Plan Review Notes
Plan Review Notes For Permit 07090828
Permit Number 07090828
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-16 10:33:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600C-04R, SEE
 2004 FBC 13-600.3.C.
  
 2) COOLING LOAD CALCULATIONS ARE SHOWING THE UNDER AIR
 AREA AS 1,916 SQUARE FEET, PLANS SHOW THE UNDER AIR
 SQUARE FEET AS 1,701,PLEASE CORRECT COOLING LOAD
 CAL'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]