| Plan Review Notes For Permit 07090828 |
| Permit Number |
07090828 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-16 10:33:03 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600C-04R, SEE | | | 2004 FBC 13-600.3.C. | | | | | | 2) COOLING LOAD CALCULATIONS ARE SHOWING THE UNDER AIR | | | AREA AS 1,916 SQUARE FEET, PLANS SHOW THE UNDER AIR | | | SQUARE FEET AS 1,701,PLEASE CORRECT COOLING LOAD | | | CAL'S. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|