.9 WATER SUPPLY, LOCAL ORD. | | | #2853-95, BACKFLOW REQUIRED ON WATER | | | SERVICE.(ADD TO NOTES) | | | | | | 2. FBC-2004 SEC. 424.2.14.1, OR | | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED, PLEASE SUBMIT) | | | | | | 3. FBC-2004 SEC. 424.2.14.2, OR | | | FBCR-2004 SEC. R4101.14.2 WATER | | | RETENTION, PROVIDE A POSITIVE MEANS OF | | | RETAINING WATER IN THE HEATER WHEN PUMP | | | IS SHUT OFF.(MANUFACTURE SHEETS | | | REQUIRED, PLEASE SUBMIT) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|