 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET 3/3, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THERE IS A SMALL APPLIANCE CIRCUIT ADDED TO THE
 PANEL SCHEDULE, BUT NO WORK SHOWN IN AREAS THIS WOULD
 SERVE, PLEASE CLARIFY.
  
 2} THERE ARE REFERENCES IN THE ELECRICAL NOTES TO BOTH
 10000 AND 22000K AIC RATINGS. SPECIFY THE CORRECCT ONE
 TO BE USED PER 110.9 AND 110.10.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE. THERE ARE REFERENCES TO THE 1996 AND 2002 NEC
 ON THE PLAN.
  