| Notes |
| Date |
Text |
| 2007-10-05 16:11:29 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | ALL COMMENTS RELATE TO SHEET 3/3, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} THERE IS A SMALL APPLIANCE CIRCUIT ADDED TO THE | | | PANEL SCHEDULE, BUT NO WORK SHOWN IN AREAS THIS WOULD | | | SERVE, PLEASE CLARIFY. | | | | | | 2} THERE ARE REFERENCES IN THE ELECRICAL NOTES TO BOTH | | | 10000 AND 22000K AIC RATINGS. SPECIFY THE CORRECCT ONE | | | TO BE USED PER 110.9 AND 110.10. | | | | | | 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS | | | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT | | | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS | | | CHANGE. THERE ARE REFERENCES TO THE 1996 AND 2002 NEC | | | ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|