2008-01-02 08:50:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9 A-1 IS CALLING FOR R4.1
 WALL INSULATION, TABLE 6C-1 ON BACK OF ENERGY
 CALCULATIONS STATES THE MINIMUM INSULATION FOR BLOCK
 WALLS IS R-5, YOU MAY NOT PICK AND CHOSE. SEE 2004 FBC
 13-602.1.A.1, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS LINE 10A IS CALLING FOR R-19
 ATTIC INSULATION, TABLE 6C-1 ON BACK OF ENERGY
 CALCULATIONS STATES THE MINIMUM INSULATION FOR ATTICS
 IS R-30, YOU MAY NOT PICK AND CHOSE. SEE 2004 FBC
 13-604.1.C.1, PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS ARE CALLING FOR 43,978
 TOTAL COOLING BTU'S, MECHANICAL PLAN PAGE 3/3 IS
 SHOWING 58,200 TOTAL COOLING BTU'S, THE PLANS CAN ONLY
 CALL FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS (A
 5 TO SYSTEM IS TO LARGE) SEE 2004 FBC 13-607.1.ABC.1.1,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]